Daikin RXYQ34PY1C [122/125] Commissioning manual em11a021 dcm601a51 intelligent touch manager
![Daikin RXQ52PY1 [122/125] Commissioning manual em11a021 dcm601a51 intelligent touch manager](/views2/1708730/page122/bg7a.png)
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
121
Problem Checking method Cause Measure
Air conditioner
control
Air conditioners continue to work in cool mode
though the room temperature is lower than the
lower limit set up by the Temperature Limit function.
Check whether the subject indoor
units have Changeover Option.
The subject indoor units are
controlled by an upper unit with
Changeover Option.
Check the Temperature Limit settings.
Air conditioners continue to work in heat mode
though the room temperature is higher than the
upper limit set up by the Temperature Limit function.
Check whether the indoor units have
Changeover Option.
The subject indoor units are
controlled by an upper unit with
Changeover Option.
Check the Temperature Limit settings.
Indoor units working in automatic
mode switches to heat (cool) mode
spontaneously.
Check in the history whether the
Temperature Limit function is running.
The subject indoor units are controlled
by the Temperature Limit function.
Check the Temperature Limit settings.
Check in the history whether the Auto
Changeover function is running.
The subject indoor units are controlled
by the Auto Changeover function.
Check the Auto Changeover settings.
Check in the history whether
switching between cool and heat
modes is according to the Schedule
function.
Switching between cool and heat modes
is controlled by a schedule program.
Check the schedule program.
Check the history whether switching
between cool and heat modes is according
to the Interlocking Control function.
Switching between cool and heat modes
is controlled by an interlocking program.
Check the interlocking program.
Check the history whether switching between
cool and heat modes is carried out manually.
Switching between cool and heat
modes is carried out manually.
PPD Cannot connect iTM to PPD
engineering tool.
When iTM and PC are connected via
hub, check whether they are correctly
connected.
PC is not connected with iTM. Connect the iTM and PC via hub
using LAN cables.
Cross cables are used as the LAN cables
connecting the iTM and hub, and PC and hub.
Use straight cables as LAN cable for
connecting the iTM and PC via hub.
The hub is turned off. Turn on the hub.
Check that iTM is turned on. The iTM is turned off. Turn on the iTM.
Check whether the network settings
on the PC are in conformity with the
settings described in this manual.
The network settings on the PC are
incorrect.
Modify the network settings on the
PC so that they are in conformity with
the settings described in this manual.
When iTM and PC are connected
directly, check whether they are
connected using the correct cable.
The LAN cable connecting the iTM
and PC is a straight cable.
Connect the iTM and PC using a
cross cable.
A Firewall is installed on the PC.
Disable or delete the Firewall on the PC. (Be
warned that disabling or deleting the rewall may
expose the system to security vulnerabilities)
The pulse port is not displayed on the
PPD setup tool.
Check whether the Pi management
point is registered in iTM.
Pi management point is not registered.
Register the Pi management point.
When trying to run a trial for the set
up model on the PPD engineering
tool, some of the indoor units are not
automatically recognized.
Check whether the management
points registered in iTM are
experiencing communication error.
Indoor units are experiencing
communication error.
Find and solve the cause of the
communication error in the indoor
units.
Check whether the subject indoor
units are included in the model
database.
The subject indoor units are not
included in the model database.
Check whether the engineering tool
is the latest.
Check with System Support if they
are supported models.
If they are supported models, ask their capacity
and actual state. If they are models that must
be set up manually, set them up manually.
The calculated power measurement
at the iTM is 1/10 of the detected
kWh.
Check whether the pulse rate is “10”
for the management point.
1 kWh/pulse is set up for pulse rate
for the management point instead of
the intended 10 kWh/pulse.
Re-set the pulse rate to 10 kWh/
pulse.
The calculated power measurement
at the iTM is 10 times the detected
kWh.
Check whether the pulse rate is “1”
for the management point.
10 kWh/pulse is set up for pulse rate
for the management point instead of
the intended 1 kWh/pulse.
Re-set the pulse rate to 1 kWh/pulse.
The pulse value does not increase
for the displayed management point.
