Daikin RXQ44PY1 [155/355] The work after the kit is connected
Превью страниц
Страница 155 /
355
![Daikin RXQ44PY1 [155/355] The work after the kit is connected](/views2/1715571/page155/bg9b.png)
SiEN34-705 Appendix
General Information 149
The work after the kit is connected
Connection of piping between the outdoor unit and the indoor unit
Air tight test
Insulation of joints
Follow the instructions in the installation manual included
with the outdoor unit, when performing installation work.
(1) Fit the insulation to the reducer and temporarily keep it in place with tape.
(2) Fit the insulation to the joint and temporarily keep it in place with tape without leaving a gap between the
insulation mating faces. (See the figure at the right.)
(3) Seal the seam between the insulation and the field supply piping insulation with the field supply tape.
(4) Wrap the tape arround the insulation attached to the joint without leaving a gap.
( section shown in the figure at the right)
Insulating tube
Tape (field supply)
Tape (field supply)
Tape (field supply)
Tape (field supply)
Insulating tube
Reducer
Joint
Local pipes insulating material
Содержание
1648- Service
- R 410a heat pump 50hz 60hz cooling only 50hz
- Manual
- Design installation testing instruction
- Sien34 705
- Test operation 2
- R 410a series
- Product outline
- Points to bear in mind at the system design 2
- Part 1 general information
- Installation 9
- Hand over to customer 27
- Caution for refrigerant leaks 24
- Appendix 28
- Part 3 operation manual 09
- Part 2 installation manual 13
- Heat pump cooling only 50hz rx y q5 54p 310 1 safety cautions 311 1 specifications 312 1 what to do before operation 312 1 remote control and cool heat selector name and function of each switch and display refer to figure 2 and 3 313 1 operation range 313 1 operation procedure 313 1 optimum operation 317 1 seasonal maintenance 317 1 following symptoms are not air conditioner troubles 317 1 0 trouble shooting 319 2 heat pump 60hz rxyq5 54p 321 2 safety cautions 322 2 specifications 323 2 what to do before operation 323 2 remote control and cool heat selector name and function of
- Heat pump cooling only 50hz rx y q5 54p 14
- Heat pump 60hz rxyq5 54p 61
- Drawings flow charts iii
- Part 4 precautions for new refrigerant r 410a 33
- Index i
- Preface
- Test operation 2
- Product outline
- Points to bear in mind at the system design 2
- Part 1 general information
- Installation 9
- Hand over to customer 27
- Caution for refrigerant leaks 24
- Appendix 28
- Indoor units
- High cop series energy saving series
- Heat pump rx y q 5p 8p 10p 12p 14p 16p 18p 20p 22p y1 e yl e 24p 26p 28p 30p 32p 34p 36p 38p 40p 42p 44p 46p 48p 50p 52p 54p
- Heat pump rx y q 16ph 18ph 24ph 26ph 28ph 30ph 32ph 34ph 36ph y1 e yl e 38ph 40ph 42ph 44ph 46ph 48ph 50ph
- General information
- Series model name power supply
- Product outline sien34 705
- Product outline
- Outdoor units normal series
- Model names of indoor outdoor units
- Floor standing type
- External appearance
- Concealed floor standing type
- Ceiling suspended type
- Ceiling suspended cassette type connection unit series
- Ceiling mounted duct type
- Ceiling mounted cassette type multi flow
- Ceiling mounted cassette type double flow
- Ceiling mounted cassette corner type
- Ceiling mounted built in type
- Wall mounted type
- 600 ceiling mounted cassette type multi flow
- Slim ceiling mounted duct type
- Sien34 705 product outline
- Outdoor air processing unit
- Indoor units heat pump 50hz 60hz cooling only 50hz
- General information 3
- Outdoor units heat pump 50hz 60hz cooling only 50hz
- Combination of outdoor units
- Product outline sien34 705
- Note fxdq has following 2 series as shown below fxdq p n a vet without drain pump
- New refrigerant model code p20 type p25 type p32 type p40 type p50 type p63 type p80 type p100 type p125 type p200 type p250 type selecting model capacity 2 kw 2 kw 3 kw 4 kw 5 kw 7 kw 9 kw 11 kw 14 kw 22 kw 28 kw equivalent output 0 hp 1hp
- Indoor unit capacity
- Hp 2 hp 2 hp 3 hp 4hp 5hp 8hp 10hp
- General information
- Fxdq p n a ve with drain pump fxzq only for eu australia
- Connectable indoor unit
- Use the above tables to determine the capacities of indoor units to be connected make sure the total capacity of indoor units connected to each outdoor unit is within the specified value kw the total capacity of connected indoor units must be within a range of 50 to 130 of the rated capacity of the outdoor unit in some models it is not possible to connect the maximum number of connectable indoor units select models so the total capacity of connected indoor units conforms to the specification
- Differences from conventional models
- Vrv iii heat pump 50hz 60hz cooling only 50hz
- Product outline sien34 705
- Model selection
- General information
- Connectable indoor units number and capacity normal series
- Sien34 705 product outline
- High cop series energy saving series
- General information 11
- Points to bear in mind at the system design
- Points relating to the performance of the air conditioning units
- The analysis of major installation problems experienced is shown below
- Points to bear in mind at the system design sien34 705
- How these installation problems affect an equipment are shown below
- General information
- The installation is of vital importance
- Striking a balance between system installation and general construction work comprehensive flow chart
- Note 1 the division of the work should be thoroughly clarified this applies particularly to work relating to the connection of control wiring fitting of remote control and central control panel boundary work on areas such as connection of drain piping and humidification supply piping inspection and foundation 2 keep a constant check on the progress of the construction work to avoid deviations from the air conditioning work schedule 3 for sleeve and insert work the positions of ceiling girders should be confirmed and sleeve and insert requirement hole diameters positioning and numbers decided this is particularly important in the case of sleeves for drain piping
- The following points should be borne in mind when preparing the contract drawings from the original drawings and the execution drawings the contract drawings for the air conditioning system are blueprints for the performance of the necessary work which are drawn up on the basis of the original drawings in such a way that a working balance is achieved between the specific requirements of each individual aspect of the work
- The following is a list of the main points to be considered when preparing contract drawings for the iii system and should be used as a reference during this stage of the work
- Points to bear in mind when preparing the contract drawings
- Objectives include the drawings should be easily comprehensible to those carrying out the work the contents of the drawings should not be subject to subsequent alteration
- Contract drawing
- At the contract drawing stage the following points are critical
- Sien34 705 points to bear in mind at the system design
- Note with the vrv iii r 410a heat pump cooling only series unit no is determined through automatic addressing therefore readout unit nos after activating the power
- Mark each outdoor unit with a code 2 add field settings and data for outdoor units and outdoor unit no if using sequential start 3 add the model number of each indoor unit connected to each refrigerant circuit 4 assign each indoor unit a code 5 fill in the location of each indoor unit 6 group indoor units controlled by one or two remote controls group or individual control 7 assign central group nos if using centralized control 8 add field settings and optional equipment for indoor units 9 add unit no if making separate field settings for each indoor unit under group control
- Main considerations in preparation of control circuit diagrams
- In addition to the design of the appropriate this system configuration it is also essential that the control system be made amply clear if the system is designed and installed without a clear comprehensive plan then problems are inevitably going to occur during the test run servicing too will become much more time consuming than necessary however if control circuit diagrams are prepared along with the contract drawings in order to make the total system clearly visible then the essential points relating to the electrical connections will be easily understood the test run will go off without a hitch and the whole system will be rendered fully effective
- General information 17
- For details on field settings and centralized control group no refer to the installation manual and system reference materials
- Step 1 compiling a system list
- Step 2 preparation of the control circuit diagrams
- Example control circuit diagram
- The above list indicates the order in which the individual work operations are normally carried out but this order may be varied where local conditions warrant such a change
- Step by step installation procedure
- Sien34 705 installation
- Installation
- General information 19
- Work involved in individual operations and points to be borne in mind
- Sleeve and insert work
- Positioning the insert
- Positioning of the pipe holes
- Height take care to account for final ceiling facing surface level 2 level level fitting is essential within 1 degree of horizontal 3 direction the unit must be fitted in line with the ultimately visible ceiling joints
- General information 21
- Example ceiling mounted cassette type fxcq63m
- Essential points when installing an indoor unit
- Sien34 705 installation
- Positioning
- Operational steps
- Installation of indoor unit
- Important points 1 the suspension bolts must be strong enough to support the weight of the indoor unit 2 optional features must be added to the indoor unit prior to installation 3 the model name should be checked prior to installation 4 take care to align the main unit correctly bearing in mind piping layout and direction of blow out 5 leave sufficient space for servicing to be carried out 6 make inspection holes for model which need them 7 fit the unit to ensure proper drainage
- The 3 principles of refrigerant piping must be strictly observed
- The 3 principles of refrigerant piping
- Refrigerant pipe work
- Operational steps
- Installation sien34 705
- General information
- Method for replacing nitrogen brazing
- Covering of refrigerant pipes
- Refrigerant pipe flushing
- 3 make sure to use the particular branches of piping that have been selected referring to chapter example of connection 4 the piping minimum thickness and material the min thickness of the pipes shows the requirements of japanese high pressure gas control low as of jan 2003 and the temper grade
- 1 2h shows the material type of jis h 3300 the thickness and material should comply with relevant local and national regulations for the design pressure 4 mpa 40bar select the wall thickness in accordance with relevant local and national regulations
- The nature and amount of the extraneous material inside the pipe can be checked during flushing by placing a rag lightly over the end of the pipe in the unlikely case that even a small quantity of moisture is found then the inside of the pipe should be dried out thoroughly action 1 flush the inside of the pipe with nitrogen gas until such time as the moisture disappears 2 carry out a thorough vacuum drying operation see page 39 1 close the main valve on the nitrogen cylinder 2 repeat the above operation for unit b 3 when the liquid pipe operations have been completed then do the same with the gas pipes
- Installation sien34 705
- General information
- Choice of materials for refrigerant piping
- A refrigerant piping selection of piping material 1 foreign materials inside pipes including oils for fabrication must be 30mg 10m or less 2 use the following material specification for refrigerant pipping construction material phosphoric acid deoxidized seamless copper for refrigerant size determine the proper size referring to chapter example of connection the wall thickness of the refrigerant piping should comply with relevant local and national regulations for r 410a the design pressure is 4 mpa 40 kgf c
- Sien34 705 installation
- Refnet joint
- Refnet header
- Refer detail of daikin refnet joint and refnet header on page 161
- General information 27
- Example r 410a rxyq p series
- Equivalent piping length of joints and header reference
- Branches
- B brazed joints and special branches 1 general use l bend joint socket joint t joint etc joints must meet the requirements of the relevant jis standard size materials thickness etc 2 special branches the daikin outdoor unit multi connection kit refnet joint refnet header or reducing socket should be used
- Brazing rod diameter φ
- 200 225 250 315 400 450 500
- The r 410a heat pump cooling only rx y q p series uses a wide range of piping sizes you should therefore be careful when selecting the nozzle tip if a small nozzle tip is used for brazing piping of large diameters such as φ 38 and φ 44 brazing flow becomes poor
- Table 1 correlation of nozzle tip and size of refrigeration piping
- Piping size
- Nozzle tip no
- Note the values in the table above are for type b torch french
- Installation sien34 705
- Hard solder
- General information
- C brazing the multi system requires only copper copper jointing and the jointing method is explained below the use of hard solder is essential
- Brazing
- Installation sien34 705
- General information
- Flare gauge adapter corresponding to the new rank when using the later use a flare gauge to take out the pipe from the gauge bar adjust it and then carry out the flare processing
- Flare connection
- D coat the inner and outer surface of the flare with refrigerator oil ester or ether oil this ensures that the flare nut passes smoothly preventing the pipe from twisting do not use suniso 4gs oil
- A stiffened pipe must always be annealed at least once prior to the flaring work b a pipe cutter must be used to cut the pipe a large pipe cutter must be used where the pipe has a large diameter when cutting a pipe which is too big for the pipe cutter a metal saw may be used but care must be taken to ensure that the debris from sawing does not get into the pipe c set the flaring tool to make sure the flare size remains within the prescribed limits
- Size from the dice surface to the copper tip in mm
- New rank compatible flare tool compared to previous refrigerants the components of a hfc refrigerant is small r 410a also has a higher pressure than other refrigerants therefore in order to strengthen the intensity of the form and size of the flare section used for r 410a class 2 apparatus unlike the specification of the conventional refrigerants it was set up with different standards when carrying out flare processing use a new rank compatible flare tool or a conventional flare tool
- Mm 72mm 1 0 mm each
- Standard torques for tightening flare nut
- Sien34 705 installation
