Si34-803 Special Control
Function 151
3.7.3 Stopping Operation of Slave Units During Master Unit is in Operation
with Multi-Outdoor-Unit System
While the master unit is in operation, this mode is used to set the refrigerant flow rate to a required level using a slave
unit in the stopped mode.
In cooling operation: Same as that of normal operation stop.
In heating operation: The system operates with following mode.
Actuator Operation
Compressor OFF
Outdoor unit fan OFF
Four way valve ON
Main motorized valve (EV1) 0 pls
Subcooling motorized valve (EV2) 0 pls
Hot gas bypass valve (SVP) OFF
Accumulator oil return valve (SVO) OFF
Injection valve (SVT 5HP only) OFF
Ending conditions Slave units are required to operate.