Daikin FXVQ500MY1 [2/12] Safety precautions
![Daikin FXVQ125MY1 [2/12] Safety precautions](/views2/1705355/page2/bg2.png)
1 English
CONTENTS
1. SAFETY PRECAUTIONS ................................................. 1
2. BEFORE INSTALLATION ................................................. 2
3. CARRY-IN METHOD ........................................................ 3
4. INSTALLATION SITE ....................................................... 3
5. CAUTION AT INSTALLATION .......................................... 4
6. REFRIGERANT PIPING ................................................... 4
7. DRAIN PIPING ................................................................. 6
8. ELECTRIC WIRING.......................................................... 6
9.
FIELD SETTING AND CONTROL WIRING ......................... 9
10.
TRIAL OPERATION .............................................................10
1. SAFETY PRECAUTIONS
Be sure to follow this “SAFETY PRECAUTIONS”.
This product comes under the term “appliances not
accessible to the general public”.
This is a class A product. In a domestic environment this
product may cause radio interference in which case the user
may be required to take adequate measures.
This manual classies the precautions into WARNINGS and
CAUTIONS.
Be sure to follow all the precautions below: They are all
important for ensuring safety.
WARNING ......... Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTION .......... Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury.
It may also be used to alert against
unsafe practices.
• After the installation is completed, test the air conditioner
and check if the air conditioner operates properly. Give
the user adequate instructions concerning the use and
cleaning of the indoor unit according to the Operation
Manual. Ask the user to keep this manual and the
Operation Manual together in a handy place for future
reference.
WARNING
• Ask your local dealer or qualied personnel to carry out
installation work.
Improper installation may result in water leakage, electric
shocks or a re.
• Perform installation work in accordance with this installation
manual.
Improper installation may result in water leakage, electric
shocks or a re.
• Consult your local dealer regarding what to do in case of
refrigerant leakage.
When the air conditioner is installed in a small room, it is
necessary to take proper measures so that the amount of
any leaked refrigerant does not exceed the concentration
limit in the event of a leakage.
Otherwise, this may lead to an accident due to oxygen
deciency.
• Be sure to use only the specied parts and accessories for
installation work.
Failure to use the specied parts may result in the air
conditioner falling down, water leakage, electric shocks, a
re, etc.
• Install the air conditioner on a foundation that can
withstand its mass.
It may lead to vibration of indoor units and cause
unpleasant chattering noise.
• Carry out the specied installation work in consideration of
strong winds, typhoons, or earthquakes.
Improper installation may result in an accident such as air
conditioner falling.
• Make certain that all electrical work is carried out by
qualied personnel according to the applicable legislation
(note 1) and this installation manual, using a separate
circuit.
In addition, even if the wiring is short, make sure to use
a wiring that has sufcient length and never connect
additional wiring to make the length sufcient.
Insufcient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or a re.
(note 1) applicable legislation means “All international,
national and local directives, laws, regulations
and/or codes which are relevant and applicable for
a certain product or domain”.
• Earth the air conditioner.
Do not connect the earth wiring to gas or water piping,
lightning conductor or telephone earth wiring.
Incomplete earthing may cause electric shocks or a re.
• Be sure to install an earth leakage circuit breaker.
Failure to do so may cause electric shocks and a re.
• Disconnect the power supply before touching the electric
components.
If you touch the live part, you may get an electric shocks.
• Make sure that all wiring is secure, using the specied
wiring and ensuring that external forces do not act on the
terminal connections or wiring.
Incomplete connection or xing may cause an overheat or
a re.
• When wiring between the indoor and outdoor units, and
wiring the power supply, form the wiring orderly so that the
control box lid can be securely fastened.
If the control box lid is not in place, overheat of the
terminals, electric shocks or a re may be caused.
• If refrigerant gas leaks during installation work, ventilate
the area immediately.
Toxic gas may be produced if refrigerant gas comes into
contact with a re.
• After completing the installation work, check to make sure
that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the
room and comes into contact with a source of a re, such
as a fan heater, stove or cooker.
• Never directly touch any accidental leaking refrigerant.
This could result in severe wounds caused by frostbite.
CAUTION
• Install drain piping according to this installation manual to
ensure good drainage, and insulate the piping to prevent
condensation.