- Important points 1 burrs should be carefully removed 2 2 spanners should be used to grip the flare nuts 3 the flare nut must be inserted before starting the flaring operation 4 the appropriate amount of torque should be used to tighten the flare nut
- General information 31
- Check that there is no superficial damage to the surface of the flare
- Flaring procedure
- Tighten the flare but with proper torque
- Not recommendable but in case of emergency
- Important points 1 only clean refrigeration oil should be used to coat the flange i e free from dirt or water 2 the correct amount of torque should be applied when tightening the flange bolts
- General information
- Flange connection
- C tighten the bolts in opposite corners first to ensure that the connection is true
- A the flange sheet surface should be clean and undamaged clean any dirt away with a cloth and check that there has been no damage b coat the flange sheet surface with refrigeration oil ester or ether oil and then insert the packing do not use suniso oil
- Standard torques for tightening screws and bolts
- Iso hexagonal bolt
- Installation sien34 705
- Thermal insulation work refrigerant piping
- Materials
- Essential points of thermal insulation
- Essential points of testing maintaining pressure over a period
- Air tight test
- Setup of air tight test referring to following figure connect an nitrogen tank refrigerant tank and a vacuum pump to the outdoor unit the shutoff valve and valve a c in following figure should be open or closed as shown in the table below
- Installation sien34 705
- Important points 1 where the lengths of piping involved are particularly long then the air tight test should be carried out block by block example 1 indoor side 2 indoor side vertical pipes 3 indoor side vertical pipes outdoor side
- General information
- Checking for leaks
- Check 2 when searching for a minor leak or when there has been a fall in pressure while the system has been fully pressurized but the source of the leak cannot be traced 1 release the nitrogen until the pressure reaches 0 mpa 2 increase pressure to 1 mpa using gaseous flon gas r 410a nitrogen and flon gas mixed 3 search for the source of the leak using a leak detector 4 if the source of the leak still cannot be traced then repressurize with nitrogen up to 4 0mpa and check again the pressure must not be increased to more than 4 0mpa
- Check 1 where pressure falls while carrying out steps 1 to 3 described on previous page check by ear listen for the sound of a major leak check by hand check for leak by feeling around jointed sections with hand soap and water check snoop bubbles will reveal the presence of a leak
- Key points lower the degree of vacuum to below 755mmhg
- What is vacuum drying
- Vacuum drying is the use of a vacuum pump to vaporize gasify the moisture liquid inside the pipes and expel it leaving the pipes completely dry inside at 1 atm 760 mmhg the boiling point evaporating temperature of water is 100 c but if a vacuum is created inside the pipes using a vacuum pump then the boiling point is rapidly reduced as the degree of the vacuum is increased if the boiling point is reduced to a level below that of the ambient temperature then the moisture in the pipes will evaporate
- Vacuum drying
- The evacuation of air conditioner piping provides the following effects 1 vacuum drying 2 removes air and nitrogen used in air tightness test from the inside of pipes therefore it is necessary to ensure that the both purposes have been achieved in the vacuum drying operation
- Choosing a vacuum pump
- When selecting a vacuum you should select one which is capable of achieving 0 torr of ultimate vacuum
- Vacuum pump maintenance because of their nature most vacuum pumps contain large amounts of oil which lubricates bearings etc and functions to enhance airtightness of pistons when using a vacuum pump to discharge air from refrigerant piping moisture in the air tends to get mixed in with the oil you must therefore change oil periodically and make sure the proper oil level is maintained perform periodic inspections in accordance with the operating instructions
- Sien34 705 installation
- General information 41
- Degree of vacuum measurement an extremely accurate vacuum gauge is required to test degree of vacuum you cannot accurately measure degree of vacuum with the compound gauge on the gauge manifold a pirani vacuum gauge is required to measure degree of vacuum accurately because pirani gauges are very sensitive and require extreme care when using they are not very suitable for use in the field you should therefore use the pirani gauge to calibrate the attached vacuum gauge on the gauge manifold and the degree of vacuum of the vacuum pump
- Degree of vacuum is expressed in torr micron mmhg and pascal pa the units correlate as follows
- 2 degree of vacuum ultimate vacuum varies largely according to use of the vacuum pump vacuum pumps used for vacuum forming cannot be used for vacuum drying a vacuum pump with a high degree of vacuum is required
- Many handy pumps fall into this category
- Installation sien34 705
- General information
- Calibration method 1 connect a pirani vacuum gauge and the gauge manifold vacuum gauge 0 760 mmhg to the vacuum pump at the same time and run the pump for about 3 minutes 2 make sure the reading of the pirani vacuum gauge is 5 torr 667 pa or less the reading of conventional vacuum pumps lowers to about 0 torr if the reading is not 5 torr or less check the vacuum pump oil oil is low in many cases 3 check the attached gauge on the gauge manifold adjust the gauge if the reading is not exactly correct 4 adjust the gauge manifold valve so that the pirani vacuum gauge reads 5 torr 5 mark the position indicated by the gauge manifold gauge with an oil based ink pen 6 use the mark of the gauge manifold as a target when vacuuming in the field
- Reference types of vacuum pump with respective maximum degree of vacuum
- Vacuum drying procedure
- Refrigerant charging instructions
- Additional charge of refrigerant at installation time
- Drain trap
- Drain pipe work indoor
- Drain pipe gradient and support
- Use of an auxiliary drain hose flexible
- The pipework should be kept as short as possible and the number of indoor units per group kept to a minimum
- It is standard work practice to make connections to the main pipe from above the pipe down from the combination should be as large as possible
- Installation sien34 705
- Important points 1 the drain pipe should be at least equal in size to that of the indoor unit 2 the drain pipe is thermally insulated to prevent the formation of condensation inside the pipe 3 the drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected some water should be added to the drain pan and the drain pump checked to see that it is functioning correctly 4 all connections should be secure special care is needed with pvc pipe the use of a colored adhesive with pvc pipes will help you to remember to connect them up
- If a drain pan made of polystyrene foam is used then an auxiliary drain hose flexible is also essential a flexible drain hose permits the drain socket and drain pipe to be connected without difficulty and prevents any undue strain being placed on the drain pan
- Grouped drain piping
- General information
- Ceiling mounted cassette type fxcq m double flow
- Sien34 705 installation
- Select piping diameter from the below table in accordance with the amount of condensation drained by all units with a common drain pipe consider 2 l hr of drainage for every 1 hp for example drainage from 3 units running at 2 hp and 2 units running at 3 hp is calculated as follows 2 l hr 2 hp 3 units 2 l hr 3 hp 2 units 24 l hr
- Relationship between riser diameter and allowable drainage for extended ventilation system
- Relationship between horizontal pipe diameter and allowable drainage for extended ventilation system
- Piping diameter for grouped drain pipes
- Notes calculations have been made with water area inside the pipe as 10 allowable flow rate figures below the decimal have been discarded use vp30 or larger pipe after the convergence point
- Notes allowed flow rate figures below the decimal have been discarded use vp30 or larger pipe in risers use the same drain pipe for the humidifier as the indoor unit
- General information 49
- Drain pump kit
- Drain piping work rig the drain pipe as shown below and take measures against condensation improperly rigged piping could lead to leaks and eventually wet furniture and belongings
- Drain piping for each model
- Installation sien34 705
- If converging multiple drain pipes install according to the procedure shown below
- General information
- Caution setting the unit at an angle opposite to the drain piping might cause leaks
- 1 carry out the drain piping the diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe vinyl tube pipe size 25 mm outer dimension 32 mm keep the drain pipe short and sloping downwards at a gradient of at least 1 100 to prevent air pockets from forming if the drain hose cannot be sufficiently set on a slope execute the drain raising piping to keep the drain hose from sagging space hanging wires every 1 to 1 m
- Use the attached drain hose and clamp metal insert the drain hose into the drain socket up to the white tape tighten the clamp until the screw head is less than 4mm from the hose wrap the attached sealing pad over the clamp and drain hose to insulate insulate the drain hose inside the building
- Select converging drain pipes whose gauge is suitable for the operating capacity of the unit
- Precautions for drain raising piping install the drain raising pipes at a height of less than 310 mm install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit
- Ceiling mounted cassette type fxfq m multi flow
- Sien34 705 installation
- Select converging drain pipes whose gauge is suitable for the operating capacity of the unit
- Note to ensure no excessive pressure is applied to the included drain hose 1 do not bend or twist when installing this may cause leakage if converging multiple drain pipes install according to the procedure shown below
- Install the drain raising pipes at a height of less than 550 mm install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit
- General information 53
- Installation sien34 705
- General information
- Caution drain piping connections do not connect the drain piping directly to sewage pipes that smell of ammonia the ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger keep in mind that it will become the cause of getting drain pipe blocked it water collects on drain pipe
- Drain piping work
- Ceiling mounted cassette corner type fxkq ma
- Caution drain piping connections do not connect the drain piping directly to sewage pipes that smell of ammonia the ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe
- 2 after piping work is finished check drainage flows smoothly open the inspection opening add approximately 1liter of water slowly into the drain pan and check drainage flow
- Note use the drain outlet for maintenance to drain water from the drain pan
- Installation sien34 705
- General information
- Slim ceiling mounted duct type fxdq
- No good good
- Ceiling mounted built in type fxsq m
- Ceiling mounted duct type fxmq ma
- Sien34 705 installation
- General information 63
- Ceiling suspended type fxhq ma
- Wall mounted type fxaq ma
- Sien34 705 installation
- General information 65
- Drain piping connections do not connect the drain piping directly to sewage pipes that smell of ammonia the ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe
- Caution
- Floor standing concealed floor standing type fxlq ma fxnq ma
- Ceiling suspended cassette type fxuq ma
- Outdoor air processing unit fxmq mf
- Electrical work
- Control wiring
- Power supply cabling of main power supply
- Taking account of noise and vibration
- Duct work indoor
- Sien34 705 installation
- Selection of location
- Personal computer or radio
- No limit to wall height no limit to wall height
- Indoor unit
- If the electric wave of am broadcasting is particularly weak keep distances of 3m or more if the electric wave of am broadcasting is particularly weak keep distances of 3m or more and use conduit tubes for power and transmission lines 2 in heavy snowfall areas select an installation site where snow will not affect operation of the unit 3 if condensate may drip on downstairs walkway depending on the floor condition take a measure such as the installation of central drain pan kit sold separately 4 the refrigerant r 410a itself is nontoxic nonflammable and is safe if the refrigerant should leak however its concentration may exceed the allowable limit depending on room size due to this it could be necessary to take measures against leakage refer to the chapter caution for refrigerant leaks
- General information 75
- Caution 1 an inverter air conditioner may cause electronic noise generated from am broadcasting examine where to install the main air conditioner and electric wires keeping proper distances away from stereo equipment personal computers etc
- Branch switch overcurrent breaker
- This unit both indoor and outdoor is suitable for installation in a commercial and light industrial environment if installed as a household appliance it could cause electromagnetic interference the vrv outdoor units should be installed in a location that meets the following requirements 1 the foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 2 the space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is available refer to below figure and choose one of both possibilities 3 there is no danger of fire due to leakage of inflammable gas 4 ensure that water cannot cause any damage to the location in case it drips out the unit e g in case of a blocked drain pipe 5 the piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length see example of connection 6 select the location of the unit in such a way that neither the discharged air
- Service space
- Inspecting and handling the unit
- Operational steps
- Notes 1 the proportions of cement sand gravel for the concrete shall be 1 2 4 and ten reinforcement bars that their diameter are 10mm approx 300mm intervals shall be placed 2 the surface shall be finished with mortar the corner edges shall be chamfered 3 when the foundation is built on a concrete floor rubble is not necessary however the surface of the section on which the foundation is built shall have rough finish 4 a drain ditch shall be made around the foundation to thoroughly drain water from the equipment installation area 5 when installing the equipment on a roof the floor strength shall be checked and water proofing measures shall be taken 6 y groove unnecessary for 5hp models 7 when selecting the piping from the bottom provide the height 200mm or more from a base
- Installation sien34 705
- Installation of outdoor unit
- General information
- Foundation of units
- Unpacking and placing the unit
- Sien34 705 installation
