Daikin RXYQ72MTJU Сервис мануал онлайн

SiUS39 - 601
RXYQ72, 96, 144, 168, 192MTJU
R-410A Heat Pump 60Hz
RXYQ72MTJU RXYQ96MTJU
RXYQ144MTJU RXYQ168MTJU RXYQ192MTJU
Содержание
- Rxyq72 96 144 168 192mtju r 410a heat pump 60hz 1
- Sius39 601 1
- Functional parts layout 6 2
- Introduction vi 2
- Model names of indoor outdoor units 2 external appearance 2
- Model selection 2
- Operation mode 2 2 basic control 3 2
- Part 1 general information 1 2
- Part 2 specifications 5 2
- Part 3 refrigerant circuit 3 2
- Part 4 function 31 2
- R 410a heat pump 60hz 2
- Refrigerant circuit 4 2
- Refrigerant flow for each operation mode 7 2
- Special control 0 2
- Specifications 2
- Table of the contents 2
- Other control 4 3
- Outdoor unit pc board layout 8 3 field setting 9 3
- Outline of control indoor unit 8 3
- Part 5 test operation 3 3
- Part 6 troubleshooting 105 3
- Protection control 9 3
- Test operation 4 3
- Troubleshooting by indication on the remote controller 20 3
- Troubleshooting by remote controller 08 3
- Part 7 replacement procedure for inv compressor vrv 217 5
- Part 8 appendix 219 5
- Piping diagrams 20 5
- Replacement procedure for inv compressor vrv rxyq72m 96m 18 5
- Troubleshooting op central remote controller 94 5
- Troubleshooting op schedule timer 00 5
- Troubleshooting op unified on off controller 08 5
- Drawings flow charts v 6
- Example of connection 37 6 thermistor resistance temperature characteristics 39 7 pressure sensor 41 8 method of replacing the inverter s power transistors and diode modules 42 6
- Index i 6
- List of electrical and functional parts 30 6
- Option list 35 6
- Part 9 precautions for new refrigerant r 410a 245 6
- Precautions for new refrigerant r 410a 46 6
- Wiring diagrams for reference 23 6
- Caution in repair 7
- Introduction 7
- Safety cautions 7
- Warning 7
- Caution 8
- Cautions regarding products after repair 8
- Warning 8
- Caution 9
- Inspection after repair 9
- Warning 9
- Caution 10
- Icons are used to attract the attention of the reader to specific information the meaning of each icon is described in the table below 10
- Using icons 10
- Using icons list 10
- Warning 10
- Preface 11
- Part 1 general information 12
- 208 230v 60hz 13
- 208 230v 60hz t 13
- Indoor units 13
- Model names of indoor outdoor units 13
- Outdoor units inverter series 13
- This time we publish sius39 601 new information rxyq 72 144 168mtju wall mounted type fxaq07 09mvju as shown by 13
- External appearance 14
- Indoor units 14
- Outdoor units 14
- Connectable indoor unit 15
- Connectable indoor units number and capacity 15
- In some models it is not possible to connect the maximum number of connectable indoor units select models so the total capacity of connected indoor units conforms to the specification 15
- Indoor unit capacity 15
- Model selection 15
- The total capacity of connected indoor units must be within a range of 70 to 130 of the rated capacity of the outdoor unit 15
- Use the above tables to determine the capacities of indoor units to be connected make sure the total capacity of indoor units connected to each outdoor unit is within the specified value btu h 15
- Vrv heat pump series 15
- Part 2 specifications 16
- Specifications 16
- Outdoor units 17
- Specifications 17
- Specifications sius39 601 17
- Sius39 601 specifications 18
- Specifications 7 18
- Specifications 19
- Specifications sius39 601 19
- Sius39 601 specifications 20
- Specifications 9 20
- Specifications 21
- Specifications sius39 601 21
- Ceiling mounted cassette type multi flow 22
- Indoor units 22
- Sius39 601 specifications 22
- Specifications 11 22
- Ceiling mounted cassette type multi flow 23
- Specifications 23
- Specifications sius39 601 23
- Sius39 601 specifications 24
- Slim ceiling mounted duct type 24
- Specifications 13 24
- Slim ceiling mounted duct type 25
- Specifications 25
- Specifications sius39 601 25
- Ceiling mounted built in type 26
- Sius39 601 specifications 26
- Specifications 15 26
- Ceiling mounted built in type 27
- Specifications 27
- Specifications sius39 601 27
- Ceiling mounted duct type 28
- Sius39 601 specifications 28
- Specifications 17 28
- Ceiling suspended type 29
- Specifications 29
- Specifications sius39 601 29
- Sius39 601 specifications 30
- Specifications 19 30
- Wall mounted type 30
- Specifications 31
- Specifications sius39 601 31
- Wall mounted type 31
- Floor standing type 32
- Sius39 601 specifications 32
- Specifications 21 32
- Concealed floor standing type 33
- Specifications 33
- Specifications sius39 601 33
- Functional parts layout 6 34
- Part 3 refrigerant circuit 34
- Refrigerant circuit 4 34
- Refrigerant flow for each operation mode 7 34
- Refrigerant circuit 35
- Refrigerant circuit sius39 601 35
- Rxyq72m 96m 35
- Refrigerant circuit 25 36
- Rxyq72m 96m 36
- Sius39 601 refrigerant circuit 36
- Front view 37
- Functional parts layout 37
- Rxyq72m 96m 37
- Refrigerant circuit 27 38
- Refrigerant flow for each operation mode 38
- Rxyq72m 96m cooling operation 38
- Sius39 601 refrigerant flow for each operation mode 38
- Cooling oil return 39
- Refrigerant circuit 39
- Refrigerant flow for each operation mode sius39 601 39
- Heating oil return defrost 40
- Refrigerant circuit 29 40
- Sius39 601 refrigerant flow for each operation mode 40
- Heating operation 41
- Refrigerant circuit 41
- Refrigerant flow for each operation mode sius39 601 41
- Operation mode 2 2 basic control 3 42
- Other control 4 42
- Outline of control indoor unit 8 42
- Part 4 function 42
- Protection control 9 42
- Special control 0 42
- Function 43
- In the event indoor unit stops or the thermostat turns off while in oil return operation or defrosting operation pump down residual operation is performed on completion of the oil return operation or defrosting operation 43
- Indoor unit stop or thermostat off 43
- Indoor unit thermostat on 43
- Malfunction standby 43
- Operation mode 43
- Operation mode sius39 601 43
- Pump down residual operation 43
- Basic control 44
- F or more 44
- Heating operation is not functional at an outdoor air temperature of 7 44
- Normal operation 44
- Compressor pi control 45
- Compressor pi control carries out the compressor capacity pi control to maintain te at constant during cooling operation and tc at constant during heating operation to ensure stable unit performance 45
- Cooling operation 45
- Heating operation 45
- Compressor operating priority 46
- Compressors are operated in the order of descending priorities compressors may operate in a pattern other than those listed in above tables subject to the operating conditions 46
- Each compressor operates in the following order of priority 46
- Function 35 46
- Inv inverter compressor std1 standard compressor 1 46
- Inv std1 46
- No 1 no 2 46
- Rxyq72m 46
- Rxyq96m 46
- Sius39 601 basic control 46
- Basic control sius39 601 47
- Compressor operating priority 47
- Compressors are operated in the order of descending priorities compressors may operate in a pattern other than those listed in above tables subject to the operating conditions 47
- Each compressor operates in the following order of priority 47
- Function 47
- Inv inverter compressor std1 standard compressor 1 47
- Inv std1 47
- No 1 no 3 47
- No 2 no 4 47
- No 2 no 4 no 1 no 3 47
- Rxyq144m 47
- Rxyq168m 47
- Compressor operating priority 48
- Compressors are operated in the order of descending priorities compressors may operate in a pattern other than those listed in above tables subject to the operating conditions 48
- Each compressor operates in the following order of priority 48
- Function 37 48
- Inv inverter compressor std1 standard compressor 1 48
- Inv std1 48
- No 1 no 3 48
- No 2 no 4 48
- No 2 no 4 no 1 no 3 48
- Rxyq192m 48
- Sius39 601 basic control 48
- Electronic expansion valve pi control 49
