Daikin EUC8JBT1 [8/10] All field piping must be installed by a licensed refrigeration technician and must comply with relevant european and na tional regulations
![Daikin EFV5JBW1 [8/10] All field piping must be installed by a licensed refrigeration technician and must comply with relevant european and na tional regulations](/views2/1696706/page8/bg8.png)
Instruction manual
EUC3JB
EUC5JB
EUC8JB
EUC10JB
Water-cooled
air conditioners
EFR3JB
EFR5JB
EFR8JB
EFR10JB
Split air-cooled
air conditioners
EFV3JB
EFV5JB
EFV8JB
EFV10JB
- Pipe connections must be done from the side of the unit (refer
to the outlook drawing for the required piping diameters).
- Standard refrigerant charge of the EFR-JB evaporating unit is
based on combination with ECR-D units and 8m pipe length.
- The EFR-JB units are shipped with a R22 holding charge. For
normal operation, an additional charge of R22 is required to
reach the standard refrigerant charge.
EFR3JB+ EFR5JB+ EFR8JB+ EFR10JB+
ECR3DV1 ECR5DV1 ECR8DV1 ECR10DV1
holding R22 charge 0.5kg 0.5kg 0.5kg 0.5kg
standard R22 charge 2.2kg 3.3kg 5.9kg 6.6kg
- If the piping length between the condenser unit and the air
conditioner exceeds 8m, additional refrigerant R22 must be
charged:
EFR3JB+ EFR5JB+ EFR8JB+ EFR10JB+
ECR3DV1 ECR5DV1 ECR8DV1 ECR10DV1
additional R22 charge 50g/m 100g/m 170g/m 170g/m
3.3. Supply cooling water (for EUC-JB units only)
- Be sure to interlock so, that the compressor will not come into
operation unless the cooling water pump is operated. For this
purpose spare terminals 9 and 10 are provided in the
switchbox. Refer to the wiring diagram on the unit with regard
to the connection method.
- In case well water is used, operate the pump after opening the
water inlet and outlet valves.
- In case cooling tower water is used, operate the fan and pump
of the cooling tower after opening the water inlet and outlet
valves.
3.4. Water quality specifications (for EUC-JB units only)
circulating supply tendency if out of
water water criteria
Items to be controlled
pH at 25°C 6.5~8.2 6.0~8.0 corrosion + scale
Electrical [mS/m] at 25°C < 80 < 30 corrosion + scale
conductivity
Chloride ion [mgCl
-
/l] < 200 < 50 corrosion
Sulfate ion [mgSO
4
2-
/l] < 200 < 50 corrosion
M-alkalinity (pH4.8) [mgCaCO
3
/l] < 100 < 50 scale
Total hardness [mgCaCO
3
/l] < 200 < 70 scale
Calcium hardness [mgCaCO
3
/l] < 150 < 50 scale
Silica ion [mgSiO
2
/l] < 50 < 30 scale
iItems to be referred to
Iron [mgFe/l] < 1.0 < 0.3 corrosion + scale
Copper [mgCu/l] < 0.3 < 0.1 corrosion
Sulfide ion [mgS
2-
/l] not not corrosion
detectable detectable
Ammonium ion [mgNH
4
+
/l] < 1.0 < 0.1 corrosion
Remaining chloride [mgCl/l] < 0.3 < 0.3 corrosion
Free carbide [mgCO
2
/l] < 4.0 < 4.0 corrosion
Stability index 6.0~7.0 - corrosion + scale
3.5. Controller
1) OFF button 6) thermostat
2) fan button 7) pilot lamp fan
3) cooling button 8) pilot lamp cooling
4) heating button 9) pilot lamp heating
5) cooling/heating button 10) pilot lamp fault
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT
OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-
CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT.
BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH
ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT
AND HAVE THEM INSTALLED BY A PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS
CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION.
1. INTRODUCTION
The Daikin EUC-JB series are water-cooled air conditioners with
cooling only application for indoor installation. The standard
operation range of the EUC-JB units ranges from +15°C to
+48°C condenser water inlet temperature.
The Daikin EFV-JB series are air-cooled air conditioners with
cooling only application for indoor installation. The EFV-JB air
conditioners can be combined with the Daikin ERC-C* or ER-D*
condensing units. The standard operation range of the units
ranges from 19°CDB to 32°CDB indoor ambient temperature.
The Daikin EFR-JB series are air-cooled air conditioners with
cooling only application for indoor installation. The EFR-JB air
conditioners can be combined with the Daikin ECR-D condenser
units. The standard operation range of the units ranges from
19°CDB to 32°CDB indoor ambient temperature.
2. DESCRIPTION OF THE UNIT
- Wiring diagram: refer to the sticker on the unit
- Outlook drawing: refer to the outlook drawings at the end of this
manual. ( = service space)
3. INSTALLATION
All field wiring and components must be installed by a licensed
electrician and must comply with relevant European and na-
tional regulations.
The field wiring must be carried out in accordance with the wir-
ing diagrams.
Be sure to use a dedicated power circuit. Never use a power
supply shared by another appliance.
Ensure that a protective guard is installed in front of the air
outlet to prevent that the fan blades be touched. The protec-
tion must comply with relevant European and national regula-
tions.
3.1. Power circuit and cable requirements
EUC3JB EUC5JB EUC8JB EUC10JB
W1 T1 W1 T1 W1 T1 W1 T1
recommended fuses [A] 12aM 16aM 16aM 25aM 20aM 32aM 25aM 40aM
EFV3JB EFV5JB EFV8JB EFV10JB
W1 T1 W1 T1 W1 T1 W1 T1
recommended fuses [A] 2aM 4aM 4aM 4aM 4aM 6aM 6aM 8aM
wire size
[mm
2
] 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
interconnection
EFR3JB EFR5JB EFR8JB EFR10JB
W1 T1 W1 T1 W1 T1 W1 T1
recommended fuses [A] 12aM 16aM 16aM 25aM 20aM 40aM 32aM 63aM
wire size
[mm
2
] 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
interconnection
3.2. Refrigerant piping (only for EFV-JB and EFR-JB units)
All field piping must be installed by a licensed refrigeration
technician and must comply with relevant European and na-
tional regulations.
Содержание
- Instruction manual 1
- Water cooled air conditioners split air cooled air conditioners 1
- All field piping must be installed by a licensed refrigeration technician and must comply with relevant european and na tional regulations 8
- All field wiring and components must be installed by a licensed electrician and must comply with relevant european and na tional regulations 8
- Be sure to interlock so that the compressor will not come into operation unless the cooling water pump is operated for this purpose spare terminals 9 and 10 are provided in the switchbox refer to the wiring diagram on the unit with regard to the connection method in case well water is used operate the pump after opening the water inlet and outlet valves in case cooling tower water is used operate the fan and pump of the cooling tower after opening the water inlet and outlet valves 8
- Be sure to use a dedicated power circuit never use a power supply shared by another appliance 8
- Controller 8
- Description of the unit 8
- Efr3jb efr5jb efr8jb efr10jb 8
- Efr3jb efr5jb efr8jb efr10jb ecr3dv1 ecr5dv1 ecr8dv1 ecr10dv1 8
- Efv3jb efv5jb efv8jb efv10jb 8
- Ensure that a protective guard is installed in front of the air outlet to prevent that the fan blades be touched the protec tion must comply with relevant european and national regula tions 8
- Euc3jb euc5jb euc8jb euc10jb 8
- If the piping length between the condenser unit and the air conditioner exceeds 8m additional refrigerant r22 must be charged 8
- Improper installation or attachment of equipment or accessories could result in electric shock short circuit leaks fire or other damage to the equipment be sure only to use accessories made by daikin which are specifically designed for use with the equipment and have them installed by a professional if unsure of installation procedures or use always contact your daikin dealer for advice and information 8
- Installation 8
- Instruction manual 8
- Introduction 8
- Pipe connections must be done from the side of the unit refer to the outlook drawing for the required piping diameters standard refrigerant charge of the efr jb evaporating unit is based on combination with ecr d units and 8m pipe length the efr jb units are shipped with a r22 holding charge for normal operation an additional charge of r22 is required to reach the standard refrigerant charge 8
- Power circuit and cable requirements 8
- Refrigerant piping only for efv jb and efr jb units 8
- Service space 8
- Split air cooled air conditioners 8
- Supply cooling water for euc jb units only 8
- The daikin efr jb series are air cooled air conditioners with cooling only application for indoor installation the efr jb air conditioners can be combined with the daikin ecr d condenser units the standard operation range of the units ranges from 19 cdb to 32 cdb indoor ambient temperature 8
- The daikin efv jb series are air cooled air conditioners with cooling only application for indoor installation the efv jb air conditioners can be combined with the daikin erc c or er d condensing units the standard operation range of the units ranges from 19 cdb to 32 cdb indoor ambient temperature 8
- The daikin euc jb series are water cooled air conditioners with cooling only application for indoor installation the standard operation range of the euc jb units ranges from 15 c to 48 c condenser water inlet temperature 8
- The field wiring must be carried out in accordance with the wir ing diagrams 8
- Water cooled air conditioners 8
- Water quality specifications for euc jb units only 8
- Wiring diagram refer to the sticker on the unit outlook drawing refer to the outlook drawings at the end of this manual 8
- Maintenance 9
- Thermostat 9
- Troubleshooting 9
- Pwe02024 1b 10
Похожие устройства
- Daikin EUC10JBW1 Инструкция по монтажу
- Daikin EUC10JBW1 Инструкция по эксплуатации
- Daikin EUC10JBT1 Инструкция по монтажу
- Daikin EUC10JBT1 Инструкция по эксплуатации
- Daikin EFV3JBW1 Инструкция по монтажу
- Daikin EFV3JBW1 Инструкция по эксплуатации
- Daikin EFV3JBT1 Инструкция по монтажу
- Daikin EFV3JBT1 Инструкция по эксплуатации
- Daikin EFV5JBW1 Инструкция по монтажу
- Daikin EFV5JBW1 Инструкция по эксплуатации
- Daikin EFV5JBT1 Инструкция по монтажу
- Daikin EFV5JBT1 Инструкция по эксплуатации
- Daikin EFV8JBW1 Инструкция по монтажу
- Daikin EFV8JBW1 Инструкция по эксплуатации
- Daikin EFV8JBT1 Инструкция по монтажу
- Daikin EFV8JBT1 Инструкция по эксплуатации
- Daikin EFV10JBW1 Инструкция по монтажу
- Daikin EFV10JBW1 Инструкция по эксплуатации
- Daikin EFV10JBT1 Инструкция по монтажу
- Daikin EFV10JBT1 Инструкция по эксплуатации