- Notes 1 when installing on a roof make sure the roof floor is strong enough and be sure to water proof all work 2 make sure the area around the machine drains properly by setting up drainage grooves around the foundation drain water is sometimes discharged from the outdoor unit when it is running 3 for anti corrosion type use nuts with resin washers if the paint on nut connections comes off the anti corrosion effect may decrease
- Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise secure the unit to its base using foundation bolts use four commercially available m12 type foundation bolts nuts and washers the foundation bolts should be inserted 20 mm make sure the base under the unit extended more than 765mm behind the unit the height of the base should be at least 150mm from the floor the unit must be installed on a solid longitudinal foundation steelbeam frame or concrete as indicated in figure
- General information 79
- Bolt pitch
- Caution caution label
- To in s t a ller s
- Do not use stands to support the corners
- Warning caution to electric shock
- To service person
- To all handlers
- For the location of the el compo box and the service port see as shown below on the right
- For removing the front panel lift the panel a little
- Check the system status on led h2p on the pc board a1p from inspection door on the el compo box cover led display shows turning off normal turning on abnormal flashing under preparation for multi system check the pc board of the master unit the master unit is the outdoor unit connected to the transmission wiring to the indoor units
- Caution for removing and installing the el compo box cover
- Beware the fan running when inspect do not touch the charged parts when inspect
- And pull the panel towards you
- Test operation
- Procedure and outline
- Check work prior to turn power supply on
- Before starting the normal operation after the completion of check operations make sure indoor and outdoor units normally operate
- Be sure to turn the power on 6 hours before starting operation to protect compressors to power on clankcase heater
- Turn power on
- Turn outdoor unit and indoor unit power on
- The master unit is the outdoor unit to which the transmission wiring for the indoor units is conncted the other outdoor units are slave units
- The check operations shown below will be automatically initiated check for erroneous wirings check for failure to open stop valves check for excessive refrigerant refilling automatic judgment of piping length
- Sien34 705 test operation
- Make field settings with outdoor unit pc board
- Make field settings if needed for the setting procedure refer to information in 4 field setting from outdoor unit on page 101 onward for the outdoor multi system make field settings with the master unit field settings made with the slave unit will be all invalid
- General information 83
- Conduct check operations
- Check to be sure the transmission is normal the transmission is normal if the leds display conditions as shown in table below
- Check the led display of the outdoor unit pc board
- Check for normal operation
- Note1 onsite settings with the power off if the cool heat selector was connected to the outdoor unit set the dip switch ds1 on the outdoor unit pc board a1p to on it is set to off when shipped from the factory for the position of the dip switch ds1 see the service precautions label see at right which is attached to the el compo box lid
- How to distinguish the master unit sub unit 1 and sub unit 2 in the multi system
- Check operation procedure
- Check operation
- Step4 make the onsite settings as needed using the push button bs1 bs5 on the outdoor unit pc board a1p with the power on see 4 field setting from outdoor unit step5 perform the check operation following the check operation method of the service precautions label on the el compo box lid the system operation for about 40 minutes and automatically stops the check operation if the malfunction code is not displayed in the remote control after the system stop check operation is completed normal operation will be possible after 5 minutes if the malfunction code is displayed in the remote control correct the malfunction following remote control displays malfunction code and perform the check operation again
- Step1 make the onsite setting as needed using the dip switches on the outdoor unit pc board a1p with the power off see below instruction note1 step2 close the el compo box lid and all front panels except as the side of the el compo box and turn on the power to the outdoor unit and all connected indoor units be sure to turn the power on at least 6 hours before operation in order to have power running to the crank case heater step3 check the led display on the outdoor unit pc board a1p is as shown in the table below and transmission is normal
- Remote control displays malfunction code
- If any malfunction codes other than the above are displayed check the service manual for how to respond
- When turning on power the second time and subsequent
- When turning on power first time
- When an indoor unit or outdoor unit has been added or indoor or outdoor unit pc board has been changed
- The unit cannot be run for up to 12 minutes to automatically set the master power and address indoor outdoor address etc status
- Tap the reset button on the outdoor unit pc board operation becomes possible for about 2 minutes if you do not push the reset button the unit cannot be run for up to 10 minutes to automatically set master power status
- Operation when power is turned on
- Caution when the 400 volt power supply is applyed to n phase by mistake replace inverter p c b a2p and control transformer t1r t2r in switch box together
- Be sure to push and hold the reset button for 5 seconds if not the addition cannot be recognized in this case the unit cannot be run for up to 12 minutes to automatically set the address indoor outdoor address etc status
- 4 local setting switch used to make field settings
- 3 mode setting switchused to change mode
- 2 set mode display led leds display mode according to the setting
- 1 microcomputer normal monitor this monitor blinks while in normal operation and turns on or off when a malfunction occurs
- Outdoor unit pc board layout
- Outdoor unit pc board
- Unit no
- Second code no
- Mode no
- First code no
- Field setting from remote control
- Field setting
- Field set mode
- Second code no first code no
- Mode no
- Infrared remote control indoor unit
- Field set mode
- Simplified remote control
- Notes 1 settings are made simultaneously for the entire group however if you select the mode no inside parentheses you can also set by each individual unit setting changes however cannot be checked except in the individual mode for those in parentheses 2 the mode numbers inside parentheses cannot be used by infrared remote controls so they cannot be set individually setting changes also cannot be checked 3 marked are factory set 4 do not make settings other than those described above nothing is displayed for functions the indoor unit is not equipped with 5 88 may be displayed to indicate the remote control is resetting when returning to the normal mode 6 if the setting mode to equipped heat reclaim ventilation fan conducts the fan residual operation by linking to indoor unit
- General information 91
- Sien34 705 test operation
- Setting contents and code no vrv indoor unit
- Test operation sien34 705
- General information
- Applicable range of field setting
- 1 static pressure selection
- When a ultra long life filter is installed the filter sign timer setting must be changed
- Ultra long life filter sign setting
- This input is used for on off operation and protection device input from the outside the input is performed from the t1 t1 terminal of the operation terminal block x1a in the electric component box
- Setting table
- If switching the filter sign on time set as given in the table below set time
- Filter sign setting
- Fan speed changeover when thermostat is off
- External on off input
- Detailed explanation of setting modes
- By setting to set fan speed you can switch the fan speed to the set fan speed when the heating thermostat is off since there is concern about draft if using fan speed up when thermostat is off you should take the setup location into consideration
- Make the following setting according to the ceiling height the setting position no is set to 01 at the factory in the case of fxaq fxhq
- In the case of fxuq71 125
- In the case of fxfq25 80
- In the case of fxfq100 125
- For the air conditioners with no setting for the function same as factory setting the units will be left in the stop condition when the power supply is reset automatically after power failure reset or the main power supply is turned on again after once turned off however for the air conditioners with the setting the units may start automatically after power failure reset or the main power supply turned on again return to the same operation condition as that of before power failure
- For the above reasons when the unit is set enabling to utilize auto restart function after power failure reset utmost care should be paid for the occurrence of the following situation
- Caution 1 the air conditioner starts operation suddenly after power failure reset or the main power supply turned on again consequently the user might be surprised with question for the reason why 2 in the service work for example turning off the main power switch during the unit is in operation and turning on the switch again after the work is completed start the unit operation the fan rotates
- Auto restart after power failure reset
- Air flow adjustment ceiling height
- Setting of air flow direction adjustment range
- Setting of air flow direction adjustment
- Set the air flow direction of indoor units as given in the table below set when optional air outlet blocking pad has been installed the second code no is factory set to 01
- Only the model fxkq has the function when only the front flow is used sets yes no of the swing flap operation of down flow
- Make the following air flow direction setting according to the respective purpose
- Air flow rate switching at discharge grille for field air flow rate switching
- Air flow direction setting
- When the optional parts high performance filter etc is installed sets to change fan speed for securing air flow rate follow the instruction manual for the optional parts to enter the setting numbers
- Setting table
- Setting of the static pressure selection for fxdq model
- Outdoor air processing unit field setting remote control
- Note bold face in indicates the default setting
- Test operation sien34 705
- Mode no
- Group no setting example
- Group no setting by infrared remote control for centralized control 1 when in the normal mode push button for 4 seconds or more and operation then enters the field set mode 2 set mode no 00 with button 3 set the group no for each group with button advance backward
- Group no
- General information
- Field set mode
- Enter the selected group numbers by pushing button 5 push button and return to the normal mode
- Caution when turning the power supply on the unit may often not accept any operation while 88 is displaying after all indications were displayed once for about 1 minute on the liquid crystal display this is not an operative fault
- Brc7c type brc7e type brc4c type
- Contents of control modes
- Setting of operation control mode from remote control local setting
- Whether operation by remote control will be possible or not for turning on off controlling temperature or setting operation mode is selected and decided by the operation mode given on the right edge of the table below
- How to select operation mode
- Do not select timer operation possible by remote control if not using a remote control operation by timer is impossible in this case 1 factory setting
- List of field setting items this following section indicates the list of field setting items for the lists of dip switch contents setting mode 1 and setting mode 2 refer to information in tables shown on the following page onward for setting items of 1 refer to detailed information provided on page 111 onward
- Field setting from outdoor unit
- Setting by dip switches using dip switches on the pc board enables field setting shown below however make no changes of factory settings except for ds1 1
- For setting items of 1 refer to detailed information provided on page 112 onward
- This mode is used to set and check the following items 1 set items in order to make cool heat selection in a batch of outdoor unit group change the setting cool heat selection ind used to select cool or heat by individual outdoor unit factory set cool heat selection master used to select cool or heat by outdoor unit group with the master unit cool heat selection slave used to select cool or heat by outdoor unit group with the slave unit 2 check items the following items can be checked 1 current operating conditions normal abnormal in check operation 2 setting conditions of cool heat selection individual batch master batch slave 3 low noise operating conditions in normal operation in low noise operation 4 demand operating conditions in normal operation in demand operation
- Test operation sien34 705
- Procedure for changing cool heat selection setting
- General information
- A setting mode 1
- 7 8 7 7 7 7
- B setting mode 2
- 7 8 8 7 8
- 7 7 7 7 7
- The numbers in the no column represent the number of times to press the set bs2 button
- Te setting h
- 7 8 8 7 7
- Tc setting h
- 7 8 7 8 8
- Sien34 705 test operation
- 7 8 7 8 7
- Setting item 0 display contents of number of units for various settings
- 7 8 7 7 8
- General information 109
- 7 8 7 7 7
- Emg operation backup operation setting
- 7 7 9 7 7
- Defrost select setting short
- 7 7 8 8 8
- C monitor mode
- 7 7 8 8 7
- 8 8 7 7 8
- 7 7 8 7 8
- 8 7 8 8 7
- 7 7 8 7 7
- 8 7 8 7 8
- 7 7 7 9 7
- 8 7 8 7 7
- 7 7 7 8 8
- 8 7 7 7 7
- 7 7 7 8 7
- 7 8 8 8 8
- 7 7 7 7 9
- 7 8 8 8 7
- 7 7 7 7 8
- There are the following 4 cool heat switching modes set cool heat separately for each outdoor unit system by indoor unit remote control set cool heat separately for each outdoor unit system by cool heat switching remote control set cool heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by indoor unit remote control set cool heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by cool heat switching remote control
- Set cool heat separately for each outdoor unit system by indoor unit remote control
- It does not matter whether or not there is outdoor outdoor unit wiring set outdoor unit pc board ds1 1 to in factory set set cool heat switching to ind individual for setting mode 1 factory set set the master unit indoor unit having the right to select the cooling heating operation mode
- In the case of wired remote controls
- In the case of infrared remote controls
- For the details refer to the installation manual supplied together with the indoor unit
- Cool heat mode switching heat pump model only
- Test operation sien34 705
