Daikin FWE06DATN5V3-L [7/200] Mounting the fan coil unit

Daikin FWE03DATN5V3-L [7/200] Mounting the fan coil unit
5 Installation
Installation manual
7
FWE03~11D
Fan coil units
3P443944-5E – 2019.09
Electrical characteristics
FWE-D
Phase 1N~
Frequency 50Hz
Voltage range 220~240V
Voltage tolerance ±10%
Maximum running current 0.46A
Overcurrent fuse 16A
Specifications for field wiring
Wire Size (mm²) Length
Power supply
wiring
H05VV-U3G
(a)(b)
According to the
applicable
legislation ≤4.0
Remote
controller and
unit
transmission
wiring
Sheathed wire 2
conductors
(c)
0.75~1.25 ≤500m
(d)
(a)
Only in case of protected pipes. Use H07RN-F in case
of no protection.
(b)
Run electrical wiring through a conduit to protect against
external forces.
(c)
Use double insulation wire for remote controller (sheath
thickness ≥1mm) or run wires through a wall or conduit
so that the user cannot come in contact with them.
(d)
The length shall be the total extended length in a system
with group control.
5 Installation
5.1 Mounting the fan coil unit
INFORMATION
The spacing between ceiling and unit should be ≥10mm
and the suction space should be ≥150mm.
INFORMATION
All the above parts are field supplied. For installation other
than standard installation, contact your local dealer for
advice.
5.1.1 Horizontal installation
10≤
10≤
1 Make the required ceiling opening for installation in an
applicable place.
It may be necessary to reinforce the suspended ceiling frame
to keep the ceiling level and to prevent it from vibrating.
Consult the builder for details.
2 Install the suspension bolts. Use either W3/8 or M10 size bolts.
Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to
reinforce the ceiling in order to bear the weight of the unit. Refer
to it to check for points requiring reinforcing. Adjust the
clearance from the ceiling before proceeding further.
a
b
c
d
e
a Ceiling slab
b Anchor
c Long nut or turn-buckle
d Suspension bolt
e Suspended ceiling
3 Install the unit temporarily.
Attach the hanger bracket to the suspension bolt. Fix the unit
securely.
a
b
c
d
a Nut (field supply)
b Washer (field supply)
c Hanger bracket
d Double nut (field supply)
4 Adjust the unit to the correct position for installation.
1/100
5 Check if the unit is horizontally levelled.
Do not install the unit tilted. If the unit is tilted against the
direction of the condensate flow (drain piping side raised), it
will cause water to drip.
Check if the unit is levelled at all 4 corners with a water level
or a water-filled plastic tube.
a
b
a Plastic tube
b Level