Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PBVE
1 Specifications
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable to set by the remote control; this pressure means : high static pressure -
standard static pressure.
The operation sound levels are conversion values in anechoic chamber. In practice, sound levels tend to be higher
than the specified values due to ambient noise or reflection. When the suction place is changed to bottom suction,
sound level will increase
1-2 ELECTRICAL SPECIFICATIONS
(50HZ)
FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
Power Supply Name VE
Phase 1~
Frequency Hz 50
Voltage V 220-240
Current
Minimum circuit amps (MCA)
A0.8 0.8 0.8
Maximum fuse amps (MFA) A 15 15 15
Full load amps (FLA) A 0.6 0.6 0.6
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS
(60HZ)
FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
Power Supply Name VE
Phase 1~
Frequency Hz 60
Voltage V 220
Current
Minimum circuit amps (MCA)
A0.9 0.9 0.9
Maximum fuse amps (MFA) A 15 15 15
Full load amps (FLA) A 0.7 0.7 0.7
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-1 TECHNICAL SPECIFICATIONS FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE