MEAN WELL HBG-100P-60B [2/7] Hbg 100p

MEAN WELL HBG-100P-60B [2/7] Hbg 100p
SPECIFICATION
MODEL
OUTPUT
VOLTAGE RANGE Note.3
FREQUENCY RANGE
POWER FACTOR
EFFICIENCY (Typ.) Note.5
AC CURRENT
INPUT
INRUSH CURRENT(Typ.)
LEAKAGE CURRENT
EMC IMMUNITY
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVER TEMPERATURE Note.10
OVER VOLTAGE
47 ~ 63Hz
<0.75mA / 277VAC
20 ~ 95% RH non-condensing
-40 ~ +80, 10 ~ 95% RH
±0.03%/ (0 ~ 45)
ENVIRONMENT
EMC EMISSION
SAFETY &
EMC
PROTECTION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
TOTAL HARMONIC DISTORTION
OVER CURRENT
SAFETY STANDARDS
COLD START 60A(twidth=550 s measured at 50% Ipeak) at 230VACμ ; Per NEMA 410
MAX. No. of PSUs on 16A
CIRCUIT BREAKER
4 units (circuit breaker of type B) / 8 units (circuit breaker of type C) at 230VAC
(Please refer to "STATIC CHARACTERISTIC" section)
90 ~ 305VAC 127 ~ 431VDC
95 ~ 108%
PF0.96/115VAC, PF0.96/230VAC, PF0.94/277VAC@full load
(Please refer to "POWER FACTOR (PF) CHARACTERISTIC" section)
THD< 20%(@load60%/115VC,230VAC; @load75%/277VAC)
(Please refer to “TOTAL HARMONIC DISTORTION(THD)” section)
Ta=-40 ~ +45 (Please refer to “ OUTPUT LOAD vs TEMPERATURE” section)
2000ms / 115VAC 500ms / 230VAC
21.6 ~ 36V
2.7A
97.2W
HBG-100P-36
36 ~ 60V
1.6A
96W
HBG-100P-60
28.8 ~ 48V
2A
96W
HBG-100P-48
1.62 ~ 2.7A
1.2 ~ 2A
1.0 ~ 1.6A
91%
91.5%
91%
41 ~ 49V
65 ~ 75V
54 ~ 63V
10 ~ 500Hz, 2G 12min./1cycle, period for 72min. each along X, Y, Z axes
346.8Khrs min. MIL-HDBK-217F (25)
Refer to mechanical specification
UL8750,CSA C22.2 No.250.13-12; ENEC EN61347-1,EN61347-2-13,EN62384, GB19510.1,GB19510.14,EAC TP TC 004 approved
I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH
Compliance to EN55015, EN61000-3-2 Class C (@load60%) ; EN61000-3-3, GB17743, GB17625.1,EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61547,light industry level(surge immunity:Line-Earth:4KV,Line-Line:2KV),EAC TP TC 020
HBG-100P s eries
100W Constant Current Mode LED Driver
Adjustable for A-Type only (via built-in potentiometer)
1.1A / 115VAC 0.5A / 230VAC 0.45A / 277VAC
Shut down o/p voltage, re-power on to recovery
Shut down o/p voltage, re-power on to recovery
0.3Kg; 45pcs/14.5Kg/1.60CUFT
RATED CURRENT
RATED POWER
CURRENT ADJ. RANGE
SET UP TIME Note.4
CURRENT TOLERANCE
CONSTANT CURRENT REGION Note.2
OPEN CIRCUIT VOLTAGE(max.)
CURRENT RIPPLE
±5.0%
5.0% max. @rated current
1.AllparametersNOTspeciallymentionedaremeasuredat230VACinput,ratedcurrentand25ofambienttemperature.
2.Pleasereferto"DRIVINGMETHODSOFLEDMODULE".
3.De-ratingmaybeneededunderlowinputvoltages.Pleasereferto“STATICCHARACTERISTIC”sectionsfordetails.
4.Lengthofsetuptimeismeasuredatfirstcoldstart.TurningON/OFFthepowersupplymayleadtoincreaseofthesetuptime.
5.TheDAtypepowersupplyislessefficientthanthetypicalefficiencyinspecificationby1%.
6.Thedriverisconsideredasacomponentthatwillbeoperatedincombinationwithfinalequipment.SinceEMCperformancewillbeaffectedbythe
completeinstallation,thefinalequipmentmanufacturersmustre-qualifyEMCDirectiveonthecompleteinstallationagain.
7.Thisseriesmeetsthetypicallifeexpectancyof>50,000hoursofoperationwhenTaisabout45orless.
8.PleaserefertothewarrantystatementonMEANWELL'swebsiteathttp://www.meanwell.com
9.Theambienttemperaturederatingof3.5/1000mwithfanlessmodelsandof5/1000mwithfanmodelsforoperatingaltitudehigherthan2000m(6500ft).
10.Allfunctionaltestingmustbefilledwithpotting,includingOTPfunction.
37V
62V
49V
Constant current limiting, recovers automatically after fault condition is removed
DALI STANDARDS
Compliance to IEC62386-101, 102, 207 for DA-Type only
File Name:HBG-100P-SPEC 2018-12-06