Functional Control ESIE10-01
2–42 Part 2 – Functional Description
3
1
2
4
5
Stopping Normal Shutdown
A normal shutdown requires the circuit to pumpdown before the compressor is turned off. This is
to be done by closing the EXV, and closing the liquid line solenoid (if present) while the compres-
sor is running.
The circuit should do a normal shutdown (pumpdown) if any of the following are true:
Staging logic requires this circuit to stop.
Unit State is Pumpdown.
A pumpdown alarm occurs on the circuit.
Circuit switch is open.
Circuit Mode set point is set to Disable.
BMS Circuit Mode set point is set to Off.
The normal shutdown is complete when any of the following are true:
Evaporator Pressure is less than the Pumpdown Pressure set point.
Circuit has been pumping down for longer than the Pumpdown Time Limit set point.
Rapid Shutdown
A rapid shutdown requires the compressor to stop and the circuit to go to the Off state immedi-
ately.
The circuit should do a rapid shutdown if either of these conditions occur at any time:
Unit State is Off.
A rapid stop alarm occurs on the circuit.