Daikin FUYP71BV1 [327/397] Dip switch ds2

Daikin RYP100B7V1 [327/397] Dip switch ds2
ESiEN02–01A Field settings
Part 4 Commissioning and Test Run 4–25
3
4
5
1
2.14 DIP switch DS2
Priority The table below contains the priority of the DIP switches.
DS2-1:
Defrost starting
time
The table below describes the DIP switch.
DS2-2:
Mode B
The table below describes the DIP switch.
When... are ON Then... has priority.
DS1-2
DS2-1
DS1-2
DS1-1
DS2-2
DS1-1
Setting Illustration Function
Factory setting OFF Accumulated operation time for defrost operation
= 3 h.
Field setting ON Changes the accumulated operation time for the
defrost operation from 3 h to 24 h in order to delay
the defrosting operation.
1234
1234
Setting Illustration Function
Factory setting OFF At the start-up of the defrost operation, the E.V.
opens at the max. (480 pulses) for a limited time
(1 or 2 min), before closing to 100 pulses.
Field setting ON Changes the following in order to avoid liquid back
to the compressor:
Changes the limited time of E.V. opening at
max. (480 pulses) from 1 or 2 min to 30 s.
Stops the compressor at defrost start and stop.
1234
1234