Daikin FXSQ80MVE [5/22] Specifications

Daikin FXSQ80MVE [5/22] Specifications
Indoor Units • Concealed Ceiling Unit • FXSQ-MVE9
1
1
•VRV
®
Systems • Indoor Units
4
1 Specifications
Standard Accessories Operation manual
Installation manual
Paper pattern for installation
Drain hose
Clamp metal
Insulation for fitting
Sealing pads
Clamps
Screws
Washer
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature
: 35°CDB, equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB,
6°CWB, equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
1-2 Electrical Specifications (50Hz) FXSQ20MVE9 FXSQ25MVE9 FXSQ32MVE9 FXSQ40MVE9 FXSQ50MVE9 FXSQ63MVE9
Power Supply Name VE
Phase 1~
Frequency Hz 50
Voltage V 220-240
Current Minimum circuit amps (MCA) A 0.5 0.5 0.5 0.6 0.9 1.1
Maximum fuse amps (MFA) A 15 15 15 15 15 15
Full load amps (FLA) A 0.4 0.4 0.4 0.5 0.7 0.9
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-2 Electrical Specifications (50Hz) FXSQ80MVE9 FXSQ100MVE9 FXSQ125MVE9
Power Supply Name VE
Phase 1~
Frequency Hz 50
Voltage V 220-240
Current Minimum circuit amps (MCA) A 1.4 1.5 2.0
Maximum fuse amps (MFA) A 15 15 15
Full load amps (FLA) A 1.1 1.2 1.6
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-1 Technical Specifications FXSQ80MVE9 FXSQ100MVE9 FXSQ125MVE9