ED721208 Commissioning Manual
6
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
34
2. .QCFKPIC%58ƂNG
Load the edited CSV file. The edited data does not overwrite everything, it only merges the
difference to the current settings data.
Log into SE Mode from the Menu List screen and display the Service Settings tab (see page 7).
Touch the Mgmt. Point Data Register button on the Service Settings tab to display the main
Mgmt. Point Data Register screen.
(52)
Connect the USB memory to the iTM unit and touch the Load button (52).
File names that can be loaded are limited to “ManagementPointData.csv”+HCƂNGKUPCOGF
differently, rename it in advance.
6QWEJVJG;GUDWVVQPQPVJG%QPƂTOFKCNQIVJCVCRRGCTUVQUVCTVNQCFKPI