- Set cool heat separately for each outdoor unit system by cool heat switching remote control it does not matter whether or not there is outdoor outdoor unit wiring set outdoor unit pc board ds1 1 to out factory set set cool heat switching to ind individual for setting mode 1 factory set
- General information
- Cool heat selector
- To indoor unit
- Set cool heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by indoor unit remote control install the external control adapter for outdoor unit on either the outdoor outdoor indoor outdoor transmission line set outdoor unit pc board ds1 1 to in factory set in setting mode 1 set the outdoor unit you want to give cool heat selection permission to as the group master and set the other outdoor units as group slave units set the outdoor unit external control adapter ss1 to both factory set or c h and ss2 to off factory set
- P ds1 ds2
- Multi outdoor units connection
- Multi outdoor units connection
- To indoor unit
- Set cool heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by cool heat switching remote control install the external control adapter for outdoor unit on either the outdoor outdoor indoor outdoor transmission line mount the cool heat selection remote control to the master outdoor unit for the unified control set the ds1 1 on the pc board of master outdoor unit to out in setting mode 1 set the outdoor unit you want to give cool heat selection permission to as the group master and set the other outdoor units as group slave units set the outdoor unit external control adapter ss1 to both factory set or c h and ss2 to off factory set
- P ds1 ds2
- Supplementation on and when switching cool heat for each adapter pc board with the use of more than one adapter pc board set the address of the external control adapter for outdoor unit pc board ds1 and ds2 so that it matches the unified cool heat address of outdoor unit main pc board
- Set lower 5 digits with binary number no to no 1
- Address setting for
- Setting of low noise operation and demand operation
- Sien34 705 test operation
- Image of operation in the case of b
- Image of operation in the case of a and b
- Image of operation in the case of a
- General information 117
- Setting of demand operation
- By connecting the external contact input to the demand input of the outdoor unit external control adapter optional the power consumption of unit operation can be saved suppressing the compressor operating condition
- B when the normal demand operation is carried out use of the external control adapter for outdoor unit is not required 1 while in setting mode 2 make setting of the set item no 32 setting of constant demand to on 2 while in setting mode 2 select the set item no 30 setting of demand 1 level and then set the setting condition to targeted mode
- A when the demand operation is carried out by external instructions with the use of the external control adapter for outdoor unit 1 while in setting mode 2 set the setting condition for set item no 12 setting of external low noise demand operation to yes 2 if necessary while in setting mode 2 select the set item no 30 setting of demand 1 level and then set the setting condition to targeted mode
- Sien34 705 test operation
- Image of operation in the case of b
- Image of operation in the case of a and b
- Image of operation in the case of a
- General information 119
- Detailed setting procedure of low noise operation and demand control
- Setting of vacuuming mode
- Setting of refrigerant recovery mode
- Check operation function
- Check operation detail
- Procedure for checking dangerous concentration
- Maximum concentration level
- Introduction
- Caution for refrigerant leaks
- Step 3
- Step 2
- Step 4
- Set of operation manuals
- Operational steps
- Names of those responsible for the work emergency contact address
- List of equipment which has been delivered
- It is essential to prepare a control wiring diagram which clarifies the refrigerant system and the control system
- Important points
- Hand over to customer
- Equipment guarantees
- Contract drawings
- Operating noise of indoor units
- Operating noise differs depending on the place of measurement room because of the various degrees with which the room reverberates the sound to determine the amount of reverberation under uniform conditions the unit has been measured in a dead room with results having been compiled in the below table the actual sound produced in unit operation can be determined from table 1
- Notes 1 excluding bedrooms 2 reference values of faint noises in the place of usage
- Difference between catalogue data and actual noise
- Classifications of indoor unit environments reference data
- Appendix
- Sound pressure rise due to room reverberation higher than catalogue data
- Faint noises and correcting operating noise with respect to faint noises
- Calculating operating noise
- When the piping length between the multi connection kits or between multi connection kit and outdoor unit is 2m or more prepare a vertical projection part 200mm or more as shown below only on the gas pipe line location less than 2m from multi connection kit in the case of 2m or less
- The projection part between multi connection piping kits
- Since there is a possibility that oil may be collected on a stop machine side install piping between outdoor units to go to level or go up to an outdoor unit and to make a slope
- Piping installation point
- In the case of 2m or more
- General information
- Appendix sien34 705
- Indicate the outdoor unit multi connection piping kit
- In case of multi outdoor system re read to the first outdoor unit multi connection piping kit as seen from the indoor unit
- Example of connection r 410a type
- Connection of 8 indoor units
- Example refrigerant branch using refnet joint
- Branch with refnet joint
- Example refrigerant branch using refnet joint and refnet header
- Branch with refnet joint and refnet header
- Example refrigerant branch using refnet header
- Branch with refnet header
- When using refnet joint at the first branch counted from the outdoor unit side choose from the following table in accordance with the outdoor unit capacity type example refnet joint a
- Refrigerant branch kit selection
- Refnet joint b
- Outdoor unit refnet joint c
- Indoor units 1 8
- How to select the refnet joint
- Example of downstream indoor units 1 example in case of refnet joint c indoor units 3 4 5 6 7 8
- Example in the case of refnet header indoor units 1 2 3 4 5 6 7 8
- Example in case of refnet joint b indoor units 7 8 example in case of refnet joint header indoor units 1 2 3 4 5 6
- Choose the refnet joints other than that for the first branch from the following table in accordance with the total capacity index of all the indoor units connected below the refnet joint
- C d e f g h 1 2 3 4 5 6
- 200 khrp26m22h max 4 branch 200
- X 640 khrp26m72h max 8 branch see note 3 next page 640
- X 290 khrp26m33h max 8 branch 290
- Sien34 705 appendix
- Refnet joint b
- Refnet header
- Outdoor unit
- Khrp26m73h max 8 branch khrp26m73hp
- K j 7 8
- Indoor units 1 8
- Indoor unit total capacity index refrigerant branch kit name
- How to select the refnet header heat pump cooling only rx y q5 54p 50ph
- General information 137
- C d e f g h i b 1 2 3 4 5 6 7 8
- How to select the outdoor unit multi connection piping kit this is required when the system is multi outdoor unit system
- Heat pump 50hz 60hz cooling only 50hz
- Choose from the following table in accordance with the number of outdoor units
- See 7 note 1 temper grade and wall thickness for pipes temper grade o type and 1 2h type indicate the material types specified in jis h 3300 unit mm
- Piping between outdoor unit and first refrigerant branch kit
- Pipe size selection
- Heat pump 50hz 60hz cooling only 50hz rx y q5 54p 50ph
- Choose from the following table in accordance with the outdoor unit capacity type piping between outdoor unit multi connection piping kits part b piping between outdoor unit and outdoor unit multi connection piping kit part c choose from the following table in accordance with the total capacity type of all the outdoor units connected above outdoor unit multi connection piping kit unit mm
- Piping between refrigerant branch kits choose from the following table in accordance with the total capacity index of all the indoor units connected below this do not let the connection piping exceed the main refrigerant piping size unit mm
- Piping between refrigerant branch kit and indoor unit match to the size of the connection piping on the indoor unit unit mm
- Total length m of liquid piping size at ø9
- Total length m of liquid piping size at ø6
- Refnet joint a b
- Refnet header
- Outdoor unit
- Indoor units 1 8
- How to calculate the additional refrigerant to be charged
- Heat pump 50hz 60hz cooling only 50hz rx y q5 54p 50ph
- 0 7 total length m of liquid piping size at ø22 0 6 total length m of liquid piping size at ø19 0 8 total length m of liquid piping size at ø15 0 2 total length m of liquid piping size at ø12
- Size of main gas and liquid pipes and allowable length
- Note 1
- Heat pump 50hz 60hz cooling only 50hz rx y q5 54p 50ph
- Diameter of above case
- Sien34 705 appendix
- Note 3
- Note 2
- If the pipe size above the refnet header is φ 34 or more khrp26m73hp is required
- General information 143
- Request for indication of setting contents additional refrigerant charging amount and installation date
- Record of field setting and additional refrigerant charge
- General information
- Fill the following record and put it on the back side of electrical board
- Appendix sien34 705
- Units bhfp22p100 3 units bhfp22p151
- Bhfp 22 p100
- This kit contains the following parts
- 2 or 3 outdoor units can be connected there are restrictions on the combination and the installation order of outdoor units so please refer to the engineering data of vrv iii and the installation manual attached sheet of outdoor unit for details
- The following parts are needed to connect this kit and are not included
- Temper grade copper tube o d copper tube w t
- Selection procedure
- See the connecting pipe sizes and location of cutting the joint for details on the necessary size prepare a gas pipe diameter for the upper outdoor unit as listed in connecting pipe sieze and location of cutting the joint for insulation materials
- Quantity and selection procedure of elbow only applies to a front or bottom connection for a lower front connection the quantity and selection procedure are different so please refer to the instructions for a lower front connection a joint for the same diameter pipes is needed only for a bottom connection see the instructions for the bottom connection for details on quantity and specifications the min thickness of the pipes in this manual shows the requirements of japanese high pressure gas control low as of jan 2003 and the temper grade o 1 2h shows the material type of jis h 3300 the tickness and material shall be selected in accordance with local for the design pressure 4 ompa 40bar unit mm
- Outdoor unit multi connection piping kit
- O type 1 2h type
- Number of outdoor units connected outdoor unit multi connection piping kit
- Kit name
- Insulation for piping connection piping
- Gas side joint liquid side joint gas side reducer liquid side reducer
- Field supply parts
- Bhfp22p100 151
- Bhfp 22 p151
- When istalling this kit please apply the following restrictions to the piping installer
- View view
- Restrictions on installing multi connection piping kit
- Installation examples
- General information
- Caution label max 15
- Caution label
- Appendix sien34 705
- Procedure for front connection
- Installation examples
- General information 147
- Cutting procedure
- Caution
- Bhfp22p100 installation instructions
- 2 finished dimensions
- 1 exterior view
- Sien34 705 appendix
- This table shows the case when the a dimensions shown in 1 2 finished dimensions is 290 mm if the a dimensions exceed 290 mm see table 1 and adjust the dimensions of the gas pipe 1 and 2 the l dimensions of the gas pipe 2 in table 1 show those when the field supply elbows have b dimension in table 2 if the b dimension is not same with table 2 see table 1 and 2 and adjust them accordingly
- Table 2 table 1
- General information
- Cut the pipes according to table 1
- Connection of gas and liquid pipes
- Appendix sien34 705
- 2 connection of pipes
- 1 cutting the field supply gas pipes
- The work after the kit is connected
- Sien34 705 appendix
- Insulation of joints
- General information 149
- Follow the instructions in the installation manual included with the outdoor unit when performing installation work
- Connection of piping between the outdoor unit and the indoor unit
- Air tight test
- Prodecure for lower front connection
- Outdoor unit b
- Outdoor unit a
- Installation examples
- General information
- Appendix sien34 705
- A standard installation has the following dimensions
- 2 finished dimensions
- 1 exterior view
- Ground
- General information 151
- Connection of gas and liquid pipes
- Caution
- Air tight test
- 2 connection of pipes
- 1 cutting the field supply gas pipe 1 to 4
- The work after the kit is connected
- Table 3 gas pipe 1 field supply gas pipe 2 field supply gas pipe 3 field supply gas pipe 4 field supply
- Sien34 705 appendix
- Max 15
- Insulation of joints
- Procedure for bottom connection
- Installation examples
- General information
- Connection of gas and liquid pipes
- Caution
- Appendix sien34 705
- 1 exterior view
- 1 cutting the field supply gas pipe 1 and 2 and the gas side accessory pipe 3 attached to the outdoor unit
- Caution
- Air tight test
- 2 connection of pipes
- The work after the kit is connected
- Sien34 705 appendix
- Max 15
- Insulation of joints
- Ground
- General information 153
- There are some restrictions on the interconnecting piping between the outdoor units see the installation manual attached to the outdoor
- Procedure for front connection
- Installation examples
- General information
- Gas pipe liquid pipe
- Bottom frame
- Bhfp22p151 installation instructions
- Appendix sien34 705
- 2 finished dimension
- 1 exterior view
- Use pipe cutter for cutting
- Units and make sure to carry out proper piping if the piping restrictions are not observed it may result in malfunction of the unit
- The work after the kit is connected
- Table 6
- Sien34 705 appendix
- Max 15
- Insulation of joints
- Ground
- General information 155
- Gas pipe 1 field supply gas pipe 2 field supply gas pipe 3 field supply
- Connection of gas and liquid pipes
- Caution
- Air tight test
- 2 connection of pipes
- 1 cutting the field supply gas pipes
- 1 cutting the field supply gas pipes
- Procedure for front connection
- Installation examples
- General information
- Connection of gas and liquid pipes
- Appendix sien34 705
- 2 connection of pipes
- 1 exterior view 1 2 finished dimensions
- The work after the kit is connected
- Insulation of joints
- Air tight test
- Procedure for bottom connection
- Installation examples
- General information
- Caution
- Appendix sien34 705
- 1 exterior view
- The work after the kit is connected
