Daikin FXVQ500NY1 [22/34] Specifcations

Daikin FXVQ250NY1 [22/34] Specifcations
Specications
41 42
VRV Indoor Units
Wall Mounted Type
Floor Standing Type/Concealed Floor Standing Type
Floor Standing Duct Type
FXLQ
FXNQ
Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
Sound level:
Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
FXAQ20PVE FXAQ25PVE FXAQ32PVE FXAQ40PVE FXAQ50PVE FXAQ63PVE
1-phase, 220-240 V/220 V, 50/60 Hz
1,900 2,400 3,100 3,900 4,800 6,100
7,500 9,600 12,300 15,400 19,100 24,200
2.2 2.8 3.6 4.5 5.6 7.1
0.019 0.028 0.030 0.020 0.033 0.050
0.049 0.049 0.090 0.090 0.110 0.110
White (3.0Y8.5/0.5)
7.5/4.5 8/5 8.5/5.5 12/9 15/12 19/14
265/159 282/177 300/194 424/318 530/424 671/494
35/31 36/31 38/31 42/3739/34 47/41
290×795×238 290×795×238 290×795×238
290×1,050×238 290×1,050×238 290×1,050×238
11.0 11.0 11.0 14.0 14.0 14.0
6.4 6.4 6.4 6.4 6.4 9.5
12.7 12.7 12.7 12.7 12.7 15.9
VP13 (External Dia, 18/Internal Dia, 13)
FXLQ50MAVE
FXNQ50MAVE
FXLQ40MAVE
FXNQ40MAVE
FXLQ32MAVE
FXNQ32MAVE
FXLQ25MAVE
FXNQ25MAVE
FXLQ20MAVE
FXNQ20MAVE
FXLQ63MAVE
FXNQ63MAVE
1-phase, 220-240 V/220 V, 50/60 Hz
1,900 2,400 3,100 3,900 4,800 6,100
7,500 9,600 12,300 15,400 19,100 24,200
2.2 2.8 3.6 4.5 5.6 7.1
FXLQ: Ivory white (5Y7.5/1)/FXNQ: Galvanised steel plate
7/6 7/6 8/6 11/8.5 14/11 16/12
247/212 247/212 282/212 388/300 494/388 565/424
35/32 35/32 35/32 38/33 39/34 40/35
600×1,000×222 600×1,000×222 600×1,140×222 600×1,140×222 600×1,420×222 600×1,420×222
610×930×220 610×930×220
610×1,070×220 610×1,070×220 610×1,350×220 610×1,350×220
25.0 25.0 30.0 30.0 36.0 36.0
19.0 19.0 23.0 23.0 27.0 27.0
6.4 6.4 6.4 6.4 6.4 9.5
12.7 12.7 12.7 12.7 12.7 15.9
21O.D.
cfm
dB(A)
mm
kg
mm
kcal/h
Btu/h
kW
kW
m
3
/min
Liquid (Flare)
Gas (Flare)
Drain
Power consumption
Casing
Dimensions (H×W×D)
Machine weight
Piping
connections
Power supply
Cooling capacity
MODEL
Cooling
Sound level (H/L)
Power consumption
Casing
Power supply
Cooling capacity
MODEL
Cooling
Airflow rate (H/L)
Rp1 (PS 1B internal thread)
Long-life filter (anti-mould resin net)
Belt drive system
3-phase 4-wire system, 380–415 V, 50 Hz
Ivory white (5Y7.5/1)
FXVQ125NY1
1,670×750×510
118
52
15.9 (Brazing)
FXVQ250NY1FXVQ200NY1
0.53
12,000
47,800
14.0
19,300
76,400
22.4
24,100
95,500
28.0
1.611.33
1,670×1,170×510
169
60
22.2 (Brazing)
1,670×950×510
144
56
9.5 (Brazing)
19.1 (Brazing)
0.75
43
1,518
1.5
69
2,436
1.5
86
3,036
152 217 281
Notes: Specifications are based on the following conditions;
Cooling : Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
   
Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
*1 Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value).
It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow.
*2 The value is the external static pressure with standard pulley.
mm
kg
dB(A)
mm
mm
mm
kW
m
3
/min
cfm
Pa
kcal/h
Btu/h
kW
kW
Liquid
Gas
Drain
Type
Motor output
Airflow rate
External static pressure *2
Drive system
Power consumption
Casing colour
Sound level *1
Dimensions (H×W×D)
Machine weight
Piping
connections
Power supply
Cooling capacity
MODEL
Cooling
Air filter
Fan
cfm
dB(A)
kcal/h
Btu/h
kW
kW
m
3
/min
Liquid (Flare)
Gas (Flare)
Drain
Machine weight
Piping
connections
Sound level (H/L)
Dimensions
(H×W×D)
FXLQ
FXNQ
FXLQ
FXNQ
mm
kg
mm
Airflow rate (H/L)
Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
Sound level:
Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
220 V
240 V 37/34 37/34 37/34 40/35 41/36 42/37
Ceiling Suspended Type
FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE
1-phase, 220-240 V/220 V, 50/60 Hz
3,100
6,100
9,600
12,300 24,200 38,200
3.6 7.1 11.2
0.111 0.115 0.135
White (10Y9/0.5)
12/10 17.5/14 25/19.5
424/353 618/494 883/688
36/31 39/34 45/37
195×960×680 195×1,160×680 195×1,400×680
24.0 28.0 33.0
VP20 (External Dia, 26/Internal Dia, 20)
cfm
dB(A)
mm
kg
mm
kcal/h
Btu/h
kW
kW
m
3
/min
Liquid (Flare)
Gas (Flare)
Drain
Power consumption
Casing
Dimensions (H×W×D)
Machine weight
Piping
connections
Power supply
Cooling capacity
MODEL
Cooling
Sound level (H/L)
Airflow rate (H/L)
6.4
12.7 15.9 15.9