RXQ5~10 + RXYQ5~48M9W1B
VRVII System air conditioner
4PW21816-1A
Installation manual
8
6.3. Example of connection
Example of connection
(Connection of 8 indoor units Heat pump system)
Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
One outdoor unit
installed
(RX(Y)Q5~16)
When multiple
outdoor units
installed
(RXYQ18~...)
Install the joint part ( part in the figure) of the outdoor unit multi connection piping kit
horizontally with attention to the installation restrictions described in "connecting the
refrigerant piping".
(*) If the system capacity is RXYQ18 or more, re-read to the first outdoor branch as
seen from the indoor unit.
Maximum allowable length
Between outdoor and indoor units
Actual pipe length
Pipe length between outdoor(*) and indoor units 150 m
[Example] unit 8: a+b+c+d+e+f+g+p150 m [Example] unit 6: a+b+h150 m, unit 8: a+i+k150 m [Example] unit 8: a+i150 m
Equivalent length
Equivalent pipe length between outdoor(*) and indoor units 175 m (Assume equivalent pipe length of refnet joint to be 0.5 m and of the refnet header to be 1.0 m. (for
calculation purposes))
Total extension
length
Total piping length from outdoor unit* to all indoor units 300 m
Between outdoor branch and outdoor unit (Only for
RXYQ18 or more)
Actual pipe length Piping length from outdoor branch to outdoor unit 10 m. Approximate length: max. 13 m
Allowable height
Between outdoor and indoor units
Difference in
height
Difference in height between outdoor and indoor units (H1)50 m (40 m if outdoor unit is located in a lower
position).
Between indoor and indoor units
Difference in
height
Difference in height between adjacent indoor units (H2)15 m
Between outdoor and outdoor units
Difference in
height
Difference in height between outdoor unit (main) and outdoor unit (sub) (H3)5 m
Allowable length after the branch Actual pipe length
Pipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit 40 m
[Example] unit 8: b+c+d+e+f+g+p40 m
[Example] unit 6: b+h40 m, unit 8: i+k40 m [Example] unit 8: i40 m
Refrigerant branch kit selection
Refrigerant branch kits can only be used with R-410A.
How to select the refnet joint
•When using refnet joints at the first branch counted from the outdoor unit side.
Choose from the following table in accordance with the capacity of the outdoor unit.
•For refnet joints other than the first branch, select the proper branch kit model based on
the total capacity index.
How to select the refnet header
Choose from the following table in accordance with the total capacity of all the indoor
units connected below the refnet header.
Note: 250 type cannot be connected below the refnet header.
How to choose an outdoor branch kit (needed if the outdoor unit capacity type
is RXYQ18 or more.)
Choose from the following table in accordance with the number of outdoor units.
Example of downstream indoor units
[Example]
in case of refnet joint C; indoor units 3+4+5+6+7+8
[Example]
in case of refnet joint B; indoor units 7+8,
in case of refnet header; indoor units 1+2+3+4+5+6
[Example]
in case of refnet header;
indoor units 1+2+3+4+5+6+7+8
Use the outdoor unit multi connection piping kit that is sold separately as an option
(BHFQ22M909+1359) for the multi installation of outdoor units. Selection method is
as shown in the right table.
•Never use the outdoor unit multi connection piping kit (BHFQ22M909+1359) that are
sold separately as an option of M-type or T-joint.
indoor unit
refnet joint
refnet header
outdoor multi connection piping kit
a
ABCDEFG
bcdef
g
hi j kl mn
1234567
8
H2
H1
P
H1
H2
a
i
b
cde f
g
h
123456
k
j
78
A
B
a
H1
H2
cde
f
g
h
i
b
1234567
8
ab c d e f
g
8
H2
H1
H3
P
hi j kl mn
123456
7
H1
a
i
b
cde f
g
h
123456
k
j
7
8
AB
H2
H1
H3
a
cde
f
g
i
h
b
123456
7
8
H2
s
r
t
r10 m (Approximate length:
max. 13 m)
s10 m (Approximate length:
max: 13 m)
t10 m (Approximate length:
max 13 m)
Outdoor unit capacity type Refrigerant branch kit name
RXYQ5 KHRQ22M20T7
RXYQ8+10 KHRQ22M29T7
RXYQ12~22 KHRQ22M64T7
RXYQ24 KHRQ22M75T7
Indoor capacity type Refrigerant branch kit name
<200 KHRQ22M20T7
200x<290 KHRQ22M29T7
290x<640 KHRQ22M64T7
>640 KHRQ22M75T7
Indoor capacity type Refrigerant branch kit name
<290 KHRQ22M29H7 (Max. 8 kit)
290x<640 KHRQ22M64H7 (Max. 8 kit)
>640 KHRQ22M75H7 (Max. 8 kit)
Number of outdoor units Branch kit name
2 BHFQ22M909 (Max. 4 kit)
3 BHFQ22M1359 (Max. 8 kit)