2.3.1 Terminal assignment of connectors
3. Function
3.1 Signalling
The DC-IN-OK, BATT-OK and DC-OUT-OK outputs are for enabling monitoring of the functions of the TSP-BCMxx(A)), input
and battery. The floating DC-IN-OK signal contacts (see Fig. 2.1 Connector J5, pin 1 & pin 2) are opened if the input voltage
is not present.
The floating BATT-OK signal contacts (see Fig. 2.1 Connector J5, pin 3 & pin 4) is monitoring if the battery can supply
enough current for a given time.
The floating DC-OUT-OK (see Fig. 2.1 Connector J5, pin 5 & pin 6) is available to monitor if the TSP-BCM12, TSP-BCM24(A) or
TSP-BCM48(A) provides an output voltage. If the output voltage on the TSP-BCM24 or TSP-BCM24A is present, the relay contact
(30Vdc / 0.6A or 60Vdc / 0.3A) is closed. It is detected by measuring the TSP-BCM12, TSP-BCM24(A) or TSP-BCM48(A) output
voltage.
TSP-BCM12, TSP-BCM24(A) & TSP-BCM48(A)
Pin No.
J1 J2 J3 J4 J5 J6
Pin 1
-Vin (DC In) GND (-) S+ 15 sec test DC-IN-OK Signal
Pos 2
(factory setting)
(other settings see chapter 3.5)
Pin 2
+Vin (DC In) GND (-) S- Com DC-IN-OK Relay contact
Pin 3
-Bat in Vout (+) - 10 min test BATT-OK Signal
Pin 4
+Bat in Vout (+) - - BATT-OK Relay contact
Pin 5
- - - - DC-OUT-OK Signal
Pin 6
- - - - DC-OUT-OK Relay contact
Pin 7
- - - - Remote ON/OFF
Pin 8
- - - - Remote ON/OFF
Pin 9
- - - - Temperature Sensing
Pin 10
- - - - Temperature Sensing
Fig. 2.1: Connectors of TSP Battery Module
Содержание
- Before installing and using the tsp bcm 12 2
- Connections wire table 2
- Disclaimer 2
- Electrical connections 2
- Mechanical mounting 2
- Step by step wiring instructions 2
- Wire and cable requirements 2
- Connection of tsp bcm12 tsp bcm24 tsp bcm24a tsp bcm48 tsp bcm48a 3
- Fig 1 connection of remote links to power supply 3
- Remote link 3
- Factory setting 4
- Function 4
- Signalling 4
- Tsp bcm12 tsp bcm24 a tsp bcm48 a 4
- Batt ok led 5
- Battery test jumper j4 5
- Dc in ok led 5
- Dc out ok led 5
- Remote on off 5
- Setting the max power input on the tsp bcm12 tsp bcm24 a or tsp bcm48 a 5
- Temperature sensing 5
- Fusing 6
- Wall mounting brackets tsp wmk01 for tsp bcm12 tsp bcm24 tsp bcm24a tsp bcm48 tsp bcm48a 7
Похожие устройства
- TRACO POWER TSP–BCM48 Datasheet
- TRACO POWER TSP–BCM48 Документация
- Daikin RXY26MTL Сервис мануал
- Daikin RXY26MTL Технические данные
- Daikin RXY26MTL Руководство по вводу в эксплуатацию
- TRACO POWER TSP–BCM24A Инструкция по эксплуатации
- TRACO POWER TSP–BCM24A Инструкция по установке
- TRACO POWER TSP–BCM24A Datasheet
- TRACO POWER TSP–BCM24A Документация
- TRACO POWER TSP–BCM48A Инструкция по эксплуатации
- TRACO POWER TSP–BCM48A Инструкция по установке
- TRACO POWER TSP–BCM48A Документация
- TRACO POWER TSP–BCM48A Datasheet
- Daikin RXY26MTLE Инструкция по эксплуатации
- Daikin RXY26MTLE Руководство по эксплуатации
- TRACO POWER TSP–REM360 Инструкция по эксплуатации
- TRACO POWER TSP–REM360 Datasheet
- TRACO POWER TSP–REM360 Инструкция по установке
- TRACO POWER TSP–REM360 Документация
- TRACO POWER TSP–REM600 Инструкция по эксплуатации