Daikin FXS80LVE [41/54] Natural evaporating pan type humidifier wiring adaptor is required

Daikin FXS25LVE [41/54] Natural evaporating pan type humidifier wiring adaptor is required
(' $FFHVVRULHV
);6/ 
6
Natural Evaporating Pan Type Humidifier (Wiring adaptor is required.)
Specifications
Precaution at use
1. “Wiring adaptor (KRP1B61)” is separately needed for one indoor unit by one piece of the adaptor.
2. This humidifier will be built in a indoor unit, while the solenoid valve box will be mounted out of the unit's body
(refer to the dimensions of optional accessories).
3. The field setting should be changed by a remote controller.
Note:
The value in JIS heating condition's standard.
Feed water piping
1. Provide a stop valve of feed water for the feed water circuit.
2. Supply clean water for the feed water. Contaminated water clogs a valve and the contaminants accumulate in a
water tank, disturbing a normal operation of the humidifier. (Never use cooling water for a cooling tower or hot
water for heating purpose). Moreover, since white powder will appear if the feed water contains much silica, it is
recommended to install a water purifier or a water softener if these phenomena are found.
3. Use water in the range of water temperature 5 ~ 50°C and water pressure 0.049 ~ 0.294 MPa[0.5 ~3kg/cm²].
Provide a reducing valve between a strainer and this kit, in case of 0.294MPa or more for feed water pressure.
4. The feed water pipe can not be connected to a public water route. Accordingly, if water must be supplied through
a public water by all means, provide a cistern tank (approved model only).
Wiring diagram
Characteristics of Filter
Model
Item
KNM25K32V1 KNM25K50V1 KNM25K63V1 KNM25K125V1
Humidifying Capacity (L/h) 0.4 0.6 1.0 1.8
Power Supply (W) Single Phase, 220-240V 50Hz
Power Consumption 12/9.6
Water Inlet Port 1/2B
Water Outlet Port VP25 (External dia.
φ32) (drain pipe at indoor unit)
Applicable Models 20·25·32Class 40·50Class 63Class 80·100·125Class
------------- Field wiring
Make wiring as shown on the
right, if a humidity controller
will be mounted.
Arrange the wiring shown
right locally for that case. Set
the turn-over switch to OFF
for the choice of ON/OFF of
group humidity controlling
input on the "Wiring adaptor
PC board" .