- Sien34 705 appendix
- Insulation of joints
- General information 159
- Connection of gas and liquid pipes
- Air tight test
- 2 connection of pipes
- 1 cutting the field supply gas pipe 1 and 2 and the gas side accessory pipe 3 attached to the outdoor unit
- Refnet joint branch kit
- Refnet joint and header
- Khrp26a73t
- Khrp26a72t
- Khrp26a33t
- Khrp26a22t
- General information
- Appendix sien34 705
- Sien34 705 appendix
- Refnet header branch kit
- Khrp26m73h
- Khrp26m72h
- Khrp26m33h
- Khrp26m22h
- General information 161
- Gas side liquid side
- Reducer
- Pipe size reduce
- Installation procedure
- Refnet header
- Make sure that all branch pipes are fitted such that they branch either horizontally or vertically
- General information 163
- For gas and liquid branch pipes
- Branch pipes must be insulated in accordance with the handbook which comes with each kit
- When you are cutting an inlet or outlet pipe with a pipe cutter make sure that you make the cut in the center of the connection area
- When the size of the selected field piping is different from that of branch pipe then the connecting section should be cut with a pipe cutter as shown in the figure below
- Sien34 705 appendix
- Refnet joints and headers
- Refnet joints
- Vrv inspection sheet
- Sien34 705 appendix
- General information 165
- V megatester
- General information
- System name
- Gas detector no leaks g ng
- Standard guideline measurement values
- Fan motor electrical insulation
- Screwdriver etc no looseness g ng
- Compressor electrical insulation
- Refrigerant system gas detector no leaks
- Breaker capacity visual inspection specified capacity g ng
- Outdoor unit 2 outdoor unit 3
- Before turning on the power
- Outdoor unit 1
- Appendix sien34 705
- M ω or more m ω
- Air filter visual inspection no clogging or damage
- M ω or more
- Inv m ω std1 m ω std2 m ω
- Installation visual inspection short circuit etc g ng
- Inspection method
- Inspection item
- Indoor unit
- Heat exchanger visual inspection no clogging or damage
- Heat exchanger visual inspection
- Standard guideline measurement values
- Sien34 705 appendix
- Installation visual inspection short circuit etc
- Inspection method
- Inspection item
- Indoor unit
- General information 167
- Fan motor electrical insulation 500 v megatester 1 m ω or more
- Decision
- Auxiliary heater electrical insulation 500 v megatester 1 m ω or more
- Outdoor unit 3
- Outdoor unit 2
- Outdoor unit 1
- General information
- During operation
- Appendix sien34 705
- System name
- System name
- Suction air temperature
- Standard guideline measurement values
- Sien34 705 appendix
- Powerly supply voltage tester rated voltage 10
- Inspection method
- Inspection item
- Indoor unit
- General information 169
- Fan rotation direction visual inspection forward rotation
- Fan operating current clamp meter
- Fan noise vibration listening no noise or vibration
- During operation
- Discharge air temperature
- Thermometer differential
- 13 c when cooling 15 20 c when heating
- Thermometer
- Rxyq5py1 rxq5py1
- Piping system diagrams
- Outdoor unit
- Heat pump cooling only 50hz
- General information
- Appendix sien34 705
- Stop valve with service port ø 7 mm flare connection
- Sien34 705 appendix
- Rxyq8py1 rxq8py1
- General information 171
- Stop valve with service port ø7 mm flare connection
- Rxyq10py1 rxyq12py1 rxq10py1 rxq12py1
- General information
- Appendix sien34 705
- Stop valve with service port ø7 mm flare connection
- Sien34 705 appendix
- Rxyq14py1 rxyq16py1 rxyq18py1 rxq14py1 rxq16py1 rxq18py1
- General information 173
- Rxyq5pyl
- Heat pump 60hz
- General information
- D055764a
- Appendix sien34 705
- Sien34 705 appendix
- Rxyq8pyl
- General information 175
- D055765a
- General information
- D055766b
- Appendix sien34 705
- Rxyq10pyl rxyq12pyl
- Sien34 705 appendix
- Rxyq14pyl rxyq16pyl rxyq18pyl
- General information 177
- D050785a
- Φ 15 or less attached piping above φ 19
- Liquid piping connection port
- Indoor unit
- Heat exchanger
- Gas piping connection port
- Fxcq fxfq fxkq fxsq fxmq fxhq fxaq fxlq fxnq
- Flare connection
- Flare connectio
- Filter filter
- Electronic expansion valve
- General information 179
- Sien34 705 appendix
- Refrigerant pipe connection port diameters
- Mm model gas liquid fxzq20m 25m 32m 40m 50m φ 12 φ 6
- Refrigerant pipe connection port diameters
- Liquid side
- Gas side
- Fxmq125mf 200mf 250mfv1
- Filter filter
- Electronic expansion valve
- Indoor unit
- Fxuq bevq
- Connection unit
- Rxyq5py1 rxyq5pyl
- Heat pump 50hz 60hz outdoor unit
- General information
- Appendix sien34 705
- Wiring diagrams heat pump 50hz 60hz cooling only 50hz
- Sien34 705 appendix
- Rxyq8py1 rxyq8pyl
- General information 183
- D050454j
- Cool heat selector
- T1a v1cp v1r v2r x1a x2a x1m x1m x1m y1e y2e y1s y2s y3s z1c 5c z1f
- Rxyq10py1 rxyq10pyl
- General information
- D050455h
- Appendix sien34 705
- Sien34 705 appendix
- Rxyq12py1 rxyq12pyl
- General information 185
- D051890g
- Appendix sien34 705
- Rxyq14py1 rxyq16py1 rxyq18py1 rxyq14pyl rxyq16pyl rxyq18pyl
- General information
- D050456h
- Sien34 705 appendix
- Rxq5py1
- General information 187
- D055257a
- Cooling only outdoor unit
- S1ph v1cp v1r v2r x1a x2a x1m x1m y1e y2e y1s y2s y3s z1c 5c z1f
- Rxq8py1
- General information
- D055258a
- Appendix sien34 705
- Rxq10py1
- General information 189
- D055259a
- T1a v1cp v1r v2r x1a x2a x1m x1m y1e y2e y1s y2s y3s z1c 7c z1f
- Sien34 705 appendix
- T1a v1cp v1r v2r x1a 4a x1m x1m y1e y2e y1s y2s y3s
- Rxq12py1
- General information
- D055260a
- Appendix sien34 705
- T1a v1cp v1r v2r x1a 4a x1m x1m y1e y2e y1s y2s y3s
- Sien34 705 appendix
- Rxq14py1 rxq16py1 rxq18py1
- General information 191
- D055261a
- Indoor units
- General information
- Field wiring heat pump cooling only 50hz 60hz
- Appendix sien34 705
- Rx y q5p 8p 10p 12p 14p 16p 18py1 rxyq5p 8p 10p 12p 14p 16p 18pyl
- Outdoor units
- When the source is connected in series between the units
- When the power source is supplied to each outdoor unit individually
- Sien34 705 appendix
- Rx y q20p 22p 24p 26p 28p 30p 32p 34p 36py1 rxyq20p 22p 24p 26p 28p 30p 32p 34p 36pyl
- General information 193
- When the power source is supplied to each outdoor unit individually
- When the power source is connected in series between the units
- Rx y q38p 40p 42p 44p 46p 48p 50p 52p 54py1 rxyq238p 40p 42p 44p 46p 48p 50p 52p 54pyl
- General information
- Appendix sien34 705
- Situation
- Main points
- Example 1 signal interference due to use of multiple core cable all model
- Bad examples and good examples in installation
- Source of problem and remedial action
- The remote control is not showing any malfunction and the system is operating but there is no flow of warm air from the indoor unit in heating mode
- The connecting cables and the corresponding piping were not correctly matched recabling was carried out and the fault disappeared
- Special care must be taken when the pipework and cabling are carried out by different people run each indoor unit in turn to check that the system is correctly matched
- Source of problem and remedial action
- Situation
- Main points
- General information
- Example 2 mismatch between cables connecting indoor and outdoor units and corresponding piping all model
- Appendix sien34 705
- Source of problem and remedial action
- Situation
- Main points
- Example 3 drain pipe trap shape defective
- Main points
- Example 4 pressure down despite absence of leaks during air tight test all model
- Source of problem and remedial action
- Situation
- Source of problem and remedial action
- Situation
- Main points
- Example 5 excessive noise due to incorrect angling of refnet joints
- Situation
- Remedial action
- Main points
- For your reference
- Example 6 cracks develop in field pipes due to thermal expansion and contraction
- Remedial action
- Main points
- Example 8 the centralized control group number cannot be set inverter k series
- Example 7 transmission wiring between the cool heat selector and the outdoor unit is too close to a high voltage wire
- Cause and remedial action
- Situation
- Situation
- Remedial action
- Main points
- Example 9 88 cannot be cleared from the central remote control
- The condition completes by executing the check operation again
- Rx y q
- Point of diagnosis
- P vrv iii series
- Measure
- Malfunction f6 is displayed during check operation in the winter season
- Due to temporary refrigerant mixing into refrigerating oil misjudgment is made when a check operation is executed under the condition of low outdoor temperature
- Condition
- Be sure to execute a check operation with the front panel closed or misjudgment is made even if the outdoor temperature is low
- Applicable models
- A malfunction f6 overcharge of refrigerant is displayed when a check operation is executed as a test operation under the condition of low outdoor temperature in the winter season
- Point of diagnosis
- Measure
- Led display for master slave judgment malfunctions at the time of test operation
- Condition
- Applicable models
- Point of diagnosis
- Measure
- Condition
- Cautions for test operation
- Cautions for demand control with externally controlled adapter
- Applicable models
- No heating operation is available though cooling operation is possible fan only operation continues with no malfunction displayed
- Measure
- Inferior insulation of the compressor before test operation
- Condition
- Applicable models
- Point of diagnosis
- Point of diagnosis
- Measure
- Cooling operation of specific indoor units is not good
- Condition
- Applicable models
- Point of diagnosis
- Measure
- Malfunction heating due to overcharge of refrigerant
- Condition
- Applicable models
- Point of diagnosis
- Measure
- High pressure shutdown occurs only when the std compressor starts
- Condition
- Applicable models
- Malfunction of transmission examples malfunction of transmission due to wiring next to the high voltage line for indoor unit
- Malfunction of transmission examples display of malfunction of transmission due to the elevator s power line
- Malfunction of transmission examples
- Malfunction of transmission examples faulty condition to multi core wire
- Malfunction of transmission examples faulty condition caused by the use of single core line
- Malfunction of transmission examples faulty condition caused by branch lines
- Part 2 installation manual
- Heat pump cooling only 50hz rx y q5 54p 14
- Heat pump 60hz rxyq5 54p 60
- System air conditioner
- Pn08043 2 em06a045
- Installation manual
- Heat pump cooling only 50hz rx y q5 54p
- Safety considerations
- First of all
- Disposal requirements
- Special notice of product
- Introduction
- Combination
- The following accessories are included the storage location of the accessories is shown in figure 1
- The capacities of outdoor units a b and c must fulfill the following conditions a b c
- Standard supplied accessories
- Note do not throw away any of the accessories until installation is complete
- 18 hp type
- 10 hp type 12 18 hp type
- 10 14 16 hp type
- Option accessory
- Note make sure that any separately purchased accessories are designed for use with r 410a
- Main components
- Installation process
- For main components and function of the main components refer to the engineering data book
- Figure 2 shows the installation process install in the order of the steps shown
- To install the outdoor units the following optional parts are also required to select an optimum kit refer to 6 refrigerant piping
- Technical and electrical specifications
- Refrigerant branching kit
- Refer to the engineering data book for the complete list of specifications
- Pipe size reducer
- Outdoor unit multi connection piping kit
- Selection of location
- Select a location for installation that meets the following conditions get the customer s permission 1 there is no danger of fire due to leakage of inflammable gas 2 select the location of the unit in such a way that neither the discharged air nor the sound generated by the unit disturb anyone 3 the foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 4 the piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length refer to 1 6 refrigerant piping 5 locations where the unit s suction vent and outlet vent do not generally face the wind wind blowing directly into the suction or outlet vents will interfere with the unit s operation if necessary install some kind of obstruction to block the wind 6 the space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is available see the installation space examples for the minimum space requirem
- Pattern 3
- Pattern 2
- Pattern 1
- No limit to wall height
- Installation space examples the installation space requirement shown in figure 3 is a reference for cooling operation when the outdoor temperature is 35 c if the design outdoor temperature exceeds 35 c or the heat load exceeds maximum capacity in all the outdoor unit take an even large space on the intake shown in figure 3 during installation install the units using the most appropriate of the patterns shown in figure 3 for the location in question taking into consideration human traffic and wind if the number of units installed is more than that shown in the pattern in figure 3 install the units so there are no short circuits as regards space in front of the unit consider the space needed for the local refrigerant piping when installing the units if the work conditions in figure 3 do not apply contact your dealer or daikin directly
- Installation manual
- Heat pump cooling only 50hz rx y q5 54p sien34 705
- Figure 3
- When installed in serial
- Service space of suction side
- Service space of front side
- Inspecting and handling the unit
- Placing the unit
- Use only pipes which are clean inside and outside and which do not accumulate harmful sulfur oxidants dirt cutting oils moisture or other contamination foreign materials inside pipes including oils for fabrication must be 30mg 10m or less use the following items for the refrigerant piping material jointless phosphor deoxidized copper pipe size see 1 6 5 example of connection to determine the correct size thickness select a thickness for the refrigerant piping which complies with national and local laws for r 410a the design pressure is 4 mpa 40 bar the minimum thickness of piping according to japan s high pressure gas safety law as of january 2003 is shown below temper grade o type 1 2h type in the table indicate the material types specified in jis h 3300
- Selection of piping material and refrigerant branching kit
- Refrigerant piping
- Protection against contamination when installing pipes
- Protect the piping to prevent moisture dirt dust etc from entering the piping
- Note exercise special caution to prevent dirt or dust when passing piping through holes in walls and when passing pipe edges to the exterior
