Systemair SWT02 [8/14] Protection class ip44 splash proof design ce compliant

Systemair SWT02 [8/14] Protection class ip44 splash proof design ce compliant
SWT
8
(1)
SE: Värme effekt
GB: Heat output
(2)
SE: Luftflöde
GB: Air flow
(3)
SE: Ljudnivå
GB: Soud level
(4a)
SE: Kastlängd
GB: Air distribution
(4b)
SE: Kastlängd med förlängningsstos
GB: Air distibution with extension sleeve
(5)
SE: Vattenvolym
GB: Water volume
Technical specification | Fan heater SWT 2
(6)
SE: Spänning
GB: Voltage
(7)
SE: Ström
GB: Amperage
(8)
SE: LxBxD
GB: LxWxH
(9)
SE: Vikt
GB: Weight
Type Heat (1)
output*
1
[kW]
Air flow (2)
[m
3
/h]
Air flow(2)
[m
3
/s]
Sound (3)
level*
2
[dB(A)]
t*
1,3
[°C]
Air throw*
4
(4a)
[m]
Air throw*
4
(4b) with
extension collar
[m]
SWT02 7,8/11 700/1100 0,19/0,31 37/53 33/29 2,2/4 4/7
SWT12 14/18 1300/2000 0,36/0,56 44/57 25/22 2,7/4,5 5/8
SWT22 29/40 2500/3900 0,69/1,08 48/60 34/30 4,5/7,5 7/12
Type Water (5)
volume*
5
[l]
Voltage (6)
[V]
Amperage (7)
[A]
LxWxH (8)
[mm]
Weight (9)
[kg]
RSK
(SE)
NRF
(NO)
SWT02 1,2 230V~ 0,4 705x535x330 19 672 67 03 850 23 11
SWT12 1,7 230V~ 0,6 825x625x355 26 672 67 04 850 23 12
SWT22 3,9 230V~ 1,0 1135x735x415 41 672 67 05 850 23 13
*
1
) Applicable at water temperature 80/60 °C, air temperature, in +15 °C.
*
2
) Conditions: Distance to the unit 5 metres.
*
3
) t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
4
) The air throw data above is valid when the horizontally adjustable air director is used and the outlet temperature is +40 °C and the
room temperature is +18 °C. The air throw is defined as the distance in a straight angle from the fan heater to the the point where the
air speed has dropped to 0,2 m/s.
*
5
) Water volume inside battery.
Protection class: (IP44), splash-proof design.