Selection of Pipe Size, Joints and Header Si38-304
318 Appendix
6.2 RXY18MY1, RXY20MY1, RXY22MY1, RXY24MY1,
RXY26MY1, RXY28MY1, RXY30MY1, RXY32MY1,
RXY34MY1, RXY36MY1, RXY38MY1, RXY40MY1,
RXY42MY1, RXY44MY1, RXY46MY1, RXY48MY1
6.2.1 How to select the REFNET Joint
How to select the REFNET Joint
Select the REFNET Joint from the following table.When using REFNET Joints at the first branch
counted from the outdoor unit side.
For REFNET Joints other than the first branch, select the proper ones based on the total
capacity index of the indoor units installed after the first branch using the following table :
6.2.2 How to select pipe size
Main Piping (Between Multi connection piping kit and REFNET Joint)
Select the proper ones based on the following table :
Piping Material
Select the piping material to be used from the next table according to piping size.
(Ex. : REFNET Joint A)
Outdoor Unit REFNET Joint(Kit Name)
RXY18-24MY1 KHRJ26K40T+KHRJ26K40TP
(Pipe Size Reducer)
RXY26-34MY1 KHRJ26K75T+KHRJ26K75TP
(Pipe Size Reducer)
RXY36-48MY1 KHRJ26K75T+KHRJ26K76TP
(Pipe Size Reducer)
Total capacity index of indoor units REFNET Joints (Kit Name)
<100 KHRJ26K11T
100x<160 KHRJ26K18T
160x<330 KHRJ26K37T
330x<640 KHRJ26K40T+KHRJ26K40TP
(Pipe Size Reducer)
640x<900 KHRJ26K75T+KHRJ26K75TP
(Pipe Size Reducer)
900 KHRJ26K75T+KHRJ26K76TP
(Pipe Size Reducer)
Outdoor Unit Gas Liquid
RXY18MY1 φ34.9 φ19.1
RXY20MY1
RXY22MY1
RXY24MY1 φ41.3
RXY26MY1 φ22.2
RXY28MY1
RXY30MY1
RXY32MY1
RXY34MY1
RXY36MY1 φ54.1
RXY38MY1
RXY40MY1
RXY42MY1
RXY44MY1
RXY46MY1
RXY48MY1
Piping Size (O / D) Temper grade of Material
φ19.1 or less O
φ22.2 or more 1 / 2H or H