- Main motorized valve ev1 control carries out the motorized valve y1e pi control to maintain the evaporator outlet superheated degree sh at constant during heating operation to make maximum use of the outdoor unit heat exchanger evaporator 49
- Subcooling motorized valve ev2 control makes pi control of the motorized valve y2e to keep the superheated degree of the outlet gas pipe on the evaporator side for the full use of the subcooling heat exchanger 49
- The optimum initial value of the evaporator outlet superheated degree is 9 f but varies depending on the discharge pipe superheated degree of inverter compressor 49
- Cooling operation fan control 50
- Fan steps 50
- In cooling operation with low outdoor air temperature this control is used to provide the adequate amount of circulation air with liquid pressure secured by high pressure control using outdoor unit fan 50
- Special control 51
- Startup control 51
- Startup control in cooling operation 51
- Startup control in heating operation 51
- Oil return operation 52
- Oil return operation in cooling operation 52
- Hours however 2 hours after turning power on first time 53
- Oil return operation in heating operation 53
- Defrost operation is started when the outdoor heat exchanger temperature becomes lower than deicer temperature defrost operation is conducted once in max 2 hours 54
- Defrosting operation 54
- Pump down residual operation 55
- Pump down residual operation in cooling operation 55
- Pump down residual operation in heating operation 55
- Restart standby 56
- Stopping operation 57
- When system is in stop mode 57
- In cooling operation the system operates in mode a or mode b listed in the table below 58
- In heating operation the system operates in mode a or mode b listed in the table below 58
- Mode a operating unit collects refrigerant 58
- Mode a or b operation 58
- Mode b stopping unit storage refrigerant 58
- Stopping operation of slave units during master unit is in operation with multi outdoor unit system 58
- The changeover operation for mode a and b is performed for the reason that the required refrigerant amount varies depending on the indoor unit operation capacity 58
- Pressure equalization prior to startup 59
- Function 49 60
- High pressure protection control 60
- In cooling operation 60
- In heating operation 60
- Protection control 60
- Sius39 601 protection control 60
- This high pressure protection control is used to prevent the activation of protection devices due to abnormal increase of high pressure and to protect compressors against the transient increase of high pressure 60
- In cooling operation 61
- In heating operation 61
- Low pressure protection control 61
- This low pressure protection control is used to protect compressors against the transient decrease of low pressure 61
- Discharge pipe protection control 62
- Each compressor performs the discharge pipe temperature protection control individually in the following sequence 62
- Inv compressor 62
- Std compressor 62
- This discharge pipe protection control is used to protect the compressor internal temperature against a malfunction or transient increase of discharge pipe temperature 62
- Fin temp standby 63
- Inv upper limit frequency 1 step 1 min up from current compressor frequency interval 63
- Inverter current 178 f continues for 3 min or more 63
- Inverter current protection control and inverter fin temperature control are performed to prevent tripping due to a malfunction or transient inverter overcurrent and fin temperature increase 63
- Inverter fin temperature control 63
- Inverter overcurrent protection control 63
- Inverter protection control 63
- Not limited 63
- Tfin 178 f inv upper limit frequency 210 hz 63
- Under fin temperature protection control 63
- When occurring 3 times within 60 min the malfunction code l4 is output 63
- Std compressor overload protection 64
- This control is used to prevent abnormal heating due to overcurrent to the compressor resulting from failures of std compressor such as locking 64
- After oil return operation after defrosting operation at the beginning of the starting control 65
- Details of outdoor unit rotation in the case of multi outdoor unit system each outdoor unit is given an operating priority for the control outdoor unit rotation makes it possible to change the operating priority of outdoor units thus the system becomes free of compressors that stop over an extended period of time at the time of partial loading preventing unbalanced oil level 65
- Example the following diagram shows outdoor unit rotation in combination of 3 outdoor units 65
- In the case of multi outdoor unit system this outdoor unit rotation is used to prevent the compressor from burning out due to unbalanced oil level between outdoor units 65
- Master unit and slave unit in this section are the names for installation they are determined in installation work and not changed thereafter these names are different from master unit and slave unit for control the outdoor unit connected the control wires f1 and f2 for the indoor unit should be designated as master unit consequently the led display on the main pcb for master unit slave unit do not change refer to the page 56 65
- Other control 65
- Outdoor unit rotation 65
- Timing of outdoor unit rotation 65
- 777777 66
- 7777777 7777 66
- 777779 66
- 777797 66
- Blink h1 66
- Emergency operation 66
- In the case of 1 outdoor unit system 66
- Led display 66
- Restrictions for emergency operation 66
- 777777 67
- 7777777 7777 67
- 777779 67
- 777797 67
- In the case of multi outdoor unit system rxyq144 168 192mtju 67
- Demand 1 setting 68
- Demand 2 setting 68
- Demand operation 68
- Heating operation is prohibited above 75 f ambient temperature 68
- Heating operation prohibition 68
- In order to save the power consumption the capacity of outdoor unit is saved with control forcibly by using demand 1 setting or demand 2 setting to operate the unit with this mode additional setting of continuous demand setting or external input by external control adapter is required 68
- Other protection control functions have precedence over the above operation 68
- Drain pump control 69
- Outline of control indoor unit 69
- The drain pump is controlled by the on off buttons 4 button 1 4 given in the figure below 69
- The objective of residual operation is to completely drain any moisture adhering to the fin of the indoor unit heat exchanger when the thermostat goes off during cooling operation 69
- When the float switch is tripped while cooling off by thermostat 69
- When the float switch is tripped while the cooling thermostat is on 69
- Thermostat sensor in remote controller 71
- Freeze prevention 73
- Outdoor unit pc board layout 8 3 field setting 9 74
- Part 5 test operation 74
- Test operation 4 74
- Check work prior to turn power supply on 75
- Follow the following procedure to conduct the initial test operation after installation 75
- Procedure and outline 75
- Test operation 75
- Turn power on 75
- 7777777 7777 7 76
- 7777777 9 76
- Check operation 76
- Conduct normal unit operation after the check operation has been completed when outdoor air temperature is 75 f or higher the unit can not be operated with heating mode see the instruction manual attached confirm that the indoor outdoor units can be operated normally when an abnormal noise due to liquid compression by the compressor can be heard stop the unit immediately and turn on the crankcase heater to heat up it sufficiently then start operation again 77
- Confirm that the indoor unit discharges cold air or warm air 77
- Confirmation on normal operation 77
- Malfunction code in case of an alarm code displayed on remote controller 77
- Operate indoor unit one by one to check that the corresponding outdoor unit operates 77
- Operate the air direction control button and flow rate control button to check the function of the devices 77