- Note all field piping must be installed by a licensed refrigeration technician and must comply with relevant local and national regulations after piping work is complete do not under any circumstances open the shutoff valve until 1 7 field wiring and 1 10 checking of device and installation conditions are complete do not use flux when brazing the refrigerant piping use the phosphor copper brazing filler metal bcup 2 jis z 3264 b cu93p 710 795 iso 3677 which does not require flux flux has extremely harmful influence on refrigerant piping systems for instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains fluorine it will damage the refrigerant oil
- For piping work follow the maximum tolerated length difference in height and length after a branch indicated in the 1 6 5 example of connection a refrigerant branching kit sold separately is needed for piping branches and connection of piping between outdoor unit in case of multi system use only separately sold items selected specifically according to the refrigerant branch kit selection in the 1 6 5 example of connection
- Pipe connection
- Connecting the refrigerant piping
- Caution after removing the gas remove the pinch piping any gas remaining inside may blow off the pinch piping when you dissolve the brazing causing damage
- Shutoff valve liquid side gas side service port
- Removing pinch piping when connecting refrigerant piping to an outdoor unit remove the pinch piping refer to figure 13 pinch piping should be removed using the procedure in the figure 13
- Procedure 3 after removing the gas from the pinch piping dissolve the brazing using a burner and remove the pinch piping
- Procedure 2 connect a charge hose to the service port of the liquid side and gas side shutoff valves and remove the gas from the pinch piping
- Procedure 1 confirm the shutoff valve is closed
- Pinch piping
- Installation manual
- Heat pump cooling only 50hz rx y q5 54p sien34 705
- Figure 14
- Figure 13
- Processing the gas side accessory pipe 2 only in case of connecting at lateral side cut the gas side accessory pipe 2 referring the figure below
- The 5hp type cannot be used as an independent unit in a multi system the outdoor unit multi connection piping kit sold separately is needed when connecting piping between outdoor units refer to the installation manual that comes with the kit when doing this piping work
- Installation manual
- Heat pump cooling only 50hz rx y q5 54p sien34 705
- Figure 15
- Installation manual 231
- Sien34 705 heat pump cooling only 50hz rx y q5 54p
- Prohibited pattern
- Precautions when connecting piping between outdoor units in case of multi system the outdoor unit multi connection piping kit sold separately is needed to connect piping between outdoor units in multi system only proceed with piping work after considering the limitations on installation listed here and in 5 branching the refrigerant piping always referring to the kit s installation manual 1 the piping between outdoor units must be installed level pattern 1 or with a rise pattern 2 otherwise oil may pool in the pipes
- Pattern 2
- Pattern 1
- Prohibited pattern
- Installation manual
- If less than 2m
- If 2 m or more
- Heat pump cooling only 50hz rx y q5 54p sien34 705
- 3 if the piping length between the outdoor units exceeds 2 m create a rise of 200 mm or more in the gas line under a length of 2 m from the outdoor unit multi connection piping kit
- 2 to avoid the risk of oil detention in the stopping unit always connect the shutoff valve and the piping between outdoor units as shown in the figure a or figure b
- How to calculate the additional refrigerant to be charged
- Heat pump cooling only 50hz rx y q5 54p sien34 705
- Example refrigerant branch using refnet joint
- Example of connection
- Xample o
- Refrigerant branch kit selection
- Pipe size selection
- Onnectio
- Installation manual
- Sien34 705 heat pump cooling only 50hz rx y q5 54p
- Installation manual 235
- Example refrigerant branch using refnet joint and refnet header
- Example refrigerant branch using refnet header
- Note 3
- Note 2
- Note 1
- Main pipe and the pipes that are not increased
- Length of above pipes must be doubled except
- For calculation of total extension length the actual
- Diameter of above case
- Φ 38 φ 22
- Outdoor unit refnet joint a g
- Indoor units 1 8
- Gas liquid
- Field wiring
- Power circuit safety device and cable requirements
- Note the above table indicates power specifications for standard combinations see 1 2 introduction if using anything other than the above combinations in a multi system calculate using the following procedure minimum circuit amp value add the minimum circuit amp values for each independent unit recommended fuse capacity select the fuse capacity with the next higher value of the calculated minimum circuit amp multiplied by 1 ex combining the rxyq30py1 using rxyq8py1 rxyq10py1 and rxyq12py1 minimum circuit amp of the rxyq8py1 in table above 18 a minimum circuit amp of rxyq10py1 in table above 21 a minimum circuit amp of rxyq12py1 in table above 22 a accordingly the minimum circuit amp of the rxyq30py1 18 21 22 62 a multiplying the result above by 1 62 1 69 a so the recommended fuse capacity would be 70 a
- A power circuit see the following table must be provided for connection of the unit this circuit must be protected with the required safety devices i e a main switch a slow blow fuse on each phase and an earth leakage circuit breaker when using residual current operated circuit breakers be sure to use a high speed type 1 second or less 200ma rated residual operating current use copper conductors only use insulated wire for the power cord select the power supply cable type and size in accordance with relevant local and national regulations specifications for local wiring are in compliance with iec60245 use wire type h05vv when protected pipes are used use wire type h07rn f when protected pipes are not used
- Wiring connection example for whole system
- Leading wire procedure
- Transmission wiring connection procedure
- Referring to figure 21 22 connect the transmission wiring between outdoor unit and indoor unit outdoor unit and outdoor unit of other system outdoor unit and outdoor unit of same system only multi system or to cool heat selector except rxq p
- Heat pump cooling only 50hz rx y q5 54p sien34 705
- Figure 23
- Between outdoor unit and outdoor unit of same system only for multi system max wiring length 30 m 3 transmission wiring to cool heat selector max wiring length 500 m
- All transmission wiring is to be procured on site all wiring should use sheathed vinyl cord 0 5 1 5 m
- Or cable duplex triplex only for the cool heat selector transmission wiring about the symbol 1 3 see figure 21 22 should be done within the following limitations if they are exceeded transmission problems may occur 1 between outdoor unit and indoor unit between outdoor unit and outdoor unit of other systems max wiring length 1 000 m max total wiring length 2 000 m max no of branches 16 note no branch is allowed after branch see figure 23 max no of outdoor units of other system that can be connected 10
- Installation manual
- Power wiring connection procedure
- Sien34 705 heat pump cooling only 50hz rx y q5 54p
- Referring to figure 27 secure and wire the power and transmission wiring using the included clamp 1 2 and 3
- Procedure for wiring inside units
- Installation manual 245
- In case of 5 10hp type
- In case of 12 18hp type
- Figure 27
- Caution the transmission wiring must be at least 50 mm away from the power wiring make sure all wiring do not contact to the pipes hatching parts in the figure 27 after wiring work is completed check to make sure there are no loose connections among the electrical parts in the el compo box
- Referring to figure 28 connect an nitrogen tank refrigerant tank and a vacuum pump to the outdoor unit the refrigerant tank and the charge hose connection to refrigerant charge port or the valve a c in figure 28 are needed in 1 11 additional refrigerant charge and check operation the shutoff valve and valve a c in figure 28 should be open or closed as shown in the table below
- Preparations
- Note the airtightness test and vacuum drying should be done using the liquid side and gas side shutoff valve service ports see the r 410a label attached to the front plate of the outdoor unit for details on the location of the service port see figure at right see shutoff valve operation procedure in 1 11 1 before working for details on handling the shutoff valve the refrigerant charge port is connected to unit pipe when shipped the unit contains the refrigerant so use caution when attaching the charge hose
- Note always use nitrogen gas for the airtightness test absolutely do not open the shutoff valve until the main power circuit insulation measurement has been completed measuring after the shutoff valve is opened will cause the insulation value to drop
- Air tight test and vacuum drying
- Air tight test and vacuum drying method
- Pipe insulation
- Checking of device and installation conditions
- The outdoor unit is charged with refrigerant when shipped from the factory but depending on the size and length of the piping when installed it may require additional charging for charging the additional refrigerant follow the procedure in this chapter and then carry out the check operation
- Shutoff valve operation procedure when operating the shutoff valve follow the procedure instructed below
- Other tanks
- Note do not open the shutoff valve until 1 10 checking of device and installation conditions are completed if the shutoff valve is left open without turning on the power it may cause refrigerant to buildup in the compressor leading insulation degradation be sure to use the correct tools the shutoff valve is not a back seat type if forced it to open it might break the valve body when using a service port use the charge hose after tightening the cap make sure no refrigerant gas is leaking
- Liquid side shutoff valve
- Installation manual
- Hp type 8hp type 10hp type 12hp type 14hp type 16hp type 18hp type
- Heat pump cooling only 50hz rx y q5 54p sien34 705
- Gas side shutoff valve φ 15 φ 19
- Caution always use the proper refrigerant r 410a if charged with the refrigerant containing an improper material it may cause an explosion or accident r 410a is a mixed refrigerant so charging it as a gas will cause the refrigerant composition to change which may prevent normal operation
- Before working
- Φ 9 the 12hp type corresponds to the 12 diameter onsite piping using the included piping
- Additional refrigerant charge and check operation
- Φ 25 the 10hp type corresponds to the 22 diameter onsite piping using the accessory pipe the 12 18hp type corresponds to the 28 diameter onsite piping using the accessory pipe
- About the refrigerant tank check whether the tank has a siphon pipe before charging and place the tank so that the refrigerant is charged in liquid form see the figure below
- Φ 12 the 18hp type corresponds to the 15 diameter onsite piping using the accessory pipe
- With siphon pipe
- Tightening torque the sizes of the shutoff valves on each model and the tightening torque for each size are listed in the table below
- Warning electric shock warning make sure to close the el compo box lid before turning on the power when performing the refrigerant charging operation perform the setting on the pc board a1p of the outdoor unit and check the led display after the power is on via the inspection door which is in the el compo box lid use an insulated rod to operate the push buttons via the el compo box s inspection door there is a risk of electric shock if you touch any live parts since this operation must be performed with the power on
- Procedure of adding refrigerant charging and check operation
- Note press the mode button bs1 if you get confused while operating this returns to setting mode 1 default
- Note if operation is performed within 12 minutes after the indoor and outdoor units are turned on h2p will be lit on and the compressor will not operate in order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting operating this is not a malfunction
- How to check how many units are connected it is possible to find out how many indoor or outdoor unit in the system are turned on by operating the push button on the pc board a1p of outdoor unit in case of multi system master unit follow the procedure below to check how many indoor or outdoor units are turned on
- Caution make sure to use the protect tool protective groves and goggles when charging the refrigerant due to a danger of liquid hammer the refrigerant must not be charged over the allowable maximum amount when charging the refrigerant do not perform the refrigerant charging operation under working for the indoor unit when opening the front panel make sure to take caution to the fan rotation during the working after the outdoor unit stops operating the fan may keep rotation for a while
- Refrigerant charging operation procedure 1 open the liquid and gas side shutoff valves the valve a c must be closed the valve a c means the valves in the figure 33
- Perform the refrigerant charging operation following refrigerant charging operation procedure as shown below and charge the remaining refrigerant of the additional charging amount for performing the refrigerant charging operation the push button on the pc board a1p of outdoor unit incase of multi system master unit are use see the figure 32 in addition the refrigerant are charged from the refrigerant charge port via the valve a see the figure 33 for operating the push button and opening and closing the valve follow the work procedure
- Note the refrigerant will be charged about 22kg in one hour at outdoor temp 30 c db 6kg at 0 c db if you need to speedup in case of multi system connect the refrigerant tanks to each outdoor unit as shown in the figure 33
- Led display 3 off 4 on 5 blinking how to distinguish the master unit sub unit 1 and sub unit 2 in the multi system
- Display of normal system
- Remote control displays malfunction code
- Method 2 by the transmission wiring to indoor unit
- Method 1 by the h8p multi led display
- Led display 3 off 4 on 5 blinking how to distinguish the master unit sub unit 1 and sub unit 2 in the multi system
- If any malfunction codes other than the above are displayed check the service manual for how to respond
- 4 make the onsite settings as needed using the push button bs1 bs5 on the outdoor unit pc board a1p with the power on see 1 12 2 onsite settings with the power on 5 perform the check operation following the check operation method of the service precautions label on the el compo box lid the system operation for about 40 minutes and automatically stops the check operation if the malfunction code is not displayed in the remote control after the system stop check operation is completed normal operation will be possible after 5 minutes if the malfunction code is displayed in the remote control correct the malfunction following remote control displays malfunction code and perform the check operation again
- 3 check the led display on the outdoor unit pc board a1p is as shown in the table below and transmission is normal
- Onsite settings with the power on
