SiENBE37-704 Specifications
Specifications 33
1-1 TECHNICAL SPECIFICATIONS FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on: indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Sound pressure levels are measured at 220V
1-2 ELECTRICAL SPECIFICATIONS FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE
Power
Supply
Name VE
Phase 1 1 1 1
Frequency Hz 50 50 50 50
Voltage V 220-240
Current Minimum circuit amps
(MCA)
A 0.30 0.30 0.30 0.50
Maximum fuse amps
(MFA)
A 15.00 15.00 15.00 15.00
Full load amps (FLA) A 0.20 0.20 0.20 0.40
Voltage
range
Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA <= 4 × FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
Finally, click on the document title of your choice.