Daikin FXLQ40P2VEB [6/19] Specifications

Daikin FXLQ63P2VEB [6/19] Specifications
• Indoor Unit • FXLQ-P
2
• VRV Systems • FXLQ-P
4
2 Specifications
Notes
(1) Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
(2) Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
(3) Contains fluorinated greenhouse gases
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA: MCA = 1.25 x FLA
MFA 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the value of MCA
Instead of a fuse, use a circuit breaker
Current - 50Hz Minimum circuit amps (MCA) A 0.3 0.6
Maximum fuse amps (MFA) A 15
Full load amps
(FLA)
Total A 0.2 0.5
Current - 60Hz Minimum circuit amps (MCA) A 0.3 (3) 0.5 (3) 0.6 (3)
Maximum fuse amps (MFA) A 15.0 (3)
Full load amps
(FLA)
Total A 0.2 (3) 0.4 (3) 0.5 (3)
2-2 Electrical Specifications FXLQ20P FXLQ25P FXLQ32P FXLQ40P FXLQ50P FXLQ63P