Daikin FXVQ125MY1 [7/12] Drain piping
![Daikin FXVQ125MY1 [7/12] Drain piping](/views2/1705355/page7/bg7.png)
6English
<125-250 type>
Refrigerant
piping insulation
(Field supply)
Refrigerant piping
(Field supply)
More than 40 mm
More than 40 mm
Connection piping
(Accessory)
Gas piping
Liquid piping
<400 · 500 type>
Refrigerant
piping insulation
(Field supply)
More than 40 mm
More than 40 mm
Connection piping
(Accessory)
Gas piping
Liquid piping
7. DRAIN PIPING
7-1 INSTALL DRAIN PIPING
• Install drain piping is order to ensure proper drainage and
insulate piping in order to prevent condensation.
• Keep the piping length as short as possible and slope the
pipe with a gradient of 1/100 or more. Do not create any air
accumulated pocket in the piping.
• Use the pipe size equivalent or larger to the pipe
connection size of the unit.
• The drain connection is available from both (left and right)
sides.
• For the right side connection, change the drain plug from
right to left.
• For piping goes through the indoor, make sure to insulate
the indoor drain socket to the end of socket.
• When connecting the drain piping, insulate the drain plug
on the opposite side of drain piping connection completely
with the attached insulation.
• Always make a drain trap at the drain outlet.
Check
• After completion of drain piping, let water ow into the
drain pan and check for drain and water leakage from the
piping connection area.
Drain trap
Unit bottom line
Insulation for
drain plug
(accessories)
make a
drain trap
Drain trap
The end of the drain port
must be always kept in the
water to prevent backflow of
odor from the sewage.
Remove the released
paper, and make sure
to label on the unit.
Drain plug
Indoor
unit
Downward inclination
1/100 or more
50 mm
or more
Drain plug cap
(accessories)
100 mm
or more
Drain piping
(for Left side connection)
CAUTION
• The connection of the drain piping
Do not directly connect the drain piping to sewerage, which
odor may smell like ammonia.
Sewerage may contain it, which may pass through the
drain piping, and result in corrosion of the indoor unit heat
exchanger.
8. ELECTRIC WIRING
CAUTION
• Install earth leakage circuit breaker.
It is our obligation to mount earth leakage circuit
breaker in order to prevent accidents such as electric
shocks and/or re.
• All eld wiring and components must be installed by a
licensed electrician and must comply with relevant local
and national regulations.
• Use copper conductors only.
• Be sure to install an earth leakage breaker.
(Failure to install an earth leakage breaker may result in
electric shocks, or re.)
• Always ground wires. (In accordance with national
regulations of the pertinent country.)
• Do not connect the ground wire to gas pipe, sewage pipe,
lightning rods, or telephone ground wires.
• Gas pipe: can explode or catch re if there is a gas
leak.
• Sewage pipes: no grounding effect is possible if hard
plastic piping is used.
• Telephone ground wires and lighting rods: dangerous
when struck by lighting due to abnormal rise in
electrical potential in the grounding.
• The eld wiring must be carried out in accordance with the
wiring diagrams and the instructions given below.
• If the fan rotates reversely, change the connection of two
power supply wires out of three.
• For connection to the terminal block, use ring type crimp
style terminal suitable for the wire size.
• Do not close the branch switch and overcurrent circuit
breaker until all the works are completed.
01_EN_3P345056-4F.indd 6 9/3/2015 15:00:25
Содержание
- Installation manual 1
- System air conditioners 1
- Contents 2
- Safety precautions 2
- 1 precaution 3
- 2 accessories 3
- 3 carry out the work giving caution to the following items and after the work is completed check these again 3
- Be sure to instruct the customer how to properly operate the system particularly the cleaning of air filter operation method temperature adjusting method showing the attached operation manual to the person do not install the unit where the atmosphere is salty such as near the seaside where the voltage frequently fluctuates or in a vehicle or a boat 3
- Before installation 3
- Check if the following accessories are included in the indoor unit 3
- English 3
- Install the air conditioner power supply wiring remote controller wiring and transmission wiring at least 1 meter away from televisions or radios to prevent image interference or noise depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise do not install the air conditioner in places such as the following 1 where there is mist of oil oil spray or vapour for example a kitchen resin parts may deteriorate and cause them to fall out or water to leak 2 where corrosive gas such as sulfurous acid gas is produced corrosion of copper pipings or brazed parts may cause the refrigerant to leak 3 where there is machinery which emits electromagnetic waves electromagnetic waves may disturb the control system and cause malfunction of the equipment 4 where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air or where volatile flammables such as thinner or gasoline are handled if the gas should leak and remained around the air con 3
- Items to be checked after the installation work is completed 3
- Make sure to recheck the items of safety precautions 3
- Make sure to use the r410a refrigerant before the installation work otherwise the unit can not operate normally for installation of outdoor unit refer to the installation manual attached to the outdoor unit do not throw away the accessories required for installation until the installation is finished 3
- 1 example of required space 4
- Carry in method 4
- Installation site 4
- 1 how to replace pulley 5
- 1 material of piping 5
- 1 remove the suction grille 2 remove the protection net then remove the cushioning material on the protection net 3 remove the front panel upper 4 remove the front panel lower 5 put the iron plate which must be wider than the fan motor under the fan motor and on the heat exchanger for protection for its fin iron plate must be supplied in the field 6 remove the terminal for the fan motor lead wire from the magnet switch 7 pull out the fan motor lead wire to the fan housing parts and let it out of the unit from the opening part on the front plate upper 8 remove the nuts of the motor base 9 remove the belt hold the fan motor base firmly when working so that it may not move suddenly 10 slide the fan housing assembly on the iron plate on which the fan motor is put the above procedure 5 frontward slowly work must be conducted by more than 3 persons one of them must hold the motor base and two or more of them must hold the fan housing 11 move the fan housing assembly to the location where can 5
