Daikin REYQ10MY1B [206/312] Outdoor unit malfunction of transmission between inverter and control pc board

Daikin FXNQ63MVE [206/312] Outdoor unit malfunction of transmission between inverter and control pc board
Si39-302 Troubleshooting by Indication on the Remote Controller
Troubleshooting 195
2.35
LC
Outdoor Unit: Malfunction of Transmission Between
Inverter and Control PC Board
Remote
Controller
Display
LC
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Check the communication state between inverter PC board and control PC board by micro-
computer.
Malfunction
Decision
Conditions
When the correct communication is not conducted in certain period.
Supposed
Causes
!
Malfunction of connection between the inverter PC board and outdoor control PC board
!
Defect of outdoor control PC board (transmission section)
!
Defect of inverter PC board
!
Defect of noise filter
!
External factor (Noise etc.)