- Be sure to push and hold the reset button for 5 seconds if not the addition cannot be recognized in this case the unit cannot be run for up to 12 minutes to automatically set the address indoor outdoor address etc status 78
- Operation when power is turned on 78
- Tap the reset button on the outdoor unit pc board operation becomes possible for about 2 minutes if you do not push the reset button the unit cannot be run for up to 10 minutes to automatically set master power status 78
- The unit cannot be run for up to 12 minutes to automatically set the master power and address indoor outdoor address etc status 78
- When an indoor unit or outdoor unit has been added or indoor or outdoor unit pc board has been changed 78
- When turning on power first time 78
- When turning on power the second time and subsequent 78
- 1 microcomputer normal monitor this monitor blinks while in normal operation and turns on or off when a malfunction occurs 79
- 2 set mode display led leds display mode according to the setting 79
- 3 mode setting switch used to change mode 79
- 4 local setting switch used to make local settings 79
- Outdoor unit pc board 79
- Outdoor unit pc board layout 79
- Field setting 80
- Field setting from remote controller 80
- Wireless remote controller indoor unit 81
- Simplified remote controller 82
- Field setting sius39 601 83
- Note 1 settings are made simultaneously for the entire group however if you select the mode no inside parentheses you can also set by each individual unit setting changes however cannot be checked except in the individual mode for those in parentheses 2 the mode numbers inside parentheses cannot be used by wireless remote controllers so they cannot be set individually setting changes also cannot be checked 3 marked are factory set 4 do not make settings other than those described above nothing is displayed for functions the indoor unit is not equipped with 5 88 may be displayed to indicate the remote controller is resetting when returning to the normal mode 6 this setting is only applicable to fxfq and fxhq type 7 if the setting mode to equipped heat reclaim ventilation fan conducts the fan residual operation by linking to indoor unit 83
- Setting contents and code no vrv unit 83
- Test operation 83
- Applicable range of field setting 84
- Contamination light 200 hrs 2 500 hrs 10 000 hrs contamination heavy 100 hrs 1 250 hrs 5 000 hrs 84
- Detailed explanation of setting modes 84
- Filter sign setting 84
- Filter specs setting standard long life ultra long life filter 84
- If switching the filter sign on time set as given in the table below set time 84
- Mode no setting switch no setting position no setting 10 20 1 01 long life filter 02 ultra long life filter 1 03 84
- Setting table 84
- Sius39 601 field setting 84
- Static pressure selection 84
- Test operation 73 84
- Ultra long life filter sign setting when a ultra long life filter is installed the filter sign timer setting must be changed 84
- Auto restart after power failure reset 85
- Caution 1 the air conditioner starts operation suddenly after power failure reset or the main power supply turned on again consequently the user might be surprised with question for the reason why 85
- External on off input this input is used for on off operation and protection device input from the outside the input is performed from the t1 t1 terminal of the operation terminal block x1a in the electric component box 85
- Fan speed changeover when thermostat is off by setting to set fan speed you can switch the fan speed to the set fan speed when the heating thermostat is off 85
- For the above reasons when the unit is set enabling to utilize auto restart function after power failure reset utmost care should be paid for the occurrence of the following situation 85
- For the air conditioners with no setting for the function same as factory setting the units will be left in the stop condition when the power supply is reset automatically after power failure reset or the main power supply is turned on again after once turned off however for the air conditioners with the setting the units may start automatically after power failure reset or the main power supply turned on again return to the same operation condition as that of before power failure 85
- In the service work for example turning off the main power switch during the unit is in operation and turning on the switch again after the work is completed start the unit operation the fan rotates 85
- Setting table 85
- Since there is concern about draft if using fan speed up when thermostat is off you should take the setup location into consideration 85
- Air flow adjustment ceiling height make the following setting according to the ceiling height the setting position no is set to 01 at the factory 86
- Air flow direction setting set the air flow direction of indoor units as given in the table below set when optional air outlet blocking pad has been installed the second code no is factory set to 01 86
- Air flow rate switching at discharge grille for field air flow rate switching when the optional parts high performance filter etc is installed sets to change fan speed for securing air flow rate follow the instruction manual for the optional parts to enter the setting numbers 86
- In the case of fxaq07 24 fxhq12 36 86
- In the case of fxfq12 36 86
- Setting of air flow direction adjustment range make the following air flow direction setting according to the respective purpose 86
- Setting table 86
- Centralized control group no setting 87
- Caution when turning the power supply on the unit may often not accept any operation while 88 is displaying after all indications were displayed once for about 1 minute on the liquid crystal display this is not an operative fault 89
- Field setting sius39 601 89
- Group no setting example 89
- Test operation 89
- Contents of control modes 90
- Setting of operation control mode from remote controller local setting 90
- Do not select timer operation possible by remote controller if not using a remote controller operation by timer is impossible in this case 91
- Factory setting 91
- How to select operation mode whether operation by remote controller will be possible or not for turning on off controlling temperature or setting operation mode is selected and decided by the operation mode given on the right edge of the table below 91
- Caution 92
- Dip switch detail 92
- Dip switch setting after changing the main p c board a1p to spare parts p c b when you change the main p c board a1p to spare parts p c b please carry out the following setting 92
- Field setting from outdoor unit 92
- If the ds1 4 ds2 1 setting refrigerant classification has not been carried out error code ua is displayed and unit can not be operated 92
- Setting by dip switches the following field settings are made by dip switches on pc board 92
- Field setting sius39 601 93
- Mode changing procedure 93
- Monitor mode h1p blinks used to check the program made in setting mode 2 93
- Setting by pushbutton switches the following settings are made by pushbutton switches on pc board 93
- Setting mode 1 h1p off initial status when normal used to select the cool heat setting also indicates during abnormal low noise control and demand control 93
- Setting mode 2 h1p on used to modify the operating status and to set program addresses etc usually used in servicing the system 93
- Test operation 93
- There are the following three setting modes 93
- A setting mode 1 94
- B setting mode 2 95
- C monitor mode 98
- Cool heat mode switching 100
- For the details refer to the installation manual supplied together with the indoor unit 100
- In the case of wired remote controllers 100
- In the case of wireless remote controllers 100