Check the port number to which the
pulse signal wire is connected.
The pulse signal wire is not
connected to the correct Pi port.
Connect the pulse signal wire to the
correct Pi port.
Check whether the detected kWh is
increasing.
The detected kWh is not increasing. Check whether the kWh meter is
correctly connected.
The total pulse value at the iTM does
not match the detected PPD value.
Check the history whether a power failure signal
has been input while iTM was being reset.
The pulse value has been partially
lost while iTM was being reset.
Give explanation to users.
Check the PPD engineering tool
settings.
PPD was set to not distribute the
consumed power while the air
conditioners are stopped.
Check the PPD specication. If there is any
problem, after consulting with the users,
modify settings to distribute the consumed
power while the air conditions are stopped.
Consumed power has been
distributed though operation time for
the subject indoor unit is “0”.
Check the PPD engineering tool
settings.
PPD was set to distribute the
consumed power also while the air
conditioners are stopped.
Check the PPD settings. If there is any
problem, after consulting with the users,
modify settings to not distribute the consumed
power while the air conditions are stopped.
Consumed power is “0” though the
subject indoor unit is operating.
Check the operation mode of the
indoor unit.
The operation mode was fan mode. Check the PPD settings.
The thermostat was always OFF
though the air conditioner was
operating in cool or heat mode.
Check the PPD settings.
Содержание
- Commissioning manual p.1
- Intelligent touch manager p.1
- Dcm601a51 p.1
- Service settings 3 p.2
- Basic functions 3 p.2
- System overview p.2
- Engineering p.2
- About the itm intelligent touch manager p.2
- Names and functions p.2
- Detailed screen description p.2
- Contents p.2
- Service settings 4 p.3
- System settings 7 p.3
- Optional functions 4 p.3
- Operating optional functions 7 p.3
- Itm integrator explanation 09 p.4
- Itm integrator 09 p.4
- Hardware specifications 22 p.4
- Useful information 20 p.4
- Appendix 20 p.4
- System overview p.5
- About the itm intelligent touch manager p.5
- 1 system configuration p.5
- Engineering p.6
- At the office see p.6
- 1 engineering workflow p.6
- Carried out on site after installation p.6
- At the site p.6
- Various engineering works are necessary for using the itm p.6
- The following diagram shows the engineering workflow p.6
- New installation without using the pre engineering tool p.6
- Engineering works can be roughly divided into those carried out at the office in advance and those p.6
- New installation by using the pre engineering tool p.7
- At the site p.7
- At the office see p.7
- 2 logging into service mode p.8
- Password after carrying out the special operation indicated below allows you to unlock the p.9
- Screen and log into the se mode p.9
- Furthermore if the screen is locked entering the service password instead of the administrator p.9
- Basic functions p.10
- Names and functions p.10
- Detailed screen description p.10
- 1 setup screen structure p.10
- 2 service settings tab p.11
- 3 system settings tab p.13
- The figure below shows the flowchart of a management point registration p.14
- Service settings p.14
- Basic functions p.14
- 1 mgmt point data regist p.14
- Registering a management point with the itm unit p.15
- Check items list p.20
- Touching the check button 13 checks the content of the current settings data and displays the p.20
- No error is displayed if no error is found touch the close button to close the screen p.20
- If an error is found discards the edited content retained until then and restores the saved original data p.20
- Checking the setting results p.20
- Check results on the information check screen p.20
- Management point type set up by switching the displayed tabs as necessary p.22
- Displayed items vary depending on the management point type p.22
- Detailed mgmt point attributes screen and button descriptions p.22
- Common 1 tab p.22
- The following describes the mng point attributes screen in detail p.22
- Tabs and items displayed on the mng point attributes screen vary depending on the selected p.22
- Sets common items for a management point p.22
- Sets up the port number and address to which the management point belongs p.23
- For the port number touch the modify button and enter it in the numerical input dialog that p.23
- For the address select it using the combo box p.23
- Duplicated addresses cannot be registered all addresses must be different p.23
- Appears p.23
- 15 port no text field address combo box p.23
- 17 mgmt pt id field p.24
- Set up information about the management point as necessary p.24
- Displays the management point id automatically allocated by the system however you cannot p.24
- Displays the detailed management point type however you cannot modify it here p.24
