Specifications SiENBE37-704
44 Specifications
Concealed Ceiling Unit (Large)
1-1 TECHNICAL SPECIFICATIONS FXMQ100MAVE FXMQ125MAVE FXMQ200MAVE FXMQ250MAVE
Nominal
Capacity
Cooling kW 11.20 14.00 22.40 28.00
Heating kW 12.50 16.00 25.00 31.50
Power input
(Nominal)
Cooling kW 0.411 0.619 1.294 1.465
Heating kW 0.411 0.619 1.294 1.465
Casing Material Galvanised steel
Dimensions Unit Height mm 390 390 470 470
Width mm 1,110 1,110 1,380 1,380
Depth mm 690 690 1,100 1,100
Weight Unit kg 63 65 137 137
Heat
Exchanger
Dimensions
Nr of Rows 3 3 3 3
Fin Pitch mm 2.00 2.00 2.00 2.00
Face Area 0.319 0.319 0.68 0.68
Nr of Stages 16 16 26 26
Fan Type Sirocco fan
Quantity 1 1 2 2
Air Flow
Rate
Cooling High m³/min 29.00 36.00 58.00 72.00
Low m³/min 23.00 29.00 50.00 62.00
Fan External
static
pressure
High Pa 157 191 221 270
Standard Pa 98 152 132 147
Motor Quantity 1 1 2 2
Model 2D11/2D3AG1VE 2D11/2D3AF1VE D13/4G2DA1 D13/4G2DA1
Output
(high)
W 270 430 380 380
Drive Direct drive
Refrigerant Name R-410A
Cooling Sound
Pressure
High dBA 43.0 45.0 48.0 48.0
Low dBA 39.0 42.0 45.0 45.0
Piping
connections
Liquid
(OD)
Type Flare connection
Diameter mm 9.5 9.5 9.5 9.5
Gas Type Flare connection Flare connection Braze connection Braze connection
Diameter mm 15.9 15.9 19.1 22.2
Drain Diameter mm 32 32 PS1B PS1B
Heat Insulation Glass fiber
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating
Safety devices PC board fuse
Fan motor thermal protector
Standard
Accessories
Standard Accessories Installation and operation manual
Drain hose Connection pipes
Sealing Pads
Clamps
Screws
Insulation for fitting
Clamp metal
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The external static pressure is changeable : change the connectors inside the electrical box, this pressure means :
High static pressure-standard
Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its colorimetric method (gravity method) 50% or more.
Sound pressure levels are measured at 220V
FXMQ200, 250MAVE cannot be connected to VRVIII-S