- It does not matter whether or not there is outdoor outdoor unit wiring 100
- Set cool heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by cool heat switching remote controller 100
- Set cool heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by indoor unit remote controller 100
- Set cool heat separately for each outdoor unit system by cool heat selector 100
- Set cool heat separately for each outdoor unit system by indoor unit remote controller 100
- Set cool heat switching to ind individual for setting mode 1 factory set 100
- Set outdoor unit pc board ds1 1 to in factory set 100
- Set the master unit indoor unit having the right to select the cooling heating operation mode 100
- There are the following 4 cool heat switching modes 100
- It does not matter whether or not there is outdoor outdoor unit wiring 101
- Set cool heat separately for each outdoor unit system by cool heat selector 101
- Set cool heat switching to ind individual for setting mode 1 factory set 101
- Set outdoor unit pc board ds1 1 to out factory set 101
- Address setting for 104
- Set lower 5 digits with binary number no to no 1 104
- Supplementation on 104
- When switching cool heat for each adapter pc board with the use of more than one adapter pc board set the address of the adapter pc board ds1 and ds2 so that it matches the unified cool heat address of outdoor unit pc board 104
- Setting of low noise operation and demand operation 105
- Image of operation in the case of a 106
- Image of operation in the case of a and b 106
- Image of operation in the case of b 106
- Image of operation in the case of a 108
- Image of operation in the case of a and b 108
- Image of operation in the case of b 108
- Sius39 601 field setting 108
- Test operation 97 108
- Additional refrigerant charge total flow 111
- Field setting sius39 601 111
- Setting of refrigerant additional charging operation 111
- Test operation 111
- When additional refrigerant is not charged all with outdoor unit in stop mode operate the outdoor unit and charge the liquid refrigerant from the service port of liquid stop value the additional charging operation is activated by pushbutton switch on the outdoor unit pc board 111
- Setting of refrigerant recovery mode 112
- Check operation 113
- Check operation function 113
- In order to perform vacuuming operation at site fully open the expansion valves of indoor and outdoor units and turn on some solenoid valves 113
- Operating procedure 113
- Press mode button bs1 once and reset setting mode 2 113
- Setting of vacuuming mode 113
- To prevent any trouble in the period of installation at site the system is provided with a test operation mode enabling check for incorrect wiring stop valve left in closed coming out or misplacing with suction pipe thermistor of discharge pipe thermistor and judgment of piping length refrigerant overcharging and learning for the minimum opening degree of motorized valve 113
- Use the vacuum pump to perform vacuuming operation 113
- With setting mode 2 while the unit stops set b refrigerant recovery vacuuming mode to on the expansion valves of indoor and outdoor units fully open and some of solenoid valves open h2p blinks to indicate the test operation and the remote controller displays test operation and under centralized control thus prohibiting operation after setting do not cancel setting mode 2 until completion of vacuuming operation 113
- Power transistor check operation 114
- Part 6 troubleshooting 116
- Troubleshooting by indication on the remote controller 20 116
- Troubleshooting by remote controller 08 116
- Troubleshooting op central remote controller 94 117
- Troubleshooting op schedule timer 00 118
- Troubleshooting op unified on off controller 08 118
- Inspection mode 119
- Local setting mode service mode 119
- Normal mode 119
- Test operation mode 119
- The following modes can be selected by using the inspection test operation button on the remote control 119
- The inspection test button 119
- Troubleshooting by remote controller 119
- Self diagnosis by wired remote controller 120
- Self diagnosis by wireless remote controller 121
- The lower digit of the code changes as shown below when the up and down buttons are pressed 122
- Operation of the remote controller s inspection test operation button 123
- Troubleshooting 123
- Troubleshooting by remote controller sius39 601 123
- Remote controller service mode 124
- Remote controller self diagnosis function 126
- The system operates for malfunction codes indicated in black squares however be sure to check and repair 128
- Detail description on next page 129
- Malfunction code indication by outdoor unit pcb 129
- Push the mode button bs1 and returns to setting mode 1 129
- Push the return button bs3 and switches to the initial status of monitor mode 129
- Push the return button bs3 once to display first digit of malfunction code 129
- Push the set button bs2 and set the led display to a setting item 129
- Push the set button bs2 once to display master or slave1 or slave2 and malfunction location 129
- Push the set button bs2 once to display second digit of malfunction code 129
- To enter the monitor mode push the mode button bs1 when in setting mode 1 129
- Troubleshooting 129
- Troubleshooting by remote controller sius39 601 129
- Sius39 601 troubleshooting by remote controller 130
- Troubleshooting 119 130
- A0 indoor unit error of external protection device 131
- Actuation of external protection device 131
- Applicable models all indoor unit models 131
- Defect of indoor unit pc board 131
- Detect open or short circuit between external input terminals in indoor unit 131
- Improper field set 131
- Malfunction decision conditions 131
- Method of malfunction detection 131
- Remote controller display 131
- Supposed causes 131
- Troubleshooting 131
- Troubleshooting by indication on the remote controller 131
- When an open circuit occurs between external input terminals with the remote controller set to external on off terminal 131
- A1 indoor unit pc board defect 132
- A3 indoor unit malfunction of drain level control system s1l 133
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 134
- Sius39 601 troubleshooting by indication on the remote controller 134
- Troubleshooting 134
- Troubleshooting 123 134
- A6 indoor unit fan motor m1f lock overload 135
- Applicable models all indoor unit models 135
- Detection by failure of signal for detecting number of turns to come from the fan motor 135
- Disconnected or faulty wiring between fan motor and pc board 135
- Fan motor lock 135
- Malfunction decision conditions 135
- Method of malfunction detection 135
- Remote controller display 135
- Supposed causes 135
- Troubleshooting 135
- Troubleshooting by indication on the remote controller sius39 601 135
- When number of turns can t be detected even when output voltage to the fan is maximum 135
- A7 indoor unit malfunction of swing flap motor ma 136
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 137
- Troubleshooting 137
- Troubleshooting by indication on the remote controller sius39 601 137
- A9 indoor unit malfunction of moving part of electronic expansion valve 20e 138
- Applicable models all indoor unit models 138
- Defect of connecting cable 138
- Defect of indoor unit pc board 138
- Malfunction decision conditions 138
- Malfunction of moving part of electronic expansion valve 138
- Method of malfunction detection 138
- Remote controller display 138
- Sius39 601 troubleshooting by indication on the remote controller 138
- Supposed causes 138
- Troubleshooting 138
- Troubleshooting 127 138
- Use a microcomputer to check the electronic expansion valve for coil conditions 138
- When the pin input of the electronic expansion valve is not normal while in the initialization of the microcomputer 138
