TRACO POWER TPP 100-112 Инструкция по установке онлайн

TRACO POWER TPP 100-148 Инструкция по установке онлайн
INSTALLATION INSTRUCTIONS
TPP 100 Series Switching Power Supply
Order Code
Nominal AC-Input
Voltage Range
Input
Voltage Range
*Output
Power max.
**DC-Output Circuit breaker
TPP 100-112
100 240Vac
50/60Hz
Universal Input
85 264Vac
47 63Hz
120 370Vdc
100 W
12.0Vdc / 8.34A
Internal
T3.15A/250Vac
fuse in line and
neutral (soldered)
TPP 100-115
15.0Vdc / 6.67A
TPP 100-124
24.0Vdc / 4.17A
TPP 100-136
36.0Vdc / 2.78A
TPP 100-148
48.0Vdc / 2.09A
*Total output power must not exceed specified max output power.
**Output adjustable by potentiometer with an insulated screwdriver.
Max. Input
current
@ V
in
= 115Vac @ V
in
= 230Vac
Typ. Power
Consumption
@ V
in
= 115Vac @ V
in
= 230Vac
TPP 100
1.15A max.
0.55A max.
TPP 100
114W typ.
Output Voltage Adjustment Range typical ±10%
Output Power Derating
above +50°C ambient temperature 2.33%/K
below 100Vac input voltage
1.33%/V
Operating Temperature Range
(with natural air convection cooling)
-25°C to +80°C
Storage Temperature Range -40°C to +85°C
Input and Output Connectors
Screw type terminal for AWG 26..16
Recommended tightening torque 0.2Nm (1.8lb.in.)
Wire end sleeve recommended
Terminal rated for 10A max (higher current connection has to be splitted)
Protective Earth PE connection is not required (protection class II prepared)
Case Material
Aluminium base
Mounting Position
Vertical (for best cooling conditions)
Mounting Inserts
8 x M3 on the bottom side (max mounting screw penetration: 2.0mm)
Recommended tightening torque 0.5Nm (4.4lb.in.)
Options
DIN-Rail clip (TPP-MK1)
Customized case and connectors on request
http://www.tracopower.com Rev: 51/13
Скачать