Improper drain piping may cause water leakage, make the
furniture get wet.
Installation
manual
VRV System
air conditioner
FXVQ125MY1 FXVQ200MY1 FXVQ250MY1 FXVQ400MY1 FXVQ500MY1 FXVQ500MY16
01_EN_3P345056-4F.indd 1 9/3/2015 15:00:21
Содержание
- Installation manual 1
- System air conditioners 1
- Contents 2
- Safety precautions 2
- 1 precaution 3
- 2 accessories 3
- 3 carry out the work giving caution to the following items and after the work is completed check these again 3
- Be sure to instruct the customer how to properly operate the system particularly the cleaning of air filter operation method temperature adjusting method showing the attached operation manual to the person do not install the unit where the atmosphere is salty such as near the seaside where the voltage frequently fluctuates or in a vehicle or a boat 3
- Before installation 3
- Check if the following accessories are included in the indoor unit 3
- English 3
- Install the air conditioner power supply wiring remote controller wiring and transmission wiring at least 1 meter away from televisions or radios to prevent image interference or noise depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise do not install the air conditioner in places such as the following 1 where there is mist of oil oil spray or vapour for example a kitchen resin parts may deteriorate and cause them to fall out or water to leak 2 where corrosive gas such as sulfurous acid gas is produced corrosion of copper pipings or brazed parts may cause the refrigerant to leak 3 where there is machinery which emits electromagnetic waves electromagnetic waves may disturb the control system and cause malfunction of the equipment 4 where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air or where volatile flammables such as thinner or gasoline are handled if the gas should leak and remained around the air con 3
- Items to be checked after the installation work is completed 3
- Make sure to recheck the items of safety precautions 3
- Make sure to use the r410a refrigerant before the installation work otherwise the unit can not operate normally for installation of outdoor unit refer to the installation manual attached to the outdoor unit do not throw away the accessories required for installation until the installation is finished 3
- 1 example of required space 4
- Carry in method 4
- Installation site 4
- 1 how to replace pulley 5
- 1 material of piping 5
- 1 remove the suction grille 2 remove the protection net then remove the cushioning material on the protection net 3 remove the front panel upper 4 remove the front panel lower 5 put the iron plate which must be wider than the fan motor under the fan motor and on the heat exchanger for protection for its fin iron plate must be supplied in the field 6 remove the terminal for the fan motor lead wire from the magnet switch 7 pull out the fan motor lead wire to the fan housing parts and let it out of the unit from the opening part on the front plate upper 8 remove the nuts of the motor base 9 remove the belt hold the fan motor base firmly when working so that it may not move suddenly 10 slide the fan housing assembly on the iron plate on which the fan motor is put the above procedure 5 frontward slowly work must be conducted by more than 3 persons one of them must hold the motor base and two or more of them must hold the fan housing 11 move the fan housing assembly to the location where can 5
- 2 parallelism of pulley 5
- 3 tension of v belt 5
- Adjust the parallelism of the pulley between the fan and the motor so as to meet the standard as below 5
- Caution 5
- Caution at installation 5
- English 5
- Follow the above procedure 1 4 6 7 10 11 12 in the order 5
- For the refrigerant piping of the outdoor unit refer to the installation manual attached to the outdoor unit make sure to use r410a as refrigerant before the installation work otherwise the unit can not operate normally make sure to insulate the piping on both the liquid side and the gas side otherwise water leakage may be caused use a heat insulating material sufficiently resistant to 120 c reinforce the refrigerant piping according to the installation environment otherwise condensation may form on the surface of the insulation 5
- Note it is recommended to check the tension as above after 24 28 hours of the operation when the new belts are used it is preferable to adjust to about 1 times the maximum value of deflection load w 5
- Refrigerant piping 5
- Tension of a v belt must meet the deflection load w as shown calculate the required deflection length l by the equation 1 its tolerance must be within the range as below 5