- Coil check method for the moving part of the electronic expansion valve disconnect the electronic expansion valve from the pc board and check the continuity between the connector pins 139
- Continuity approx 15 139
- Continuity approx 30 139
- No continuity 139
- Normal 139
- Af indoor unit drain level above limit 140
- Aj indoor unit malfunction of capacity determination device 141
- C4 indoor unit malfunction of thermistor r2t for heat exchanger 142
- C5 indoor unit malfunction of thermistor r3t for gas pipes 143
- C9 indoor unit malfunction of thermistor r1t for suction air 144
- Cj indoor unit malfunction of thermostat sensor in remote controller 145
- E1 outdoor unit pc board defect 146
- E3 outdoor unit actuation of high pressure switch 147
- Abnormal drop of low pressure lower than 21psi 148
- Abnormality is detected by the pressure value with the low pressure sensor 148
- Applicable models rxyq72m 96m 148
- Defect of low pressure sensor 148
- Defect of outdoor unit pc board 148
- E4 outdoor unit actuation of low pressure sensor 148
- Error is generated when the low pressure is dropped under specific pressure 148
- Malfunction decision conditions 148
- Method of malfunction detection 148
- Remote controller display 148
- Sius39 601 troubleshooting by indication on the remote controller 148
- Stop valve is not opened 148
- Supposed causes 148
- Troubleshooting 148
- Troubleshooting 137 148
- Refer to pressure sensor pressure voltage characteristics table on p241 149
- Voltage measurement point 149
- E5 compressor motor lock 150
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 151
- Troubleshooting 151
- Troubleshooting by indication on the remote controller sius39 601 151
- Applicable models rxyq72m 96m 152
- Closed stop value 152
- Detects the overcurrent with current sensor ct 152
- E6 compressor motor overcurrent lock 152
- Faulty compressor 152
- Faulty current sensor a5p 152
- Faulty magnetic switch 152
- Improper power voltage 152
- Malfunction decision conditions 152
- Malfunction is decided when the detected current value exceeds the below mentioned value for 2 seconds 152
- Method of malfunction detection 152
- Obstacles at the discharge port 152
- Remote controller display 152
- Sius39 601 troubleshooting by indication on the remote controller 152
- Supposed causes 152
- Troubleshooting 152
- Troubleshooting 141 152
- V unit 28 a 152
- Applicable models rxyq72m 96m 153
- Clearing condition operate for 5 minutes normal 153
- E7 malfunction of outdoor unit fan motor 153
- Fan does not run due to foreign matters tangled 153
- Malfunction decision conditions 153
- Malfunction of fan motor 153
- Malfunction of fan motor system is detected according to the fan speed detected by hall ic when the fan motor runs 153
- Method of malfunction detection 153
- Remote controller display 153
- Supposed causes 153
- The harness connector between fan motor and pc board is left in disconnected or faulty connector 153
- Troubleshooting 153
- Troubleshooting by indication on the remote controller sius39 601 153
- When connector detecting fan speed is disconnected 153
- When malfunction is generated 4 times the system shuts down 153
- When the fan runs with speed less than a specified one for 15 seconds or more when the fan motor running conditions are met 153
- Note refer check 8 9 and 12 to p 1 154
- Sius39 601 troubleshooting by indication on the remote controller 154
- Troubleshooting 154
- Troubleshooting 143 154
- Applicable models rxyq72m 96m 155
- Check disconnection of connector check continuity of expansion valve coil 155
- Defect of connecting cable 155
- Defect of moving part of electronic expansion valve 155
- Defect of outdoor unit pc board a1p 155
- E9 outdoor unit malfunction of moving part of electronic expansion valve y1e y2e 155
- Error is generated under no common power supply when the power is on 155
- Malfunction decision conditions 155
- Method of malfunction detection 155
- Remote controller display 155
- Supposed causes 155
- Troubleshooting 155
- Troubleshooting by indication on the remote controller sius39 601 155
- Coil check method for the moving part of the electronic expansion valve disconnect the electronic expansion valve from the pc board and check the continuity between the connector pins 156
- Continuity approx 15 156
- Continuity approx 30 156
- No continuity 156
- Normal 156
- F3 outdoor unit abnormal discharge pipe temperature 157
- F6 refrigerant overcharged 158
- H7 abnormal outdoor fan motor signal 159
- Disconnect connector x2a and measure the following resistance 160
- Sius39 601 troubleshooting by indication on the remote controller 160
- Troubleshooting 149 160
- Applicable models rxyq72m 96m 161
- Defect of outdoor unit pc board a1p 161
- Defect of thermistor r1t for outdoor air 161
- H9 outdoor unit malfunction of thermistor r1t for outdoor air 161
- Malfunction decision conditions 161
- Method of malfunction detection 161
- Refer to thermistor resistance temperature characteristics table on p239 161
- Remote controller display 161
- Supposed causes 161
- The abnormal detection is based on current detected by current sensor 161
- The alarm indicator is displayed when the fan only is being used also 161
- Troubleshooting 161
- When the outside air temperature sensor has short circuit or open circuit 161
- Applicable models rxyq72m 96m 162
- Faulty current sensor 162
- Faulty outdoor unit pc board 162
- J2 current sensor malfunction 162
- Malfunction decision conditions 162
- Malfunction is detected according to the current value detected by current sensor 162
- Method of malfunction detection 162
- Remote controller display 162
- Sius39 601 troubleshooting by indication on the remote controller 162
- Supposed causes 162
- Troubleshooting 162
- Troubleshooting 151 162
- When the current value detected by current sensor becomes 5a or lower or 40a or more during standard compressor operation 162
- Applicable models rxyq72m 96m 163
- Defect of outdoor unit pc board a1p 163
- Defect of thermistor r31t r32t for outdoor unit discharge pipe 163
- J3 outdoor unit malfunction of discharge pipe thermistor r31 33t 163
- Malfunction decision conditions 163
- Malfunction is detected from the temperature detected by discharge pipe temperature thermistor 163
- Method of malfunction detection 163
- Refer to thermistor resistance temperature characteristics table on p240 163
- Remote controller display 163
- Supposed causes 163
- The alarm indicator is displayed when the fan is being used also 163
- Troubleshooting 163
- When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected 163
- J5 outdoor unit malfunction of thermistor r2t for suction pipe 164
- J6 outdoor unit malfunction of thermistor r4t for outdoor unit heat exchanger deicer 165
- Applicable models rxyq72m 96m 166
- Faulty outdoor unit pc board 166
- Faulty receiver outlet liquid pipe thermistor r6t 166
- J7 malfunction of receiver outlet liquid pipe thermistor r6t 166
- Malfunction decision conditions 166
- Malfunction is detected according to the temperature detected by receiver outlet liquid pipe thermistor 166
- Method of malfunction detection 166
- Refer to thermistor resistance temperature characteristics table on p239 166
- Remote controller display 166
- Sius39 601 troubleshooting by indication on the remote controller 166
- Supposed causes 166
- Troubleshooting 166
- Troubleshooting 155 166
- When the receiver outlet liquid pipe thermistor is short circuited or open 166
- Applicable models rxyq72m 96m 167
- Faulty oil equalizing pipe thermistor r7t 167
- Faulty outdoor unit pc board 167
- J8 malfunction of oil equalizing pipe thermistor r7t 167
- Malfunction decision conditions 167
- Malfunction is detected according to the temperature detected by oil equalizing pipe thermistor 167
- Method of malfunction detection 167
