SiENBE37-704 Specifications
Specifications 45
1-2 ELECTRICAL SPECIFICATIONS FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MAVE
Power
Supply
Name VE
Phase 1 1 1 1
Frequency Hz 50 50 50 50
Voltage V 220-240
Current Minimum circuit amps
(MCA)
A 1.30 1.30 1.30 1.50
Maximum fuse amps
(MFA)
A 15.00 15.00 15.00 15.00
Full load amps (FLA) A 1.00 1.00 1.00 1.20
Voltage
range
Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage rang variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA <= 4 × FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet. daikineurope. com, select "E-Data Books".
Finally, click on the document title of your choice.
1-2 ELECTRICAL SPECIFICATIONS FXMQ100MAVE FXMQ125MAVE FXMQ200MAVE FXMQ250MAVE
Power
Supply
Name VE
Phase 1 1 1 1
Frequency Hz 50 50 50 50
Voltage V 220-240
Current Minimum circuit amps
(MCA)
A 2.50 3.80 8.10 9.00
Maximum fuse amps
(MFA)
A 15.00 15.00 15.00 15.00
Full load amps (FLA) A 2.00 3.00 6.50 7.20
Voltage
range
Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA <= 4 × FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet. daikineurope.com, select"E-Data Books".
Finally, click on the document title of your choice.