Systemair SWL02 [11/22] Technical specifications

Systemair SWL22 [11/22] Technical specifications
SWL
11
Approved for 220V/1ph/60Hz. Product performance for 220V/1ph/60Hz will differ from stated data.
Technical specifications
Fan heater SWL (IP44)
Type Heat output*
1
[kW]
Air flow
[m³/h]
Air flow
[m³/s]
Sound power*
2
[dB(A)]
Sound pressure*
3
[dB(A)]
SWL02
12 650/1120 0,18/0,31
59 30/43
SWL12
19 1450/2450 0,40/0,68
70 41/54
SWL22
31 2200/3950 0,61/1,10
75 46/59
SWL32
50 4230/6450 1,18/1,79
72 46/56
SWL33
64 3700/5850 1,02/1,63
68 47/53
Fan heater SWL (IP44)
Type
t*
1,4
[°C]
Water volume*
5
[l]
Voltage
[V]
Amperage
[A]
Weight
[kg]
SWL02
36/30 1,3 230V~ 0,4 16
SWL12
27/22 1,5 230V~ 0,8 20
SWL22
29/23 2,7 230V~ 1,2 30
SWL32
27/23 3,8 230V~ 2,3 50
SWL33
37/32 5,2 230V~ 2,3 53
*
1
) Applicable at water temperature 80/60 °C, air temperature, in +15 °C.
*
2
) Sound power (L
WA
) measurements according to ISO 27327-2: 2014, Installation type E.
*
3
) Sound pressure (L
pA
). Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent
absorption area: 200 m². At lowest/highest airflow.
*
4
) t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
5
) Water volume inside water coil.
Extra air director
SWL
Air throw
Type Air throw
[m]
Air throw with
extra air director
[m]
SWL02 8 -
SWL12 12 16
SWL22 18 23
SWL32 24 31
SWL33 22 29
The air throw data above is valid when the horizontally adjustable air director is used and at highest air
flow and room temperature +18 °C. The air throw is defined as the distance in a straight angle from the fan
heater to the point where the average air speed has dropped to 0,5 m/s.