- Refer to thermistor resistance temperature characteristics table on p239 167
- Remote controller display 167
- Supposed causes 167
- Troubleshooting 167
- Troubleshooting by indication on the remote controller sius39 601 167
- When the oil equalizing pipe thermistor is short circuited or open 167
- Applicable models rxyq72m 96m 168
- Faulty outdoor unit pc board 168
- Faulty sub cooling gas pipe thermistor r5t 168
- J9 malfunction of sub cooling gas pipe thermistor r5t 168
- Malfunction decision conditions 168
- Malfunction is detected according to the temperature detected by sub cooling gas pipe thermistor 168
- Method of malfunction detection 168
- Refer to thermistor resistance temperature characteristics table on p239 168
- Remote controller display 168
- Supposed causes 168
- Troubleshooting 168
- When the sub cooling gas pipe thermistor is short circuited or open 168
- Applicable models rxyq72m 96m 169
- Connection of low pressure sensor with wrong connection 169
- Defect of high pressure sensor system 169
- Defect of outdoor unit pc board 169
- Ja outdoor unit malfunction of discharge pipe pressure sensor 169
- Malfunction decision conditions 169
- Malfunction is detected from the pressure detected by the high pressure sensor 169
- Method of malfunction detection 169
- Remote controller display 169
- Supposed causes 169
- Troubleshooting 169
- Troubleshooting by indication on the remote controller sius39 601 169
- When the discharge pipe pressure sensor is short circuit or open circuit 169
- Refer to pressure sensor pressure voltage characteristics table on p241 170
- Voltage measurement point 170
- Applicable models rxyq72m 96m 171
- Connection of high pressure sensor with wrong connection 171
- Defect of low pressure sensor system 171
- Defect of outdoor unit pc board 171
- Jc outdoor unit malfunction of suction pipe pressure sensor 171
- Malfunction decision conditions 171
- Malfunction is detected from pressure detected by low pressure sensor 171
- Method of malfunction detection 171
- Refer to pressure sensor pressure voltage characteristics table on p241 171
- Remote controller display 171
- Supposed causes 171
- Troubleshooting 171
- Troubleshooting by indication on the remote controller sius39 601 171
- Voltage measurement point 171
- When the suction pipe pressure sensor is short circuit or open circuit 171
- Actuation of fin thermal actuates above 192 f 172
- Applicable models rxyq72m 96m 172
- Defect of fin thermistor 172
- Defect of inverter pc board 172
- Fin temperature is detected by the thermistor of the radiation fin 172
- L4 outdoor unit malfunction of inverter radiating fin temperature rise 172
- Malfunction decision conditions 172
- Method of malfunction detection 172
- Refer to thermistor resistance temperature characteristics table on p239 172
- Remote controller display 172
- Supposed causes 172
- Troubleshooting 172
- When the temperature of the inverter radiation fin increases above 192 f 172
- Applicable models rxyq72m 96m 173
- Compressor start up malfunction mechanical lock 173
- Defect of compressor coil disconnected defective insulation 173
- Defect of inverter pc board 173
- Higher voltage than actual is displayed when the inverter output voltage is checked by tester 173
- L5 outdoor unit inverter compressor abnormal 173
- Malfunction decision conditions 173
- Malfunction is detected from current flowing in the power transistor 173
- Method of malfunction detection 173
- Remote controller display 173
- Supposed causes 173
- Troubleshooting 173
- Troubleshooting by indication on the remote controller sius39 601 173
- Troubleshooting compressor inspection 173
- When an excessive current flows in the power transistor instantaneous overcurrent also causes activation 173
- L8 outdoor unit inverter current abnormal 174
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 175
- Troubleshooting 175
- Troubleshooting by indication on the remote controller sius39 601 175
- Troubleshooting output current check 175
- Applicable models rxyq72m 96m 176
- Defect of compressor 176
- Defect of inverter pc board 176
- L9 outdoor unit inverter start up error 176
- Malfunction decision conditions 176
- Malfunction is detected from current flowing in the power transistor 176
- Method of malfunction detection 176
- Pressure differential start 176
- Remote controller display 176
- Sius39 601 troubleshooting by indication on the remote controller 176
- Supposed causes 176
- Troubleshooting 176
- Troubleshooting 165 176
- When overload in the compressor is detected during startup 176
- Lc outdoor unit malfunction of transmission between inverter and control pc board 177
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 178
- Sius39 601 troubleshooting by indication on the remote controller 178
- Troubleshooting 178
- Troubleshooting 167 178
- P1 outdoor unit inverter over ripple protection 179
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 180
- Sius39 601 troubleshooting by indication on the remote controller 180
- Troubleshooting 180
- Troubleshooting 169 180
- P4 outdoor unit malfunction of inverter radiating fin temperature rise sensor 181
- Pj outdoor unit faulty field setting after replacing main pc board or faulty combination of pc board 182
- Uo outdoor unit low pressure drop due to refrigerant shortage or electronic expansion valve failure 183
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 184
- Refer to pressure sensor pressure voltage characteristics table on p241 184
- Refer to thermistor resistance temperature characteristics table on p239 184
- Sius39 601 troubleshooting by indication on the remote controller 184
- Troubleshooting 184
- Troubleshooting 173 184
- Applicable models rxyq72m 96m 185
- Defect of outdoor pc board a1p 185
- Detection is based on the voltage in main circuit capacitor for inverter and supply voltage the phase of each phase are detected by reverse phase detection circuit and right phase or reverse phase are judged 185
- Malfunction decision conditions 185
- Method of malfunction detection 185
- Power supply open phase 185
- Power supply reverse phase 185
- Remote controller display 185
- Supposed causes 185
- Troubleshooting 185
- Troubleshooting by indication on the remote controller sius39 601 185
- U1 outdoor unit reverse phase open phase 185
- When a significant phase difference is made between phases 185
- U2 outdoor unit power supply insufficient or instantaneous failure 186
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 187
- Troubleshooting 187
- Troubleshooting by indication on the remote controller sius39 601 187
- U3 outdoor unit check operation not executed 188
- U4 malfunction of transmission between indoor units and outdoor units 189
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 190
- Sius39 601 troubleshooting by indication on the remote controller 190
- Troubleshooting 190
- Troubleshooting 179 190
- Applicable models all models of indoor units 191
- Connection of two main remote controllers when using 2 remote controllers 191
- Defect of indoor unit pc board 191
- Defect of remote controller pc board 191
- In case of controlling with 2 remote controller check the system using microcomputer is signal transmission between indoor unit and remote controller main and sub is normal 191
- Malfunction decision conditions 191
- Malfunction of indoor unit remote controller transmission 191
- Malfunction of transmission caused by noise 191
- Method of malfunction detection 191
- Normal transmission does not continue for specified period 191
- Remote controller display 191
- Supposed causes 191
- Troubleshooting 191
- Troubleshooting by indication on the remote controller sius39 601 191
- U5 indoor unit malfunction of transmission between remote controller and indoor unit 191
- U7 indoor unit malfunction of transmission between outdoor units 192