- 20 icon field p.24
- 19 detailed info text field p.24
- 18 name text field p.24
- Touch the modify button and set the icon in the icon setup screen that appears p.24
- Touch the modify button and enter the value in the text input dialog that appears p.24
- 16 detailed type field p.24
- Touch the modify button and enter the name in the name input dialog that appears p.24
- The range of values you can enter set is as indicated in the table below p.24
- The number of characters you can enter is 0 to 50 irrespective of single or double byte p.24
- Specify a name for the management point using 1 to 12 characters irrespective of single or p.24
- Sets up the management point name p.24
- Sets up the icon for the management point p.24
- Modify it here p.24
- Double byte p.24
- Acceptable range for each numeric value p.32
- Registering management points using a csv file p.34
- Management point data is registered can be used as a template for new implementations since p.37
- Csv file format p.37
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.37
- The format of the csv file output from the itm is as shown below a csv file output when no p.37
- The following table shows the csv format for management point data registration p.37
- Set to 1 when not used the item is regarded as not used if either the object type or object instance value is set to 1 for information on the object type refer to the applicable guideline iso16484 5 p.37
- Only the area used by the system and the header portion are output p.37
- Numeric values indicated in each item correspond to the column number in the csv file the first column is fixed and used for data type identification blank items indicate there is no applicable data p.37
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.38
- 2 other setting p.39
- 3 diii net engineering p.40
- Pressing the refresh button 5 updates 3 and 4 touching the ok button displays a p.41
- This itm is not displayed in 4 p.41
- That can be installed together are as follows p.41
- Range limit p.41
- Port selected in 3 where its name is displayed along with its main sub setting central units p.41
- If you install or uninstall another controller please review the configuration of the setpoint p.41
- Confirmation dialog touch the yes button to commit the screen closes and the system restarts p.41
- 3 is a list of connector plugs for each itm port 4 is a list of central units recognized on the p.41
- 5 changeover option p.42
- 4 time zone p.42
- The release button 3 the changeover option becomes selectable at that moment the p.43
- The displayed contents are as indicated in the table below p.43
- Settings button 2 the changeover option becomes able at that moment the changeover p.43
- Selectable touching the refresh button 4 updates the contents displayed in 1 close the p.43
- Select the indoor unit for which you want to set the changeover option from 1 and touch the p.43
- Select the indoor unit for which you want to release the changeover option from 1 and touch p.43
- Screen using the close button p.43
- Registered columns other than group addr are displayed blank p.43
- Option for the other indoor units in the same refrigeration system becomes n a p.43
- N a a group address not registered as a management point p.43
- Maintenance a group address of a connected unit under maintenance p.43
- Changeover option for the other indoor units in the same refrigeration system also becomes p.43
- 2 comm err group address of the connected unit with communication error p.43
- 1 is an air conditioner list displaying all group addresses when no management points are p.43
- 6 history mgmt delete p.44
- The management points as well as system settings p.45
- Set up most of the items at the office including detailed settings and automatic control settings for p.45
- Pre engineering tool and itm unit data flow diagram p.45
- Pre engineering is carried out to lessen the work to be carried out on site such as when installing p.45
- Making extensive modifications to the settings due to the implementation of new functions etc p.45
- Itm integrator uses the backup data for restoring because it is not compatible with the pre p.45
- Itm in a large new property modifying settings due to a large scale equipment renovation or p.45
- Input output function described in 4 1 and the backup function described in 4 9 you will be able to p.45
- Engineering tool p.45
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.45
- By using the pre engineering tool demo version for pc described here together with the csv file p.45
- 7 pre engineering p.45
- Relationship between the assumed scenario and functions p.46
- Download the pre engineering tool from the distributor s page p.47
- Displaying the main screen p.47
- To use the pre engineering tool a separate pc is necessary the requirements for the pc are as p.47
