VRV Systems • Indoor Units
169
Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-NVE
2 - 3 Safety device settings
2-2 ELECTRICAL SPECIFICATIONS FXDQ20NVE FXDQ25NVE FXDQ32NVE FXDQ40NVE FXDQ50NVE FXDQ63NVE
Power Supply Name VE VE VE VE VE VE
Phase 111111
Frequency Hz 50 50 50 50 50 50
Voltage V 220-240
Current Minimum circuit amps
(MCA)
A 0.90 0.90 0.90 1.00 1.00 1.10
Maximum fuse amps (MFA) A 15.00 15.00 15.00 15.00 15.00 15.00
Full load amps (FLA) A 0.70 0.70 0.70 0.80 0.80 0.90
Voltage range Minimum V -10%
Maximum V +10%
NOTES
1 Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
2 Maximum allowable voltage range variation between phases is 2%.
3MCA/MFA:
MCA = 1.25 x FLA
MFA<= 4 x FLA
4 next lower standard fuse rating minimum 15A
5 select wire size based on the MCA
6 instead of a fuse, use a circuit breaker
FXDQ-NVE
20 25 32 40 50 63
PC BOARD FUSE 250V 5A
FAN MOTOR THERMAL PROTECTOR °C OFF: 130
±5
/ ON: 83
±15
4D043861A