- Onsite settings with the power off
- Onsite settings
- Test run
- Checks after test run
- Before test run
- Caution for refrigerant leaks
- Installation manual
- Heat pump 60hz rxyq5 54p
- System air conditioner
- P171361 7j em06a035
- Safety considerations
- First of all
- Special notice of product
- Disposal requirements
- Introduction
- Combination
- Pipe size reducer
- Outdoor unit multi connection piping kit
- Option accessory
- Note make sure that any separately purchased accessories are designed for use with r 410a
- Note do not throw away any of the accessories until installation is complete
- 18 hp type
- 10 hp type 12 18 hp type
- 10 14 16 hp type
- To install the outdoor units the following optional parts are also required to select an optimum kit refer to 2 6 refrigerant piping
- The following accessories are included the storage location of the accessories is shown in figure 1
- Standard supplied accessories
- Refrigerant branching kit
- Technical and electrical specifications
- Refer to the engineering data book for the complete list of specifications
- Main components
- Installation process
- Installation manual
- Heat pump 60hz rxyq5 54p sien34 705
- For main components and function of the main components refer to the engineering data book
- Figure 2 shows the installation process install in the order of the steps shown
- No limit to wall height
- Installation space examples the installation space requirement shown in figure 3 is a reference for cooling operation when the outdoor temperature is 35 c if the design outdoor temperature exceeds 35 c or the heat load exceeds maximum capacity in all the outdoor unit take an even large space on the intake shown in figure 3 during installation install the units using the most appropriate of the patterns shown in figure 3 for the location in question taking into consideration human traffic and wind if the number of units installed is more than that shown in the pattern in figure 3 install the units so there are no short circuits as regards space in front of the unit consider the space needed for the local refrigerant piping when installing the units if the work conditions in figure 3 do not apply contact your dealer or daikin directly
- Installation manual 269
- Figure 3
- When installed in serial
- Sien34 705 heat pump 60hz rxyq5 54p
- Service space of suction side
- Service space of front side
- Selection of location
- Select a location for installation that meets the following conditions get the customer s permission 1 there is no danger of fire due to leakage of inflammable gas 2 select the location of the unit in such a way that neither the discharged air nor the sound generated by the unit disturb anyone 3 the foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 4 the piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length refer to 2 6 refrigerant piping 5 locations where the unit s suction vent and outlet vent do not generally face the wind wind blowing directly into the suction or outlet vents will interfere with the unit s operation if necessary install some kind of obstruction to block the wind 6 the space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is available see the installation space examples for the minimum space requirem
- Pattern 3
- Pattern 2
- Pattern 1
- Inspecting and handling the unit
- Placing the unit
- Protection against contamination when installing pipes
- Protect the piping to prevent moisture dirt dust etc from entering the piping
- Note exercise special caution to prevent dirt or dust when passing piping through holes in walls and when passing pipe edges to the exterior
- Note all field piping must be installed by a licensed refrigeration technician and must comply with relevant local and national regulations after piping work is complete do not under any circumstances open the shutoff valve until 2 7 field wiring and 2 10 checking of device and installation conditions are complete do not use flux when brazing the refrigerant piping use the phosphor copper brazing filler metal bcup 2 jis z 3264 b cu93p 710 795 iso 3677 which does not require flux flux has extremely harmful influence on refrigerant piping systems for instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains fluorine it will damage the refrigerant oil
- For piping work follow the maximum tolerated length difference in height and length after a branch indicated in the 2 6 5 example of connection a refrigerant branching kit sold separately is needed for piping branches and connection of piping between outdoor unit in case of multi system use only separately sold items selected specifically according to the refrigerant branch kit selection in the 2 6 5 example of connection
- Use only pipes which are clean inside and outside and which do not accumulate harmful sulfur oxidants dirt cutting oils moisture or other contamination foreign materials inside pipes including oils for fabrication must be 30mg 10m or less use the following items for the refrigerant piping material jointless phosphor deoxidized copper pipe size see 2 6 5 example of connection to determine the correct size thickness select a thickness for the refrigerant piping which complies with national and local laws for r 410a the design pressure is 4 mpa 40 bar the minimum thickness of piping according to japan s high pressure gas safety law as of january 2003 is shown below temper grade o type 1 2h type in the table indicate the material types specified in jis h 3300
- Selection of piping material and refrigerant branching kit
- Refrigerant piping
- Pipe connection
- Connecting the refrigerant piping
- Sien34 705 heat pump 60hz rxyq5 54p
- Shutoff valve liquid side gas side service port
- Removing pinch piping when connecting refrigerant piping to an outdoor unit remove the pinch piping refer to figure 13 pinch piping should be removed using the procedure in the figure 13
- Procedure 3 after removing the gas from the pinch piping dissolve the brazing using a burner and remove the pinch piping
- Procedure 2 connect a charge hose to the service port of the liquid side and gas side shutoff valves and remove the gas from the pinch piping
- Procedure 1 confirm the shutoff valve is closed
- Pinch piping
- Installation manual 275
- Figure 14
- Figure 13
- Caution after removing the gas remove the pinch piping any gas remaining inside may blow off the pinch piping when you dissolve the brazing causing damage
- Processing the gas side accessory pipe 2 only in case of connecting at lateral side cut the gas side accessory pipe 2 referring the figure below
- When connecting the piping on site be sure to use the accessory piping make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit
- The 5hp type cannot be used as an independent unit in a multi system the outdoor unit multi connection piping kit sold separately is needed when connecting piping between outdoor units refer to the installation manual that comes with the kit when doing this piping work
- Sien34 705 heat pump 60hz rxyq5 54p
- Installation manual 277
- Figure 15
- Prohibited pattern
- Precautions when connecting piping between outdoor units in case of multi system the outdoor unit multi connection piping kit sold separately is needed to connect piping between outdoor units in multi system only proceed with piping work after considering the limitations on installation listed here and in 5 branching the refrigerant piping always referring to the kit s installation manual 1 the piping between outdoor units must be installed level pattern 1 or with a rise pattern 2 otherwise oil may pool in the pipes
- Pattern 2
- Pattern 1
- Installation manual
- Heat pump 60hz rxyq5 54p sien34 705
- If less than 2m
- If 2 m or more
- 3 if the piping length between the outdoor units exceeds 2 m create a rise of 200 mm or more in the gas line under a length of 2 m from the outdoor unit multi connection piping kit
- 2 to avoid the risk of oil detention in the stopping unit always connect the shutoff valve and the piping between outdoor units as shown in the figure a or figure b
- Sien34 705 heat pump 60hz rxyq5 54p
- Prohibited pattern
- Installation manual 279
- Xample o
- Refrigerant branch kit selection
- Pipe size selection
- Onnectio
- Installation manual
- How to calculate the additional refrigerant to be charged
- Heat pump 60hz rxyq5 54p sien34 705
- Example refrigerant branch using refnet joint
- Example of connection
- Sien34 705 heat pump 60hz rxyq5 54p
- Installation manual 283
- Example refrigerant branch using refnet joint and refnet header
- Example refrigerant branch using refnet header
- Note 3
- Note 2
- Note 1
- Main pipe and the pipes that are not increased
- Length of above pipes must be doubled except
- For calculation of total extension length the actual
- Diameter of above case
- Φ 38 φ 22
- Outdoor unit refnet joint a g
- Indoor units 1 8
- Gas liquid
- F 2 g 2
- Field wiring
- Power circuit safety device and cable requirements
- Note the above table indicates power specifications for standard combinations see 2 2 introduction if using anything other than the above combinations in a multi system calculate using the following procedure minimum circuit amp value add the minimum circuit amp values for each independent unit recommended fuse capacity select the fuse capacity with the next higher value of the calculated minimum circuit amp multiplied by 1 ex combining the rxyq30pyl using rxyq8pyl rxyq10pyl and rxyq12pyl minimum circuit amp of the rxyq8pyl in table above 18 a minimum circuit amp of rxyq10pyl in table above 22 a minimum circuit amp of rxyq12pyl in table above 23 a accordingly the minimum circuit amp of the rxyq30pyl 18 22 23 65 a multiplying the result above by 1 65 1 71 a so the recommended fuse capacity would be 80 a
- A power circuit see the following table must be provided for connection of the unit this circuit must be protected with the required safety devices i e a main switch a slow blow fuse on each phase and an earth leakage circuit breaker when using residual current operated circuit breakers be sure to use a high speed type 1 second or less 200ma rated residual operating current use copper conductors only use insulated wire for the power cord select the power supply cable type and size in accordance with relevant local and national regulations specifications for local wiring are in compliance with iec60245 use wire type h05vv when protected pipes are used use wire type h07rn f when protected pipes are not used
- Wiring connection example for whole system
- Leading wire procedure
- Transmission wiring connection procedure
- Referring to figure 21 22 connect the transmission wiring between outdoor unit and indoor unit outdoor unit and outdoor unit of other system outdoor unit and outdoor unit of same system only multi system or to cool heat selector
- Installation manual
- Heat pump 60hz rxyq5 54p sien34 705
- Figure 23
- Between outdoor unit and outdoor unit of same system only for multi system max wiring length 30 m 3 transmission wiring to cool heat selector max wiring length 500 m
- All transmission wiring is to be procured on site all wiring should use sheathed vinyl cord 0 5 1 5 mm2 or cable duplex triplex only for the cool heat selector transmission wiring about the symbol 1 3 see figure 21 22 should be done within the following limitations if they are exceeded transmission problems may occur 1 between outdoor unit and indoor unit between outdoor unit and outdoor unit of other systems max wiring length 1 000 m max total wiring length 2 000 m max no of branches 16 note no branch is allowed after branch see figure 23 max no of outdoor units of other system that can be connected 10
- Power wiring connection procedure
- Procedure for wiring inside units
- Installation manual 293
- In case of 5 10hp type
- In case of 12 18hp type
- Figure 27
- Caution the transmission wiring must be at least 50 mm away from the power wiring make sure all wiring do not contact to the pipes hatching parts in the figure 27 after wiring work is completed check to make sure there are no loose connections among the electrical parts in the el compo box
- Sien34 705 heat pump 60hz rxyq5 54p
- Referring to figure 27 secure and wire the power and transmission wiring using the included clamp 1 2 and 3
- Referring to figure 28 connect an nitrogen tank refrigerant tank and a vacuum pump to the outdoor unit the refrigerant tank and the charge hose connection to refrigerant charge port or the valve a c in figure 28 are needed in 2 11 additional refrigerant charge and check operation the shutoff valve and valve a c in figure 28 should be open or closed as shown in the table below
- Preparations
- Note the airtightness test and vacuum drying should be done using the liquid side and gas side shutoff valve service ports see the r 410a label attached to the front plate of the outdoor unit for details on the location of the service port see figure at right see shutoff valve operation procedure in 2 11 1 before working for details on handling the shutoff valve the refrigerant charge port is connected to unit pipe when shipped the unit contains the refrigerant so use caution when attaching the charge hose
- Note always use nitrogen gas for the airtightness test absolutely do not open the shutoff valve until the main power circuit insulation measurement has been completed measuring after the shutoff valve is opened will cause the insulation value to drop
- Air tight test and vacuum drying
- Air tight test and vacuum drying method
- Pipe insulation
- Checking of device and installation conditions
- Heat pump 60hz rxyq5 54p sien34 705
- Gas side shutoff valve φ 15 φ 19
- Caution always use the proper refrigerant r 410a if charged with the refrigerant containing an improper material it may cause an explosion or accident r 410a is a mixed refrigerant so charging it as a gas will cause the refrigerant composition to change which may prevent normal operation
- Before working
- Additional refrigerant charge and check operation
- About the refrigerant tank check whether the tank has a siphon pipe before charging and place the tank so that the refrigerant is charged in liquid form see the figure below
- Φ 9 the 12hp type corresponds to the 12 diameter onsite piping using the included piping
- Φ 25 the 10hp type corresponds to the 22 diameter onsite piping using the accessory pipe the 12 18hp type corresponds to the 28 diameter onsite piping using the accessory pipe
- Φ 12 the 18hp type corresponds to the 15 diameter onsite piping using the accessory pipe
- With siphon pipe
- The outdoor unit is charged with refrigerant when shipped from the factory but depending on the size and length of the piping when installed it may require additional charging for charging the additional refrigerant follow the procedure in this chapter and then carry out the check operation
- Shutoff valve operation procedure when operating the shutoff valve follow the procedure instructed below
- Other tanks