- Start up the pre engineering tool on the pc p.47
- Pc requirement for running the pre engineering tool p.47
- Indicated in the table below p.47
- Main screen p.48
- Scenario 1 installation to new property p.49
- Screen of demo version for pc p.50
- Scenario 2 maintenance of existing property when carrying out pre engineering using the current setting p.53
- Scenario 3 restore with existing property s backup data p.55
- Scenario 4 implementation of new functions due to existing property s upgrade p.56
- 8 upgrade p.56
- 9 backup p.57
- 10 installation p.59
- 11 contact info p.61
- The registered contact information can be checked on the contact tab of the information screen p.62
- Accessible from the standard view screen see user s manual em11a015 p.62
- Caution p.63
- 12 setting outdoor unit p.63
- Use internal pi or such other functions processed based on information from the outdoor units you p.64
- There are two jumper pins to be cut so be sure to cut both of p.64
- The total number of outdoor units connected to the diii net expander adapter whose j1 p.64
- The jumper pin to be cut is j1 only p.64
- Table of types p.64
- Precautions when using diii net expander adapter p.64
- Need to cut the jumper pin of the diii net expander adapter p.64
- Jumper pins were cut and those directly connected to itm should be 10 or less p.64
- Intended functions monitoring of outdoor units energy navigator and leakage detection p.64
- In the application using the diii net expander adapter if you monitor the outdoor units or p.64
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.64
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.65
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.66
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.67
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.68
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.69
- The schedule control function you can make the outdoor units run leakage check at a specified p.70
- The leakage check takes approximately 180 minutes to complete p.70
- The following shows the system configuration diagram p.70
- Systems for leakage leakage check can be carried our centrally for multiple refrigeration systems p.70
- System configuration p.70
- Scope of this specification p.70
- Leakage check is a function available in vrv iii or later outdoor units it checks refrigeration p.70
- Installed in a property by sending instructions from the itm to the outdoor units via diii net using p.70
- Date and time you can also run leakage check manually on site furthermore leakage check p.70
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.70
- Can also be run from the web remote management see page 90 p.70
- Before starting leakage check inform the user of note described on page 80 p.70
- 13 leakage check p.70
- The installation information p.71
- Amount of refrigerant charged by the outdoor unit using refrigerant charging operation p.71
- Without it the outdoor unit cannot recognize the amount of automatically charged refrigerant p.71
- The outdoor unit s address is necessary make sure addresses are set up in advance p.71
- The following preparations are necessary for running leakage check p.71
- Registering indoor units p.71
- Refrigerant charging operation must have been run during installation and trial of outdoor units p.71
- Refrigerant charging operation p.71
- Preparations p.71
- Outdoor unit s address setting see installation manual em11a016 p.71
- Manually register indoor units that belong to the refrigeration system of each outdoor unit based on p.71
- Log into se mode from the menu list screen and display the service settings tab see page 7 p.71
- Leakage check is not possible if refrigerant charging operation has not been run because p.71
- Leakage check functions p.71
- Running leakage check by schedule control p.73
- Copying a schedule program p.75
- Starting leakage check by manual operation p.76
- Stopping leakage check by manual operation p.77
- When operation is via web connection the csv is output to the hdd of the pc connected p.78
- To the web p.78
- The csv file format specification is as follows p.78
- Outputting the leakage check results to a csv file p.78
- Output the leakage check results to a csv file p.78
- Outdoor units registered in the outdoor unit list 19 as a csv file named leakagecheck csv if p.78
- Insert a usb memory into the itm and touch the csv output button 20 a confirmation dialog p.78
- File leakagecheck sequential number 1 to 9 if there are no more sequential numbers that can p.78
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.78
- Be used an error dialog is displayed and the output to csv file aborted p.78
- Appears touching the yes button outputs to the usb memory the leakage check results for all p.78
- A file with the same name already exists the leakage check results are saved by naming the p.78
