Daikin FXMQ32PVE [3/20] Specifications

Daikin FXMQ32PVE [3/20] Specifications
Indoor Units • CONCEALED CEILING UNIT • FXMQ-PVE
•VRV
®
Systems • Indoor Units
132
1 Specifications
Indoor Unit VRV Systems FXMQ-PVEConcealed C
1-1 TECHNICAL SPECIFICATIONS FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE
Capacity Cooling kW 4.5 5.6 7.1 9.0 11.2 14.0
Heating kW 5.0 6.3 8.0 10.0 12.5 16.0
Power Input Cooling kW 0.194 (1)
0.193 (2)
0.215 (1)
0.214 (2)
0.230 (1)
0.229 (2)
0.298 (1)
0.297 (2)
0.376 (1)
0.375 (2)
0.461 (1)
0.460 (2)
Heating kW 0.182 0.203 0.218 0.286 0.364 0.449
Casing Material Galvanised steel plate
Dimensions Unit Height mm 300 300 300 300 300 300
Width mm 700 1,000 1,000 1,000 1,400 1,400
Depth mm 700 700 700 700 700 700
Weight Unit kg 28 36 36 36 46 46
Heat
Exchanger
DimensionsNr of Rows 333333
Fin Pitch mm 1.75 1.75 1.75 1.75 1.75 1.75
Face
Area
0.148 0.249 0.249 0.249 0.383 0.383
Nr of Stages 16 16 16 16 16 16
Fan Type Sirocco fan
Air Flow Rate Cooling High high m³/min 16 18 19.5 25 32 39
High m³/min 13 16.5 17.5 22.5 27 33
Low m³/min 11 15 16 20 23 28
Fan External static
pressure
High Pa 160 200 200 200 200 200
Standard Pa 100 100 100 100 100 100
Low Pa 30 50 50 50 50 50
Motor Output
(high)
W 140 350 350 350 350 350
Drive Direct drive
Piping
connections
Liquid (OD) Type Flare connection
Diameter mm 6.35 9.52 9.52 9.52 9.52 9.52
Gas Type Flare connection
Diameter mm 12.7 15.9 15.9 15.9 15.9 15.9
Drain Diameter mm VP25 (I.D. 32/O.D. 25)
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating
Safety devices Fuse
Fan driver overload protector
Standard
Accessories
Standard Accessories Operation manual
Installation manual
Drain hose
Sealing pads
Clamps
Washer
Screws
Insulation for fitting
Clamp metal
Air discharge flange
Air suction flange
Legend (1) 50Hz, 220-240V
(2) 60Hz, 220V
Notes Nominal cooling capacities are based on following conditions: return air temperature: 27°CDB/19°CWB; outdoor
temperature: 35°CDB; standard external static pressure: 100Pa; equivalent refrigerant piping: 7.5m (horizontal)
Nominal heating capacities are based on following conditions: return air temperature: 20°CDB; outdoor temperature:
7°CDB/6°CWB; standard external static pressure: 100Pa; equivalent refrigerant piping: 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable in 13 or 14 stages within the ( ) range by the remote control.
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric
method(gravity method) 50% or more.