Daikin FXCQ40MVE4 [4/14] 1 precautions

Daikin FXCQ40MVE4 [4/14] 1 precautions
2 English
2. Where corrosive gas, such as sulphurous acid gas, is pro-
duced.
Corroding of copper pipes or soldered parts may result in
refrigerant leakage.
3. Near machinery emitting electromagnetic radiation.
Electromagnetic radiation may disturb the operation of the
control system and result in a malfunction of the unit.
4.
Where flammable gas may leak, where there is carbon fibre
or ignitable dust suspensions in the air, or where volatile flam-
mables such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.
The air conditioner is not intended for use in a potentially
explosive atmosphere.
2. BEFORE INSTALLATION
When moving the unit while removing it from the carton
box, be sure to lift it by holding on to the four lifting lugs
without exerting any pressure on other parts, especially,
the refrigerant piping, drain piping, and other resin
parts.
Be sure to check the type of R410A refrigerant to be used
before installing the unit. (Using an incorrect refrigerant will
prevent normal operation of the unit.)
The accessories needed for installation must be retained in
your custody until the installation work is completed. Do not
discard them!
Decide upon a line of transport.
Leave the unit inside its packaging while moving, until reach-
ing the installation site. Where unpacking is unavoidable, use
a sling of soft material or protective plates together with a
rope when lifting, to avoid damage or scratches to the unit.
When moving the unit at or after opening, hold the unit by the
hanger brackets (×4). Do not apply force to the refrigerant
piping, drain piping or plastic parts.
When selecting installation site, refer to the paper pattern.
For the installation of an outdoor unit, refer to the installation
manual attached to the outdoor unit.
Do not install or operate the unit in rooms mentioned below.
Laden with mineral oil, or filled with oil vapor or spray
like in kitchens. (Plastic parts may deteriorate which
could eventually cause the unit to fall out of place, or
could lead to leaks.)
Where corrosive gas like sulfurous gas exists. (Cop-
per tubing and brazed spots may corrode, which
could eventually lead to refrigerant leaks.)
Where exposed to combustible gases and where vol-
atile flammable gas like thinner or gasoline is used.
(Gas in the vicinity of the unit could ignite.)
Where machines can generate electromagnetic
waves. (Control system may malfunction.)
Where the air contains high levels of salt such as that
near the ocean and where voltage fluctuates greatly
such as that in factories. Also in vehicles or vessels.
This unit, both indoor and outdoor, is suitable for installation in
a commercial and light industrial environment.
If installed as a household appliance it could cause electro-
magnetic interference.
2-1 PRECAUTIONS
Be sure to read this manual before installing the indoor unit.
Entrust installation to the place of purchase or a qualified ser-
viceman. Improper installation could lead to leaks and, in
worse cases, electric shock of fire.
Use only parts provided with the unit or parts satisfying
required specifications. Unspecified parts could cause the
unit to fall out of place, or could lead to leaks and, in worse
cases, electric shock or fire.
2-2 ACCESSORIES
Check the following accessories are included with your unit.
Screws for fixing panels are attached to decoration panel.
2-3 OPTIONAL ACCESSORIES
The optional decoration panel and remote controller are
required for this indoor unit. (Refer to Table 1)
These are two types of remote controllers: wired and wire-
less. Select a remote controller from Table 2 according to
customer request and install in an appropriate place.
Tabl e 1
Name Metal clamp
Paper pattern for
installation
Quantity 1 pc. 1 pc.
Shape
Name Drain hose
Insulation for fitting
Quantity 1 pc. 1 each
Shape
for gas pipe
for liquid pipe
Name Washer fixing plate Sealing pad
Quantity 4 pcs. 1 each
Shape
Large
Small
Name
Washer for hanging
bracket
Clamp
Quantity 8 pcs. 8 pcs.
Shape
Name Screws (M5)
(Other)
Operation manual
Installation manual
Quantity 4 pcs.
Shape
For paper pattern for
installation
Model
Optional decoration panel
White
FXCQ20 · 25 · 32MVE BYBC32GJW1 · BYBC32G-W1
FXCQ40 · 50MVE BYBC50GJW1 · BYBC50G-W1
FXCQ63MVE BYBC63GJW1 · BYBC63G-W1
FXCQ80 · 125MVE BYBC125GJW1 · BYBC125G-W1
01_EN_3P086156-5X.fm Page 2 Tuesday, April 14, 2009 9:24 AM