- Caution p.79
- The following describes the operation when another control comes into conflict with the leakage p.80
- Conflict with other controls p.80
- The following describes the failure modes of the leakage check p.82
- Failure mode p.82
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.82
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.83
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.84
- Service settings p.85
- Optional functions p.85
- Entering the activation key p.85
- Acquiring the activation key p.85
- 1 activation p.85
- 2 dealer option setup p.87
- System settings p.88
- Operating optional functions p.88
- 1 network p.88
- For settings necessary on the itm unit see 6 1 network this chapter describes the pc setup p.91
- 2 web remote management p.91
- To use the web remote management functions you need to separately prepare a pc and software p.91
- The itm can be remotely operated via the internet or local network p.91
- Such as a web browser the requirements for the pc are as indicated in the table below p.91
- Procedure p.91
- When connecting the pc and itm via a hub p.92
- When connecting the pc and itm directly p.92
- Use a 100base tx or higher ethernet straight cable p.92
- Use a 100base tx or higher ethernet cross cable p.92
- Straight cable connection diagram cross cable connection diagram p.92
- Ethernet cables use for connecting networks come in two types straight and cross connect the pc p.92
- Connecting the pc and itm p.92
- Connect the pc and itm unit into a network using an ethernet cable p.92
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.92
- And itm unit by referring to the connection diagrams below p.92
- Checking the web browser and flash player versions p.93
- Setting up the ip address windows xp professional p.94
- Double click local area connection p.95
- Click network connections p.95
- Select properties p.96
- Select internet protocol tcp ip and click properties p.96
- To connect to the itm via the internet ask its ip address and subnet mask to your network p.97
- Set them up as follows when connecting to the itm via local network p.97
- Properties and local area connection properties screens p.97
- Itm settings at shipment are as follows p.97
- Ip address 192 68 subnet mask 255 55 55 p.97
- Click close to close the local area connection status screen and finish setup p.97
- Check that the settings are correct and click ok to close the internet protocol tcp ip p.97
- Administrator and set them up p.97
- Setting up the ip address windows vista business p.98
- Double click local area connection p.99
- Click manage network connections p.99
- Click properties p.100
- Select internet protocol version 4 tcp ipv4 and click properties p.100
- Setting up the ip address windows 7 professional p.102
- Select properties p.103
- Double click local area connection p.103
- To connect to the itm via the internet ask its ip address and subnet mask to your network p.104
- Select internet protocol version 4 tcp ipv4 and click properties p.104
- Administrator and set them up p.104
- Precautions when using internet explorer on windows vista and windows 7 p.105
- Network connection check p.106
- Check whether the ethernet connection between a pc and itm is normal p.106
- Carry out the following procedure from the pc p.106
- The command prompt starts up type ping followed by one single byte space and then the itm p.108
- Ip address and press the enter key in this example the ip address is 192 68 p.108
- Logging into service mode via web remote management p.109
- 1 basic setup p.110
- Itm integrator p.110
- Itm integrator explanation p.110
- Set up the itm integrator unit p.115
- To be made in the respective itm or from the itm integrator standard view screen by accessing p.115
- The respective itm p.115
- Service settings described in this chapter are for the itm integrator unit settings for itm units are p.115
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.115
- 2 itm integrator service settings p.115
- Service settings tab menu list screen p.116
- Controller access setup p.117
- Useful information p.121
- Troubleshooting table p.121
- Appendix p.121
- 1 troubleshooting p.121
- Commissioning manual em11a021 dcm601a51 intelligent touch manager p.122
- Hardware specifications p.123
- 1 itm hardware specification p.123
- Em11a02 p.125
Похожие устройства
-
Daikin FXSQ125A2VEBРуководство по запуску и установке -
Daikin FXSQ100A2VEBРуководство по инсталляции -
Daikin FXSQ80A2VEBИнструкция по монтажу -
Daikin FXSQ63A2VEBРуководство по монтажу -
Daikin FXSQ50A2VEBИнструкция по монтажу -
Daikin FXSQ40A2VEBИнструкция по монтажу -
Daikin FXSQ32A2VEBИнструкция по установке -
Daikin FXSQ25A2VEBИнструкция по установке -
Daikin FXSQ20A2VEBРуководство по инсталляции -
Daikin FXSQ15A2VEBИнструкция по монтажу -
Daikin RXYQ54PYLСервис мануал -
Daikin RXYQ52PYLСервис мануал