Daikin RXYQ54PY1C [38/125] Commissioning manual em11a021 dcm601a51 intelligent touch manager

Daikin RXQ40PHY1 [38/125] Commissioning manual em11a021 dcm601a51 intelligent touch manager
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
37
Classication
Keyword Description Value
Management point type
Di Pi D3Di D3Dio
Indoor
unit
Outdoor
unit
Internal
Ai
Ventilator
Chiller
Internal
Pi
BACnet
Di
BACnet
Dio
BACnet
Ai
BACnet
Ao
Di/Dio DIMODE Di Operation mode 0: Normal, 1: Equipment error input 9
CPTYPE Point type 0: B type, 1: A type 10
LATEROPE Post-Priority 0: Disable, 1: Enable
ABNORMALOP Error output holding 0: Disable, 1: Enable
STARTFAIL
Error Mask Time after operation input
0: 10 seconds, 1: 30 seconds
MONITORIN Monitor input 0: Disable, 1: Enable
ABNORMAL INPUT Error input detection 0: B type, 1: A type
STARTSTOP FAILURE Start/Stop error 0: Disable, 1: Enable
OUTPUTSPECCONTACT Output contact 0: B type, 1: A type
Pi PVAL Pulse value 0 to 999999999, −1: Out of scope of merge 9
PCONST Pulse constant 1 to 999999 10
PRATIO Power ratio 0.01 to 99999.99 11
UNITSTR Unit string
String (0 to 8 characters regardless of single or double byte)
12 8
CFA
Correction coefcient a
0.000 to 1000.000 9
CFB
Correction coefcient b
−10.000 to 10.000 10
Ai/Ao
UNITSTR Unit string
String (0 to 8 characters regardless of single or double byte)
For Internal Ai:
Set to “°C” or “°F” depending on the System Settings if any
reference management point exists.
Set to “---” if no reference management point exists.
For other management points:
Set to “°C” or “°F” depending on the System Settings, except
when the Analog type is Temperature.
6 10 11
TARGETID
Target management point
Management point ID (indoor unit, chiller), −1: Not specied
7
TARGETTYPE
Measured analog value
1: Suction temperature, 2: Setpoint (Indoor unit)
1: Water inlet temperature,
2: Water outlet temperature (Chiller)
8
ANALOGTYPE Analog type 0: Normal, 1: Temperature 11 12
MARGIN Hysteresis See page 31. 9 12
UPPERVAL Upper limit See page 31. 10 13
LOWERVAL Lower limit See page 31. 11 14
ULMMONLV
Upper limit monitoring level
0: Disable, 1: Monitoring, 2: Monitor + History 12 15
LLMMONLV
Lower limit monitoring level
0: Disable, 1: Monitoring, 2: Monitor + History 13 16
MINVAL Minimum value See page 31. 17
MAXVAL Maximum value See page 31. 18
TERMMINVAL
Terminal minimum value
See page 31.
TERMMAXVAL
Terminal maximum value
See page 31.
OPMINVAL
Minimum operation value
See page 31. 13
OPMAXVAL
Maximum operation value
See page 31. 14
OPUNIT
Displayed accuracy (exponent of 10)
See page 31. 15
Ventilator
VMODE Ventilation mode 0: Disabled, 1: Enabled 11
FRESHENUP Fresh up 0: Disabled, 1: Enabled 12
AUTOVOL Automatic air volume 0: Disabled, 1: Enabled 13