Daikin RXY48MY1 [327/346] Rxy5my1 rxy8my1 rxy10my1 rxy12my1 rxy14my1 rxy16my1

Daikin RXY12MYL [327/346] Rxy5my1 rxy8my1 rxy10my1 rxy12my1 rxy14my1 rxy16my1
Selection of Pipe Size, Joints and Header Si38-304
316 Appendix
6. Selection of Pipe Size, Joints and Header
6.1 RXY5MY1, RXY8MY1, RXY10MY1, RXY12MY1,
RXY14MY1, RXY16MY1
6.1.1 How to select the REFNET Joint
How to select the REFNET Joint
Select the REFNET Joint from the following table when using REFNET Joints at the first branch
counted from the outdoor unit side.
(Ex. : REFNET Joint A)
For REFNET Joints other than the first branch, select the proper ones based on the total
capacity index of the indoor units installed after the first branch using the following table :
6.1.2 How to select pipe size
Between outdoor unit and uppermost stream REFNET Joint.
Piping Material
Select the piping material to be used from the next table according to piping size.
6.1.3 How to select the REFNET header
Select the proper REFNET Header using the following table based on the total capacity index of
indoor units installed after the header.
Outdoor Unit REFNET Joints (Kit Name)
RXY5MY1 KHRJ26K18T
RXY8,10MY1 KHRJ26K37T
RXY12-16MY1 KHRJ26K40T+KHRJ26K40TP
(Pipe Size Reducer)
Total capacity index of indoor units REFNET Joints (Kit Name)
<100 KHRJ26K11T
100x<160 KHRJ26K18T
160x<330 KHRJ26K37T
330x<640 KHRJ26K40T+KHRJ26K40TP
(Pipe Size Reducer)
640x<900 KHRJ26K75T+KHRJ26K75TP
(Pipe Size Reducer)
Pipe size connected to outdoor unit.
Outdoor Unit Gas Liquid
RXY5M φ19.1 φ9.5
RXY8, 10MY1 φ28.6 φ12.7
RXY12-16MY1 φ34.9 φ15.9
Piping Size (O / D) Temper grade of Material
φ19.1 or less O
φ22.2 or more 1 / 2H or H
Total capacity index of indoor units REFNET Header (Kit Name)
<100 KHRJ26K11H
100x<160 KHRJ26K18H
160x<330 KHRJ26K37H
330x<640 KHRJ26K40H+KHRJ26K40HP
(Pipe Size Reducer)