SiENBE37-704 Specifications
Specifications 47
1-2 ELECTRICAL SPECIFICATIONS FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE
Power
Supply
Name VE
Phase 1 1 1
Frequency Hz 50 50 50
Voltage V 220-240
Current Minimum circuit amps
(MCA)
A 0.80 0.80 0.90
Maximum fuse amps
(MFA)
A 15.00 15.00 15.00
Full load amps (FLA) A 0.60 0.60 0.70
Voltage
range
Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%
MCA/MFA : MCA = 1.25 × FLA
MFA <= 4 × FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
Finally, click on the document title of your choice.