Daikin FXLQ20MAVE [18/27] Safety devices setting

Daikin FXLQ32MAVE [18/27] Safety devices setting
FXLQ-MAVE / FXNQ-MAVE
18
7. Safety Devices Setting
Model
FXLQ20MAVE
FXNQ20MAVE
FXLQ25MAVE
FXNQ25MAVE
FXLQ32MAVE
FXNQ32MAVE
PCB fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor thermal fuse °C
Fan motor thermal protector °C
OFF : 135±10
ON : 120 or less
OFF : 135±10
ON : 120 or less
OFF : 135±10
ON : 120 or less
Model
FXLQ40MAVE
FXNQ40MAVE
FXLQ50MAVE
FXNQ50MAVE
FXLQ63MAVE
FXNQ63MAVE
PCB fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A
Fan motor thermal fuse °C
Fan motor thermal protector °C
OFF : 135±10
ON : 120 or less
OFF : 135±10
ON : 120 or less
OFF : 135±10
ON : 120 or less
C: 3D034529G