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 193
- Troubleshooting 193
- Troubleshooting by indication on the remote controller sius39 601 193
- Applicable models all models of indoor units 194
- Connection between sub remote controllers 194
- Defect of remote controller pc board 194
- In case of controlling with 2 remote controller check the system using microcomputer if signal transmission between indoor unit and remote controller main and sub is normal 194
- Malfunction decision conditions 194
- Malfunction of transmission between main and sub remote controller 194
- Method of malfunction detection 194
- Normal transmission does not continue for specified period 194
- Remote controller display 194
- Sius39 601 troubleshooting by indication on the remote controller 194
- Supposed causes 194
- Troubleshooting 194
- Troubleshooting 183 194
- U8 indoor unit malfunction of transmission between main and sub remote controllers 194
- U9 indoor unit malfunction of transmission between indoor units and outdoor units in the same system 195
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 196
- Sius39 601 troubleshooting by indication on the remote controller 196
- Troubleshooting 196
- Troubleshooting 185 196
- Ua improper combination of indoor units and outdoor units indoor units and remote controller 197
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 198
- Sius39 601 troubleshooting by indication on the remote controller 198
- The number of indoor units that can be connected to a single outdoor unit system depends on the type of outdoor unit 198
- Troubleshooting 198
- Troubleshooting 187 198
- Uc address duplication of central remote controller 199
- Ue malfunction of transmission between centralized controller and indoor unit 200
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 201
- Troubleshooting 201
- Troubleshooting by indication on the remote controller sius39 601 201
- Applicable models all indoor units models rxyq72m 96m 202
- Defect of indoor unit pc board 202
- Failure to execute check operation 202
- Improper connection of transmission wiring between indoor outdoor unit and outdoor unit external control adaptor for outdoor unit 202
- Malfunction decision conditions 202
- Method of malfunction detection 202
- Note wiring check operation may not be successful if carried out after the outdoor unit has been off for more than 12 hours or if it is not carried out after running all connected indoor units in the fan mode for at least an hour 202
- Remote controller display 202
- Sius39 601 troubleshooting by indication on the remote controller 202
- Stop valve is left in closed 202
- Supposed causes 202
- The malfunction is determined as soon as the abnormality aforementioned is detected through checking the system for any erroneous connection of units on the check operation 202
- The number of indoor units in terms of data transmission becomes mismatched to that of indoor units with changes in temperature on operation for checks 202
- Troubleshooting 202
- Troubleshooting 191 202
- Uf system is not set yet 202
- Uh malfunction of system refrigerant system address undefined 203
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 204
- Sius39 601 troubleshooting by indication on the remote controller 204
- Troubleshooting 204
- Troubleshooting 193 204
- M1 pc board defect 205
- Troubleshooting op central remote controller 205
- M8 malfunction of transmission between optional controllers for centralized control 206
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 207
- Troubleshooting 207
- Troubleshooting op central remote controller sius39 601 207
- Ma improper combination of optional controllers for centralized control 208
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 209
- Troubleshooting 209
- Troubleshooting op central remote controller sius39 601 209
- Mc address duplication improper setting 210
- Troubleshooting op schedule timer 211
- Ue malfunction of transmission between central remote controller and indoor unit 211
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 212
- Sius39 601 troubleshooting op schedule timer 212
- Troubleshooting 212
- Troubleshooting 201 212
- M1 pc board defect 213
- M8 malfunction of transmission between optional controllers for centralized control 214
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 215
- Troubleshooting 215
- Troubleshooting op schedule timer sius39 601 215
- Ma improper combination of optional controllers for centralized control 216
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 217
- Troubleshooting 217
- Troubleshooting op schedule timer sius39 601 217
- Mc address duplication improper setting 218
- Operation lamp blinks 219
- Troubleshooting op unified on off controller 219
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 220
- Sius39 601 troubleshooting op unified on off controller 220
- Troubleshooting 220
- Troubleshooting 209 220
- Display under centralized control blinks repeats single blink 221
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred 222
- Sius39 601 troubleshooting op unified on off controller 222
- Troubleshooting 222
- Troubleshooting 211 222
- Troubleshooting 223
- Troubleshooting op unified on off controller sius39 601 223
- Applicable models unified on off controller 224
- Central control address group no is not set for indoor unit 224
- Detect the malfunction according to diii net transmission data 224
- Display under centralized control blinks repeats double blink 224
- Improper control range setting switch 224
- Improper wiring of transmission wiring 224
- Malfunction decision conditions 224
- Method of malfunction detection 224
- Remote controller display 224
- Sius39 601 troubleshooting op unified on off controller 224
- Supposed causes 224
- Troubleshooting 224
- Troubleshooting 213 224
- Under centralized control repeats double blink 224
- When no central control addresses are set to indoor units when no indoor units are connected within the control range 224
- Check no 8 check on connector of fan motor power supply cable 1 turn off the power supply measure the resistance between phases of u v w at the motor side connectors three core wire to check that the values are balanced and there is no short circuiting while connector or relay connector is disconnected 225
- Check no 9 check on connector of fan motor signal wire 1 turn off the power supply 2 measure the resistance between vcc and each phase of u v w and gnd and each phase at the motor side connectors five core wire to check that the values are balanced within the range of 20 while connector or relay connector is disconnected 225
- Troubleshooting 225
- Troubleshooting op unified on off controller sius39 601 225
- Check no 12 check on pulse input of position signal of fan inverter pcb 1 disconnect the connector x2a while power supply off and operation off 2 is the voltage between pins no 4 and 5 on x2a approx 15 v after power supply is turned on 3 connect the connector x2a while power supply off and operation off 4 check below conditions when the fan motor is rotated one turn manually under the condition of operation off after power supply is turned on are the pulse approx 0 v and 5 v generated 4 times between no 1 and 5 on x2a are the pulse approx 0 v and 5 v generated 4 times between no 2 and 5 on x2a are the pulse approx 0 v and 5 v generated 4 times between no 3 and 5 on x2a 226
- Check no 13 power transistor check mode when the inverter system malfunctions malfunction of inverter inv compressor to locate where the malfunction occurs switching to the power transistor check mode of inverter in the service mode setting enables not to judge the position detection signal malfunction but to output waveform only during inverter operation the waveform can be checked by disconnecting the wiring of compressor after the completion of checks return the system to the previous mode and wait for 30 seconds or more until the discharge of capacitor is completed then conduct a subsequent work 226
