Daikin REYQ34M7W1B [17/32] Capacity correction ratio

Daikin REYQ34M7W1B [17/32] Capacity correction ratio
• Selection procedure
2
Systems • Selection procedure
16
2 Capacity correction ratio
2-12 REYQ16M7W1B
Rate of change in cooling capacity Rate of change in heating capacity
3D042144
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum)
under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.
3 Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit)
cooling / heating capacity
= cooling / heating capacity obtained from performance characteristics table x each capacity rate of change
When piping length differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is:
cooling / heating capacity = cooling / heating capacity of each unit x capacity rate of change for each piping length
4 When overall equivalent pipe length is 90m or more, the diameter of the main liquid pipes (outdoor unit-branch sections) must be increased.
5 When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only)
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Heating)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 1.0
6 In the combination which does not include cooling only indoor unit, calculate the equivalent length pipe by the following when you calculate cooling
capacity.
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 0.88
EXPLANATION OF SYMBOLS
H
p
: Level difference (m) between indoor and outdoor units with indoor unit in inferior position
H
M
: Level difference (m) between indoor and outdoor units with indoor unit in superior position
L: Equivalent pipe length (m)
α : Capacity correction factor
Diameter of above case
Model liquid
REYQ16MY1B ø 15.9
Diameter of gas pipes
Model liquid
REYQ16MY1B ø 12.7
80 m 40 m
Outdoor unit
Indoor unit
Equivalent length Equivalent length
Size increase
Branch
80 m 40 m
Equivalent length Equivalent length
Outdoor unit
Indoor unit
Size increase
Branch
BS unit

Содержание

Скачать