Si39-302 Troubleshooting by Indication on the Remote Controller
Troubleshooting 161
2.5
A7
Indoor Unit: Malfunction of Swing Flap Motor (MA)
Remote
Controller
Display
A7
Applicable
Models
FXCQ, FXAQ, FXFQ, FXHQ, FXKQ
Method of
Malfunction
Detection
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Decision
Conditions
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
motor is energized for a specified amount of time (about 30 seconds).
Supposed
Causes
!
Defect of swing motor
!
Defect of connection cable (power supply and limit switch)
!
Defect of air flow direction adjusting flap-cam
!
Defect of indoor unit PC board