General Outline ESIE10-01
1–82 Part 1 – System Outline
3
11
4
5
The pressure drop at the selected working condition will be:
Notes: If the calculated evaporator water pressure drop is below 10 kPa or above 100 kPa please contact the
factory for dedicated evaporator.
PD
2
(kPa) = 73 (kPa) x
PD
2
(kPa) = 52 (kPa)
1.8
25.61 (l/s)
30.90 (l/s)