- Notes be sure to disconnect the compressor wiring when conducting the check operation mentioned above when the output voltage is approx 100 200 v 10 hz and the voltage balance between phases u v v w w u is within 5 the inverter pcb is normal 226
- Sius39 601 troubleshooting op unified on off controller 226
- The condition 2 dose not appear faulty pcb replacing the pcb the conditions 4 do not appear faulty hall ic replacing fan motor of outdoor unit 226
- Troubleshooting 215 226
- Voltage output will be different depend on measuring device 226
- Part 7 replacement procedure for inv compressor vrv ii 228
- Replacement procedure 229
- Replacement procedure for inv compressor vrv ii rxyq72m 96m 229
- Replacement procedure for inv compressor vrv rxyq72m 96m 229
- Example of connection 37 6 thermistor resistance temperature characteristics 39 7 pressure sensor 41 8 method of replacing the inverter s power transistors and diode modules 42 230
- List of electrical and functional parts 30 230
- Option list 35 230
- Part 8 appendix 230
- Piping diagrams 20 230
- Wiring diagrams for reference 23 230
- Outdoor unit 231
- Piping diagrams 231
- Rxyq72m 96m 231
- Electronic expansion valve filter filter 232
- Fxfq 12m 18m 24m 30m 36mvju fxsq 12m 18m 24m 30m 36m 48mvju fxmq 30m 36m 48mvju fxhq 12m 24m 36mvju fxaq 07m 09m 12m 18m 24mvju fxlq 12m 18m 24mvju fxnq 12m 18m 24mvju 232
- Heat exchanger gas piping connection port 232
- Indoor unit 232
- Liquid piping connection port 232
- R1t thermistor for suction air temperature r2t thermistor for liquid line temperature r3t thermistor for gas line temperature 232
- Refrigerant pipe connection port diameters 233
- Outdoor unit 234
- Rxyq72 96mtju 234
- Wiring diagrams for reference 234
- Field wiring 235
- Rxyq72 96mtju 235
- Rxyq144 168 192mtju 236
- Fxdq07m 09m 12m 18m 24mvju 237
- Fxfq12m 18m 24m 30m 36mvju 237
- Indoor unit 237
- Fxmq30m 36m 48mvju 238
- Fxsq12m 18m 24m 30m 36m 48mvju 238
- Fxaq07m 09m 12m 18m 24mvju 239
- Fxhq12m 24m 36m 239
- Fxlq12m 18m 24mvju fxnq12m 18m 24mvju 240
- List of electrical and functional parts 241
- Outdoor unit 241
- Rxyq72m 96mtju 241
- Appendix 231 242
- Indoor side 242
- Indoor units 242
- Sius39 601 list of electrical and functional parts 242
- Appendix 243
- List of electrical and functional parts sius39 601 243
- Appendix 233 244
- Sius39 601 list of electrical and functional parts 244
- Appendix 245
- List of electrical and functional parts sius39 601 245
- 2 electrical box 5 1 6 1 is required for controller no 5 6 246
- Building management system 246
- Is a registered trade mark of echelon corporation 246
- Is a registered trademark of american society of heating refrigerating and air conditioning engineers ashrae 246
- Lonwork 246
- Notes 1 installation box no is necessary for each adaptor marked 246
- Option list 246
- Option list of controllers 246
- Optional accessories of operation control system 246
- Appendix 247
- Option list sius39 601 247
- Option lists outdoor unit 247
- Rxyq72 96 144 168 192mtju 247
- Appendix 237 248
- Branch with refnet joint branch with refnet joint and refnet header branch with refnet header 248
- Example of connection 248
- How to calculate the additional refrigerant to be charged 248
- Pipe size selection 248
- Refrigerant branch kit selection 248
- Sius39 601 example of connection 248
- Appendix 239 250
- Indoor unit for air suction r1t for liquid pipe r2t for gas pipe r3t 250
- Outdoor unit fin thermistor r1t 250
- Outdoor unit for outdoor air r1t for suction pipe r2t for heat exchanger deicer r4t for sub cooling heat exchanger r5t for receiver outlet liquid pipe r6t for oil equalizing piping r7t 250
- Sius39 601 thermistor resistance temperature characteristics 250
- Thermistor resistance temperature characteristics 250
- Appendix 251
- Outdoor unit thermistors for discharge pipe r3t r31t r32t 251
- Thermistor resistance temperature characteristics sius39 601 251
- Appendix 241 252
- Pressure sensor 252
- Sius39 601 pressure sensor 252
- Before checking disconnect the electric wiring connected to the power transistor and diode module 253
- Decision according to continuity check by analog tester 253
- Electronic circuit 253
- Inverter p c board 253
- Inverter pc board a1p 253
- Method of replacing the inverter s power transistors and diode modules 253
- Part 9 precautions for new refrigerant r 410a 256
- Precautions for new refrigerant r 410a 46 256
- About refrigerant r 410a 257
- Characteristics of new refrigerant r 410a 1 performance almost the same performance as r 22 and r 407c 2 pressure working pressure is approx 1 times more than r 22 and r 407c 3 refrigerant composition few problems in composition control since it is a quasi azeotropic mixture refrigerant 257
- Mpa 145 psi 257
- Non azeotropic mixture refrigerant mixture of two or more refrigerants having different boiling points 257
- Outline 257
- Precautions for new refrigerant r 410a 257
- Quasi azeotropic mixture refrigerant mixture of two or more refrigerants having similar boiling points 257
- The design pressure is different at each product please refer to the installation manual for each product reference 1 mpa 10 9716 kgf c 257
- Precautions for new refrigerant r 410a 247 258
- Sius39 601 precautions for new refrigerant r 410a 258
- Thermodynamic characteristic of r 410a 258
- As for the charge mouthpiece and packing 1 2unf20 is necessary for mouthpiece size of charge hose 259
- Copper tube material and thickness 259
- O soft annealed h hard drawn 259
- R 410a is used under higher working pressure compared to previous refrigerants r 22 r 407c furthermore the refrigerating machine oil has been changed from suniso oil to ether oil and if oil mixing is occurred sludge results in the refrigerants and causes other problems therefore gauge manifolds and charge hoses that are used with a previous refrigerant r 22 r 407c can not be used for products that use new refrigerants be sure to use dedicated tools and devices 259
- Service tools 259
- Tool compatibility 259
- Conventional flaring tools can be used when the work process is changed change of work process previously a pipe extension margin of 0 to 0 mm was provided for flaring for r 410a air conditioners perform pipe flaring with a pipe extension margin of 1 to 1 mm for clutch type only conventional tool with pipe extension margin adjustment can be used 260
- Differences 2 change of dimension a 260
- Flaring tool 260
- Specifications 2 dimension a 260
- Unit mm 260
- Regarding purchasing of service tools please contact following address daikin u s corporation dallas office 1645 wallace dr ste 110 carrollton tx 75006 tel 1 972 245 1510 fax 1 972 245 1038 264
- Symbols 266
- Drawings flow charts 270
- This book is made of recycled paper 273
Похожие устройства
- Xilence XN044 Техническая спецификация
- Daikin RXYQ144MTJU Сервис мануал
- Daikin RXYQ168MTJU Сервис мануал
- Daikin RXYQ192MTJU Сервис мануал
- Daikin RXYQ72MTJU Технические данные
- Daikin RXYQ144MTJU Технические данные
- Daikin RXYQ168MTJU Технические данные
- Daikin RXYQ192MTJU Технические данные
- Xilence XN042 Техническая спецификация
- Daikin RXYQ72MTJU Руководство по вводу в эксплуатацию
- Daikin RXYQ144MTJU Руководство по вводу в эксплуатацию
- Daikin RXYQ168MTJU Руководство по вводу в эксплуатацию
- Daikin RXYQ192MTJU Руководство по вводу в эксплуатацию
- Xilence XN041 Техническая спецификация
- Xilence XN054 Техническая спецификация
- Xilence XN053 Техническая спецификация
- Xilence XN052 Техническая спецификация
- Xilence XN051 Техническая спецификация
- Xilence XN050 Техническая спецификация
- Xilence XN240 Техническая спецификация