Test Operation SiBE37-704_A
191 Test Operation
Remote controller heating mode malfunction codes
Remote controller cooling mode malfunction codes
1.2.6.6
Procedure for inputting the additional refrigerant charge weight into the PCB
Availability of the leak detection function feature requires input of the additional refrigerant
charge amount immediately after finishing the automatic charging. The input must be executed
before performing the test operation.
If a wrong value is inputted for the additional charged refrigerant weight, the accuracy of the
leak detection function will decrease.
Procedure
1. Close the electric box lid and all front panels except the one on the side of the electric box.
2. Press and hold the BS1 MODE button for 5 seconds to enter into setting mode 2.
The H1P LED is on
k.
3. Press the BS2 SET button 14 times.
The LED display must be as follows:
Press the BS3 RETURN button once as confirmation of the LEDs combination.
LEDs will be blinking in function of the last entered setting (factory setting = 0 kg).
4. The weighed and already recorded amount of additional refrigerant charge (not the total
amount of refrigerant present in the system) must be entered by selecting the corresponding
LED display.
Scroll through the possible LED combinations by pressing the BS2 SET button until the LED
3. Remote controller malfunction code display
Error code
P8
recharge
operation
Close valve A immediately and press the TEST OPERATION button once.
The operation will restart from the charging mode judgement onwards.
P2
charge hold
Close valve A immediately. Check following items:
- Check if the gas side stop valve is opened correctly
- Check if the valve of the refrigerant cylinder is
opened
- Check if the air inlet and outlet of the indoor unit are
not obstructed
After correcting the
abnormality, restart the
automatic charging
procedure again.
Error code
PA, PH, PC
replace
cylinder
Close valve A and replace the empty cylinder. When renewed, open valve A (the
outdoor unit will not stop operating).
The code on the display shows the unit where a cylinder is to be renewed:
PA
= master unit,
PH
= slave unit 1,
PC
= slave unit 2, flashing
PA
,
PH
and
PC
= all units
After replacing the cylinder, open valve A again and continue the work.
In case of an outdoor multi system, replacing the refrigerant tank of the
outdoor unit during the refrigerant charging operation when the display on the
remote controller is not showing
PA, PH
or
PC,
may cause an abnormal stop
of the refrigerant charging operation.
P8
recharge
operation
Close valve A immediately.
Restart the automatic charging procedure again.
P2
charge hold
Close valve A immediately. Check following items:
- Check if the high pressure/low pressure gas pipe,
suction gas pipe, liquid pipes and equalizer pipe
stop valves are opened correctly
- Check if the valve of the refrigerant cylinder is
opened
- Check if the air inlet and outlet of the indoor unit are
not obstructed
After correcting the
abnormality, restart the
automatic charging
procedure again.
*
abnormal
stop
Close valve A immediately. Confirm the malfunction
code by the remote controller and correct the
abnormality by following the "Correcting after abnormal
completion of the test operation" on page 199.