- 2 parallelism of pulley 5
- 3 tension of v belt 5
- Adjust the parallelism of the pulley between the fan and the motor so as to meet the standard as below 5
- Caution 5
- Caution at installation 5
- English 5
- Follow the above procedure 1 4 6 7 10 11 12 in the order 5
- For the refrigerant piping of the outdoor unit refer to the installation manual attached to the outdoor unit make sure to use r410a as refrigerant before the installation work otherwise the unit can not operate normally make sure to insulate the piping on both the liquid side and the gas side otherwise water leakage may be caused use a heat insulating material sufficiently resistant to 120 c reinforce the refrigerant piping according to the installation environment otherwise condensation may form on the surface of the insulation 5
- Note it is recommended to check the tension as above after 24 28 hours of the operation when the new belts are used it is preferable to adjust to about 1 times the maximum value of deflection load w 5
- Refrigerant piping 5
- Tension of a v belt must meet the deflection load w as shown calculate the required deflection length l by the equation 1 its tolerance must be within the range as below 5
- This unit is for using r410a only make sure to follow the items as shown in below when working use the pipe cutter and the flaring tool that are exclusively used for r410a at flare connection apply ether oil or ester oil to the flare section protect the piping by a pinch or taping to prevent invasion of contamination moisture and dusts into the piping 5
- Use the copper tube according to the following table 5
- 1 install drain piping 7
- Drain piping 7
- Electric wiring 7
- 1 remove the front panel lower 8
- 1 remove the front panel lower 2 fix the each wire on the control box with the attached clamp 3 for wiring specifications refer to the details of standard devices 8
- 2 external wiring method 8
- 3 example of wiring 8
- Apply putty or insulation material field supply without any clearance on the wiring intake section to prevent small animals from entering the unit if small animals such as insects enter the inside of the unit it may cause short circuit in the control box connect the wire securely using designated wire and fix it with attached clamp without applying external pressure on the terminal parts make sure the wiring and the control box lid do not stick up above the structure and close the control box lid firmly 8
- Caution 8
- Do not have low voltage wires wiring between units and other high voltage run through the same locations and there must be min 50 mm distance between wires outside of the unit or it may cause a malfunction or a breakdown of the unit by receiving electrical noise external noise 8
- Downloaded from www manualslib com manuals search engine 8
- English 8
- Ex2 for multiple indoor units 8
- F1f2 t1t2 8
- Prohibited 8
- The control panel is the standard built in ex1 when using in pairs 8
- When removing the front panel lower there is the control box 8
- Wiring from left side 8
- Wiring from right side 8
- 4 precautions when laying power wiring 9
- 5 details of standard devices 9
- Abnormal heating may occur if the wirings are not tightened securely 9
- Caution for wiring 9
- Connect the terminal as shown in fig 2 do not carry out soldering finish when stranded wires are used otherwise the loosening of wires may result in abnormal heat radiation 9
- Do not carry out soldering finish when stranded wirings are used 9
- Electrical characteristics 9
- English 9
- Ex3 for group control 9
- Ex4 when including bs unit 9
- For connection to the terminal block use ring type crimp style terminals with insulation sleeve or insulate the wirings properly 9
- If an improper screw driver is used it may damage the screw head and a proper tightening cannot be carried out if a terminal is over tightened it may be damaged refer to the table shown below for tightening torque of terminals 9
- Note 1 it is not necessary to set the indoor unit address for group control the setting is made automatically when the power supply is turned on 2 make sure to disconnect the control panel wiring of the units over the second one 3 in this case all indoor units within the group are controlled by the control panel for the group control 9
- Refer to the installation manual attached to the outdoor unit for the details of the wire gauge of the power supply to the outdoor unit the earth leakage breaker the circuit breaker capacity and wiring use only the wiring devices specified in the following table for the wiring between indoor unit and outdoor unit branch off the exclusive lines for power supply to the indoor unit according to the following specification 9
- Table 1 9
- Use a proper screw driver for tightening the terminal screws 9
- Use the required wirings connect them securely and fix these wirings securely so that external force may not apply to the terminals 9
- Warning 9
- When wiring form the wirings orderly so that the control box lid can be securely fastened if the control box lid is not in place the wirings may come out or be sandwiched by the box and the lid and cause electric shocks or a fire 9
- 1 field setting 10
- Field setting and control wiring 10
- 2 remote controller and centralized control 11
- Trial operation 11
- P345056 4f em13a004b 12
Похожие устройства
- Daikin FXVQ125MY1 Брошюра
- Daikin FXVQ125MY1 Технические данные
- Daikin FXVQ200MY1 Инструкция по монтажу
- Daikin FXVQ200MY1 Брошюра
- Daikin FXVQ200MY1 Технические данные
- Daikin FXVQ250MY1 Инструкция по монтажу
- Daikin FXVQ250MY1 Брошюра
- Daikin FXVQ250MY1 Технические данные
- Daikin FXVQ400MY1 Инструкция по монтажу
- Daikin FXVQ400MY1 Брошюра
- Daikin FXVQ400MY1 Технические данные
- Daikin FXVQ500MY1 Инструкция по монтажу
- Daikin FXVQ500MY1 Брошюра
- Daikin FXVQ500MY1 Технические данные
- Daikin FXVQ500MY16 Инструкция по монтажу
- Daikin FXVQ500MY16 Брошюра
- Daikin FXVQ500MY16 Технические данные
- Daikin FXN20LVE Сервис мануал
- Candy CMXC 30DCS Техническое описание
- Candy CMXC 30DCS Руководство пользователя