- This unit is for using r410a only make sure to follow the items as shown in below when working use the pipe cutter and the flaring tool that are exclusively used for r410a at flare connection apply ether oil or ester oil to the flare section protect the piping by a pinch or taping to prevent invasion of contamination moisture and dusts into the piping 5
- Use the copper tube according to the following table 5
- 1 install drain piping 7
- Drain piping 7
- Electric wiring 7
- 1 remove the front panel lower 8
- 1 remove the front panel lower 2 fix the each wire on the control box with the attached clamp 3 for wiring specifications refer to the details of standard devices 8
- 2 external wiring method 8
- 3 example of wiring 8
- Apply putty or insulation material field supply without any clearance on the wiring intake section to prevent small animals from entering the unit if small animals such as insects enter the inside of the unit it may cause short circuit in the control box connect the wire securely using designated wire and fix it with attached clamp without applying external pressure on the terminal parts make sure the wiring and the control box lid do not stick up above the structure and close the control box lid firmly 8
- Caution 8
- Do not have low voltage wires wiring between units and other high voltage run through the same locations and there must be min 50 mm distance between wires outside of the unit or it may cause a malfunction or a breakdown of the unit by receiving electrical noise external noise 8
- Downloaded from www manualslib com manuals search engine 8
- English 8
- Ex2 for multiple indoor units 8
- F1f2 t1t2 8
- Prohibited 8
- The control panel is the standard built in ex1 when using in pairs 8
- When removing the front panel lower there is the control box 8
- Wiring from left side 8
- Wiring from right side 8
- 4 precautions when laying power wiring 9
- 5 details of standard devices 9
- Abnormal heating may occur if the wirings are not tightened securely 9
- Caution for wiring 9
- Connect the terminal as shown in fig 2 do not carry out soldering finish when stranded wires are used otherwise the loosening of wires may result in abnormal heat radiation 9
- Do not carry out soldering finish when stranded wirings are used 9
- Electrical characteristics 9
- English 9
- Ex3 for group control 9
- Ex4 when including bs unit 9
- For connection to the terminal block use ring type crimp style terminals with insulation sleeve or insulate the wirings properly 9
- If an improper screw driver is used it may damage the screw head and a proper tightening cannot be carried out if a terminal is over tightened it may be damaged refer to the table shown below for tightening torque of terminals 9
- Note 1 it is not necessary to set the indoor unit address for group control the setting is made automatically when the power supply is turned on 2 make sure to disconnect the control panel wiring of the units over the second one 3 in this case all indoor units within the group are controlled by the control panel for the group control 9
- Refer to the installation manual attached to the outdoor unit for the details of the wire gauge of the power supply to the outdoor unit the earth leakage breaker the circuit breaker capacity and wiring use only the wiring devices specified in the following table for the wiring between indoor unit and outdoor unit branch off the exclusive lines for power supply to the indoor unit according to the following specification 9
- Table 1 9
- Use a proper screw driver for tightening the terminal screws 9
- Use the required wirings connect them securely and fix these wirings securely so that external force may not apply to the terminals 9
- Warning 9
- When wiring form the wirings orderly so that the control box lid can be securely fastened if the control box lid is not in place the wirings may come out or be sandwiched by the box and the lid and cause electric shocks or a fire 9
- 1 field setting 10
- Field setting and control wiring 10
- 2 remote controller and centralized control 11
- Trial operation 11
- P345056 4f em13a004b 12
Похожие устройства
- Daikin FXVQ500MY1 Брошюра
- Daikin FXVQ500MY1 Технические данные
- Daikin FXVQ500MY16 Инструкция по монтажу
- Daikin FXVQ500MY16 Брошюра
- Daikin FXVQ500MY16 Технические данные
- Daikin FXN20LVE Сервис мануал
- Candy CMXC 30DCS Техническое описание
- Candy CMXC 30DCS Руководство пользователя
- Daikin FXN25LVE Сервис мануал
- Candy CMXG 25DCW Техническое описание
- Candy CMXG 25DCW Руководство пользователя
- Daikin FXN32LVE Сервис мануал
- Candy CMXW 30DS Техническое описание
- Candy CMXW 30DS Руководство пользователя
- Daikin FXN40LVE Сервис мануал
- Daikin FXN50LVE Сервис мануал
- Daikin FXN63LVE Сервис мануал
- Candy CMXG20DR Техническое описание
- Candy CMXG20DR Руководство пользователя
- Candy CMW 2070S Техническое описание