Indoor Units • Concealed Ceiling Unit • FXSQ-MVE9
1 Specifications
1-3 Electrical Specifications (60Hz) FXSQ20MVE9 FXSQ25MVE9 FXSQ32MVE9 FXSQ40MVE9 FXSQ50MVE9 FXSQ63MVE9
Power Supply Name VE
Phase 1~
Frequency Hz 60
Voltage V 220
Current Minimum circuit amps (MCA) A 0.6 0.6 0.8 0.9 1.0 1.4
Maximum fuse amps (MFA) A 15 15 15 15 15 15
Full load amps (FLA) A 0.5 0.5 0.6 0.7 0.8 1.1
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 Electrical Specifications (60Hz) FXSQ80MVE9 FXSQ100MVE9 FXSQ125MVE9
Power Supply Name VE
Phase 1~
Frequency Hz 60
Voltage V 220
Current Minimum circuit amps (MCA) A 1.8 1.9 2.5
Maximum fuse amps (MFA) A 15 15 15
Full load amps (FLA) A 1.4 1.5 2.0
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker