Daikin UAT320AMY12 [6/43] Specifications

Daikin UAT700AMY1 [6/43] Specifications
3
1
2
Rooftops • Cooling only
2
Cooling only • R-22 • UAT-AMY1
2 Specifications
2-1 CAPACITY AND POWER INPUT UAT180AMY1 UAT240AMY1 UAT280AMY1 UAT320AMY1 UAT450AMY1
Cooling Minimum kW 17.291 23.446 29.307 33.996 43.961
Power Input Cooling Nominal kW 5.61 8.10 10.50 11.56 15.60
EER Nominal 3.08 2.89 2.79 2.94 2.82
2-1 CAPACITY AND POWER INPUT UAT560AMY1 UAT700AMY1 UAT850AMY1 UATC10AMY1 UATC12AMY1
Cooling Minimum kW 58.614 73.268 87.921 96.420 118.401
Power Input Cooling Nominal kW 20.70 27.56 35.96 39.87 46.80
EER Nominal 2.83 2.66 2.44 2.42 2.53
2-2 TECHNICAL SPECIFICATIONS UAT180AMY1 UAT240AMY1 UAT280AMY1 UAT320AMY1 UAT450AMY1
Evaporator Control Air Discharge Ducted
Operation SLM Controller SLM Controller SLM Controller SLM Controller Sequential Controller
Air Flow Rate Cooling m³/min 51 80 100 102 160
External Static Pressure Pa 98 98 98 98 196
Piping
connections
Condensation
Drain Size
Diameter
(OD)
mm 25.4 25.4 25.4 25.4 25.4
Condensor Casing Colour Light Grey
Material Electro galvanised mild steel
Dimensions Unit Height mm 1,000 1,000 1,000 1,000 1,200
Width mm 1,100 1,300 1,300 1,300 1,990
Depth mm 1,530 1,530 1,530 1,530 1,670
Packing Height mm 1,090 1,090 1,090 1,090 1,320
Width mm 1,250 1,450 1,450 1,450 2,100
Depth mm 1,680 1,680 1,680 1,680 1,810
Condensor Weight Unit kg 295 370 400 425 665
Heat
Exchanger
Dimensions Face
Area
1.41 1.41 1.42 1.42 2 x 1.25
Condensor Air Flow Rate Cooling m³/min 127 160 160 227 320
Motor Output W 400 550 550 580 550
CompressorQuantity 11112
Compressor Motor Type Scroll type
Operation
Range
Cooling Min °CDB 20°C
Max °CDB 54°C
Condensor Sound Level
(nominal)
Sound
power
dBA6365666870
Refrigerant Type R-22
Charge kg 5.2 4 5.9 6.2 2 x 4.5
Control Thermal expansion
valve
Capillary tube Capillary tube Thermal expansion
valve
Capillary tube
Safety Devices High pressure switch
Phase sequencer
Discharge thermostat setting
Notes All specifications are subjected to change by the manufacturer without prior notice.
All units are being tested and comply to ISO5151.
Nominal cooling and heating capacity are based on the following conditions: cooling -27°CDB/19°CWB indoor and
35°CDB/24°CWB outdoor, heating -20°CDB indoor and 7°CDB/6°CWB outdoor.
Sound pressure levels are according to JIS B 8615 standard. Position of the measurement is 1m in front and 1m below
the unit.
Designation based on cooling cycle.
2-2 TECHNICAL SPECIFICATIONS UAT560AMY1 UAT700AMY1 UAT850AMY1 UATC10AMY1 UATC12AMY1
Evaporator Control Air Discharge Ducted
Operation Sequential Controller
Air Flow Rate Cooling m³/min 190 227 272 312 354
External Static Pressure Pa 196 294 294 294 294
Piping
connections
Condensation
Drain Size
Diameter
(OD)
mm 25.4 25.4 25.4 25.4 25.4
Condensor Casing Colour Light Grey
Material Electro galvanised mild steel

Содержание

Скачать