MEAN WELL RT-85A Data Sheet онлайн

MEAN WELL RT-85A Data Sheet онлайн
Protectiontype: Hiccupmode,recoversautomaticallyafterfaultconditionisremoved
SPECIFICATION
MODEL RT-85A RT-85B RT-85C RT-85D
DCVOLTAGE
RATEDCURRENT
OUTPUT
VOLTAGE ADJ.RANGE
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
ACCURRENT (Typ.)
INPUT
INRUSHCURRENT (Typ.)
LEAKAGECURRENT
SAFETY STANDARDS
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
5V
CH1
12V
CH2
-5V
CH3
12V
CH2
-12V
CH3
5V
CH1
5V
CH1
15V
CH2
24V
CH2
-15V
CH3
12V
CH3
5V
CH1
8A 3.5A 0.5A 3.5A 0.5A 7A 6A3A 2A0.5A 1A8A
2~10A 0.3~4A 0~1A 0.3~4A 0~1A 2~10A 2~10A0.3~4A
0.3~2.5A
0~1A 0.1~1A2~10A
84.5W 88W 87.5W 90W
80mVp-p
120mVp-p
100mVp-p
120mVp-p
120mVp-p
80mVp-p 80mVp-p
120mVp-p
150mVp-p
120mVp-p
120mVp-p
80mVp-p
CH1:4.75~5.5V CH1:4.75~5.5V CH1:4.75~5.5V CH1:4.75~5.5V
2.0% 5.0% 6.0% 5.0% 6.0% 2.0% 2.0%+3,-7% 6.0% 6.0%
6.0%
2.0%
0.5% 1.0% 1.0% 1.0% 0.5% 0.5%1.0% 1.0%
5.0%
1.0% 1.0%0.5%
1.0% 3.0% 6.0% 3.0% 6.0%
1.0%
1.0% 1.0%3.0% 3.0%6.0%1.0%
500ms,20ms/230VAC1200ms,30ms/115VAC atfullload
100ms/230VAC18ms/115VAC atfullload
88~264VAC125~373VDC (Withstand300VACsurgefor5sec.Withoutdamage)
47~63Hz
76% 77% 79%76%
CH1:5.75~6.75V
2.5A/115VAC1.5A/230VAC
COLDSTART 40A/230VAC
<2mA /240VAC
110~150% ratedoutputpower
Protectiontype:Hiccupmode,recoversautomaticallyafterfaultconditionisremoved
UL60950-1, TUVEN60950-1approved
CompliancetoEN55022(CISPR22)ClassB, EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,EN61000-6-2(EN50082-2),heavyindustrylevel,criteria A
-25~+70
(Referto"DeratingCurve")
20~90%RH non-condensing
-40~+85 ,10~95%RH
0.03%/ (0~50 )on+5Voutput
10~500Hz,5G10min./1cycle,periodfor 60min.eachalongX, Y,Zaxes
215Khrsmin.MIL-HDBK-217F(25 )
159*97*38mm(L*W*H)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 20% to 100% rated load, and other output at 60% rated load.
6. Each output can work within current range. But total output power can't exceed rated output power.
7. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
8. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up time.
For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
0.6Kg;24pcs/15.4Kg/0.7CUFT
85W TripleOutputSwitchingPowerSupply
RT- 8 5 se ri es
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC/25 /70%RH
CURRENTRANGE Note.6
RATEDPOWER Note.6
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
LINEREGULATION Note.4
LOADREGULATION Note.5
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note7)
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
LED indicator for power on
100% full load burn-in test
All using 105
Withstand 300VAC surge input for 5 second
High operating temperature up to 70
Withstand 5G vibration test
High efficiency, long life and high reliability
3 years warranty
long life electrolytic capacitors
Features :
OUTPUTNUMBER
EMCIMMUNITY
EMCEMISSION
FileName:RT-85-SPEC2011-08-19
Скачать