ELECTRICAL WIRING CONNECTION
X1
IMPORTANT: * These values are for information only. They should be checked and selected to comply with local and/or
national codes and regulations. They are also subject to the type of installation and size of conductors.
** The appropriate voltage range should be checked with label data on the unit.
There must be an all pole disconnection in the supply mains with a contact separation of at least 3mm.
Model FWG05AAT(F) FWG08AAT(F) FWG11AAT(F)
Voltage Range**
220V-240V/~/50Hz + !
Recommended time delay fuse* (A) 222
Power Supply Cable* (mm
2
) 1.5 1.5 1.5
Interconnection cable size* (mm
2
)
Number of conductors
333
Model: FWG05/08/11AAT
X2
X3
FCU 1 FCU 2
LN1CVLV
L
N
CHILLER
Model: FWG05/08/11AAF
L
N
3WV
X1
X2
FCU 1
HVLV
CHILLER
NLN1CVLV N
3WV
LN1CVLV N
FCU 3
N1 CVLV N2 L N
3WV
FCU 2
HVLV N1 CVLV N2 L N
3WV3WV
L
N
X3
3 Way Valve
Relay
3WV
X1, X2,X3
Field Supply Wire
3 Way Valve
Relay
3WV
X1, X2,X3
Field Supply Wire
L
N
L
N
3WV3WV
FCU 3
HVLV N1 CVLV N2 L N
3WV3WV
L
N
!
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
All power line must be from the
same phase.
!
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
All power line must be from the
same phase.
1 IM-CKEW(DC)-1013(5)DAIKIN-EN.i9 91 IM-CKEW(DC)-1013(5)DAIKIN-EN.i9 9 12/27/16 8:45:03 AM12/27/16 8:45:03 AM

Содержание

English ELECTRICAL WIRING CONNECTION IM PORTANT These values are for information only They should be checked and selected to comply with local and or national codes and regulations They are also subject to the type of installation and size of conductors The appropriate voltage range should be checked with label data on the unit There must be an all pole disconnection in the supply mains with a contact separation of at least 3mm Model FWG05 08 11AAT All power line must be from the same phase Model FWG05 08 11AAF All power line must be from the same phase Model FWG05AAT F Voltage Range Recommended time delay fuse FWG08AAT F FWGllAAT F 220V 240V 50Hz A Power Supply Cable in in2 Interconnection cable size Number of conductors in in2 2 2 2 1 5 1 5 1 5 3 3 3 1 9