Troubleshooting by Indication on the Remote Controller SiBE34-703
162 Troubleshooting
3.35 LC Outdoor Unit: Malfunction of Transmission between
Inverter and Control PC Board
Remote
Controller
Display
LC
Applicable
Models
RXYSQ4~6P
Method of
Malfunction
Detection
Check the communication state between inverter PC board and control PC board by micro-
computer.
Malfunction
Decision
Conditions
When the correct communication is not conducted in certain period.
Supposed
Causes
Malfunction of connection between the inverter microcomputer and outdoor control
microcomputer
Defect of outdoor unit PC board (A1P)
External factor (Noise etc.)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are the
connectors of the
inverter PC board and the
control PC board
securely
connected?
Replace the inverter PC board
(A2P) or the control PC board
(A1P).
Table 1: Combination of PC boards
Connect a connecting wire, and
then restart operation.
NO
NO
Are there
any broken wires in
the connectors of the
inverter PC board and
the control PC
board?
Repair the broken wires, and then
restart operation.
YES
YES
NO
Was the
inverter PC board or the
control PC board
replaced?
Are the inverter
PC board and the control PC board
used in combination of types listed
in Table 1?
Correct the combination following
Table 1, and then restart
operation.
YES
YES
NO
Type of control
PC board
RXYSQ4P7Y1B
RXYSQ5P7Y1B
RXYSQ6P7Y1B
EC0640-1
RXYSQ4P7Y1BH
RXYSQ5P7Y1BH
RXYSQ6P7Y1BH
EC0640-2
PC0625-1
PC0625-2
Type of inverter
PC board