Daikin FXL32LVE [61/254] Oil return operation

Daikin FXM125LVE [61/254] Oil return operation
Special Control Si38-606
50 Function
3.2 Oil Return Operation
3.2.1 Oil Return Operation in Cooling Operation
* In the case of multi-outdoor-unit system,
Master unit: Performs the operations listed in the table above.
Slave units: Operating units perform the operations listed in the table above.
Non-operating units perform the operations listed in the table above from the oil return operation.
(Non-operating unit stops during “oil return preparation operation”.)
Outdoor unit actuator
Oil return preparation
operation
Oil return operation Post-oil-return operation
Compressor Upper limit control 124 Hz + ON + OFF 124 Hz + ON + OFF
Outdoor unit fan Fan control Fan control Fan control
Main motorized valve (EV1) 0 pls 0 pls 0 pls
Subcooling motorized valve (EV2) SH control 0 pls 0 pls
Hot gas bypass valve (SVP) OFF ON ON
Oil equalization valve (SVO) ON ON ON
Receiver gas charging valve (SVL) OFF OFF OFF
Receiver gas discharging valve
(SVG)
OFF OFF OFF
Non-operating unit gas discharging
valve (SVSG)
OFF OFF OFF
Non-operating unit liquid pipe stop
valve (SVSL)
ON ON ON
Ending conditions 20 sec.
3 min.
Ts - Te<5
10 sec.
or
Indoor unit actuator Cooling oil return operation
Fan
Thermostat ON unit Set Air Volume
Stopping unit OFF
Thermostat OFF unit OFF
Electronic expansion valve
Thermostat ON unit Normal opening
Stopping unit 200 pls
Thermostat OFF unit 200 pls

Содержание

Скачать