- Note do not open the shutoff valve until 2 10 checking of device and installation conditions are completed if the shutoff valve is left open without turning on the power it may cause refrigerant to buildup in the compressor leading insulation degradation be sure to use the correct tools the shutoff valve is not a back seat type if forced it to open it might break the valve body when using a service port use the charge hose after tightening the cap make sure no refrigerant gas is leaking
- Liquid side shutoff valve
- Installation manual
- Hp type 8hp type 10hp type 12hp type 14hp type 16hp type 18hp type
- Procedure of adding refrigerant charging and check operation
- Note press the mode button bs1 if you get confused while operating this returns to setting mode 1 default
- Note if operation is performed within 12 minutes after the indoor and outdoor units are turned on h2p will be lit on and the compressor will not operate in order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting operating this is not a malfunction
- How to check how many units are connected it is possible to find out how many indoor or outdoor unit in the system are turned on by operating the push button on the pc board a1p of outdoor unit in case of multi system master unit follow the procedure below to check how many indoor or outdoor units are turned on
- Caution make sure to use the protect tool protective groves and goggles when charging the refrigerant due to a danger of liquid hammer the refrigerant must not be charged over the allowable maximum amount when charging the refrigerant do not perform the refrigerant charging operation under working for the indoor unit when opening the front panel make sure to take caution to the fan rotation during the working after the outdoor unit stops operating the fan may keep rotation for a while
- Warning electric shock warning make sure to close the el compo box lid before turning on the power when performing the refrigerant charging operation perform the setting on the pc board a1p of the outdoor unit and check the led display after the power is on via the inspection door which is in the el compo box lid use an insulated rod to operate the push buttons via the el compo box s inspection door there is a risk of electric shock if you touch any live parts since this operation must be performed with the power on
- Refrigerant charging operation procedure 1 open the liquid and gas side shutoff valves the valve a c must be closed the valve a c means the valves in the figure 33
- Perform the refrigerant charging operation following refrigerant charging operation procedure as shown below and charge the remaining refrigerant of the additional charging amount for performing the refrigerant charging operation the push button on the pc board a1p of outdoor unit incase of multi system master unit are use see the figure 32 in addition the refrigerant are charged from the refrigerant charge port via the valve a see the figure 33 for operating the push button and opening and closing the valve follow the work procedure
- Note the refrigerant will be charged about 22kg in one hour at outdoor temp 30 c db 6kg at 0 c db if you need to speedup in case of multi system connect the refrigerant tanks to each outdoor unit as shown in the figure 33
- Led display 3 off 4 on 5 blinking how to distinguish the master unit sub unit 1 and sub unit 2 in the multi system
- Display of normal system
- Remote control displays malfunction code
- Method 2 by the transmission wiring to indoor unit
- Method 1 by the h8p multi led display
- Led display 3 off 4 on 5 blinking how to distinguish the master unit sub unit 1 and sub unit 2 in the multi system
- If any malfunction codes other than the above are displayed check the service manual for how to respond
- 4 make the onsite settings as needed using the push button bs1 bs5 on the outdoor unit pc board a1p with the power on see 2 12 2 onsite settings with the power on 5 perform the check operation following the check operation method of the service precautions label on the el compo box lid the system operation for about 40 minutes and automatically stops the check operation if the malfunction code is not displayed in the remote control after the system stop check operation is completed normal operation will be possible after 5 minutes if the malfunction code is displayed in the remote control correct the malfunction following remote control displays malfunction code and perform the check operation again
- 3 check the led display on the outdoor unit pc board a1p is as shown in the table below and transmission is normal
- Onsite settings with the power on
- Onsite settings with the power off
- Onsite settings
- Test run
- Checks after test run
- Before test run
- Caution for refrigerant leaks
- Part 3 operation manual
- Heat pump cooling only 50hz rx y q5 54p 10
- Heat pump 60hz rxyq5 54p 21
- System air conditioner
- Pn08043 1 em06a044
- Operation manual
- Heat pump cooling only 50hz rx y q5 54p
- Sien34 705 operation manual
- Operation manual 311
- 1 safety cautions
- Operation manual sien34 705
- 2 specifications
- Operation manual
- 1 initial refrigerant charge
- Names and functions of parts refer to figure 1
- Inverter series
- Inlet air outlet air
- Inlet air
- Indoor unit
- Heat pumps rxyq series yes no
- Figure 1 shows system with cool heat selector
- Figure 1
- Wrong cleaning may make the plastics parts broken or cause fail ure of water leakage or electric shock do not touch the air inlet or aluminium fin of the air condi tioner otherwise injury may be caused do not place objects in direct proximity of the outdoor unit and do not let leaves and other debris accumulate around the unit leaves are a hotbed for small animals which can enter the unit once in the unit such animals can cause malfunctions smoke or fire when making contact with electrical parts
- Cooling only rxq series
- This operation manual is for the following system with standard con trol before initiating operation contact your daikin dealer for the operation that corresponds to your system type and mark if your installation has a customized control system ask your daikin dealer for the operation that corresponds to your system
- Cool heat selector operation modes
- Single unit
- Cool heat selector except rxq series
- Outlet air
- Combination unit
- Outdoor units refer to figure 1
- About the specifications see single unit according to the indepen dent unit
- Outdoor unit
- 3 what to do before operation
- Sien34 705 operation manual
- Operation manual 313
- Figure 3
- Figure 2
- 5 operation range
- 4 remote control and cool heat selector name and function of each switch and display refer to figure 2 and 3
- 4 remote control and cool heat selector name and function of each switch and dis play refer to figure 2 and 3
- Figure 4
- 6 operation procedure
- 6 1 cooling heating and fan only operation
- Operation manual sien34 705
- Operation manual
- Figure 7
- Sien34 705 operation manual
- Operation manual 315
- Figure 8
- Figure 6
- Figure 5
- 6 3 adjusting the air flow direction refer to figure 6 only for double flow multi flow corner ceil ing suspended and wall mounted
- 6 2 program dry operation
- Figure 9
- Figure 13
- Figure 11
- Figure 10
- 6 5 setting the master remote control except rxq series refer to figure 10
- 6 4 programming start and stop of the system with timer refer to figure 9
- Refer to figure 13
- Operation manual sien34 705
- Operation manual
- Sien34 705 operation manual
- Operation manual 317
- Figure 14
- 9 following symptoms are not air conditioner troubles
- 9 2 it stops sometimes
- 9 1 the system does not operate
- 8 seasonal maintenance
- 8 2 at the end of the season
- 8 1 at the beginning of the season
- 7 optimum operation
- 6 6 precautions for group control system or two remote control control system
- 9 11 the outdoor unit fan does not spin
- Operation manual sien34 705
- 9 10 the units can give off odours
- Operation manual
- 9 9 dust comes out of the unit
- 9 8 noise of air conditioners
- 9 7 white mist comes out of a unit
- 9 6 the fan direction does not correspond to the setting
- 9 5 the fan strength does not correspond to the set ting
- 9 4 fan operation is possible but cooling and heat ing do not work
- 9 3 cool heat cannot be changed over
- 9 17 does not cool very well
- 9 16 hot air is emitted even though the unit is stopped
- 9 15 it stops sometimes
- 9 14 the inside of an outdoor unit is warm even when the unit has stopped
- 9 13 the compressor or fan in the outdoor unit does not stop
- 9 12 the display shows
- 10 trouble shooting
- Trip po s ition bre a ker
- Sien34 705 operation manual
- S witch on
- Operation manual 319
- Figure 12
- After sales service and warranty
- Operation manual sien34 705
- Operation manual
- System air conditioner
- P171361 6j em06a034
- Operation manual
- Heat pump 60hz rxyq5 54p
- Operation manual sien34 705
- Operation manual
- 1 safety cautions
- 1 initial refrigerant charge combination unit
- Names and functions of parts refer to figure 1
- Inverter series
- Inlet air outlet air
- Inlet air
- Indoor unit
- Heat pumps rxyq series yes no
- Figure 2
- Figure 1 shows system with cool heat selector
- Wrong cleaning may make the plastics parts broken or cause fail ure of water leakage or electric shock do not touch the air inlet or aluminium fin of the air condi tioner otherwise injury may be caused do not place objects in direct proximity of the outdoor unit and do not let leaves and other debris accumulate around the unit leaves are a hotbed for small animals which can enter the unit once in the unit such animals can cause malfunctions smoke or fire when making contact with electrical parts
- Figure 1
- This operation manual is for the following system with standard con trol before initiating operation contact your daikin dealer for the operation that corresponds to your system type and mark if your installation has a customized control system ask your daikin dealer for the operation that corresponds to your system
- Cool heat selector operation modes
- Single unit
- Cool heat selector
- About the specifications see single unit according to the indepen dent unit 2 there is the case that rxyq16pyl or rxyq18pyl is composed of single unit
- Sien34 705 operation manual
- 4 remote control and cool heat selector name and function of each switch and display refer to figure 2 and 3
- Outlet air
- 4 remote control and cool heat selector name and function of each switch and dis play refer to figure 2 and 3
- Outdoor units refer to figure 1
- 3 what to do before operation
- Outdoor unit
- 2 specifications
- Operation manual 323
- Operation manual sien34 705
- Operation manual
- Figure 3
- 6 operation procedure
- 6 1 cooling heating and fan only operation
- 5 operation range
- Figure 7
- Figure 4
- Sien34 705 operation manual
- Operation manual 325
- Operation manual sien34 705
- Operation manual
- Figure 8
- Figure 6
- Figure 5
- 6 3 adjusting the air flow direction
- 6 2 program dry operation
- Operation manual 327
- Figure 9
- Figure 13
- Figure 11
- Figure 10
- 6 5 setting the master remote control refer to figure 10
- 6 4 programming start and stop of the system with timer refer to figure 9
- Sien34 705 operation manual
- Refer to figure 13
- Operation manual sien34 705
- Operation manual
- Figure 14
- 9 following symptoms are not air conditioner troubles
- 9 2 it stops sometimes
- 9 1 the system does not operate
- 8 seasonal maintenance
- 8 2 at the end of the season
- 8 1 at the beginning of the season
- 7 optimum operation
- 6 6 precautions for group control system or two remote control control system
- 9 12 the display shows
- 9 11 the outdoor unit fan does not spin
- Sien34 705 operation manual
- 9 10 the units can give off odours
- Operation manual 329
- 9 9 dust comes out of the unit
- 9 8 noise of air conditioners
- 9 7 white mist comes out of a unit
- 9 6 the fan direction does not correspond to the setting
- 9 5 the fan strength does not correspond to the set ting
- 9 4 fan operation is possible but cooling and heat ing do not work
- 9 3 cool heat cannot be changed over
- 9 17 does not cool very well
- 9 16 hot air is emitted even though the unit is stopped
- 9 15 it stops sometimes
- 9 14 the inside of an outdoor unit is warm even when the unit has stopped
- 9 13 the compressor or fan in the outdoor unit does not stop
- After sales service and warranty
- 10 trouble shooting
- Trip po s ition bre a ker
- S witch on
- Operation manual sien34 705
- Operation manual
- Figure 12
- Sien34 705 operation manual
- Operation manual 331
- Precautions for new refrigerant r 410a 34
- Precautions for new refrigerant r 410a
- Part 4 precautions for new refrigerant r 410a
- Part 4
- Precautions for new refrigerant r 410a
- Outline
- H 1 non azeotropic mixture refrigerant mixture of two or more refrigerants having different boiling points h 2 quasi azeotropic mixture refrigerant mixture of two or more refrigerants having similar boiling points h 3 the design pressure is different at each product please refer to the installation manual for each product reference 1 mpa 10 9716 kgf c
- Characteristics of new refrigerant r 410a 1 performance almost the same performance as r 22 and r 407c 2 pressure working pressure is approx 1 times more than r 22 and r 407c 3 refrigerant composition few problems in composition control since it is a quasi azeotropic mixture refrigerant
- About refrigerant r 410a
- Thermodynamic characteristic of r 410a
- Sien34 705 precautions for new refrigerant r 410a
- Precautions for new refrigerant r 410a 335
- Refrigerant cylinders
- Ve up r 407c
- Tool compatibility
- Thickness t mm 0 0 0 1 1 1 1 1 1 1 1
- Service tools
- R 410a is used under higher working pressure compared to previous refrigerants r 22 r 407c furthermore the refrigerating machine oil has been changed from suniso oil to ether oil and if oil mixing is occurred sludge results in the refrigerants and causes other problems therefore gauge manifolds and charge hoses that are used with a previous refrigerant r 22 r 407c can not be used for products that use new refrigerants be sure to use dedicated tools and devices
- Pipe size
- O soft annealed h hard drawn
- O o o o o 1 2h 1 2h 1 2h 1 2h 1 2h 1 2h
- O o o o 1 2h 1 2h 1 2h 1 2h 1 2h 1 2h 1 2h
- Material
- Copper tube material and thickness
- As for the charge mouthpiece and packing 1 2unf20 is necessary for mouthpiece size of charge hose
- Φ 6 φ 9 φ 12 φ 15 φ 19 φ 22 φ 25 φ 28 φ 31 φ 38 φ 44
- Ve up r 410a
- Unit mm
- Specifications 2 dimension a
- Flaring tool
- Differences 2 change of dimension a
- Conventional flaring tools can be used when the work process is changed change of work process previously a pipe extension margin of 0 to 0 mm was provided for flaring for r 410a air conditioners perform pipe flaring with a pipe extension margin of 1 to 1 mm for clutch type only conventional tool with pipe extension margin adjustment can be used
- Can not be used
- Symbols
- Drawings flow charts
- Ésien34 705æëí
- Naamloze vennootschap zandvoordestraat 300 b 8400 oostende belgium www daikin eu btw be 0412 120 336 rpr oostende
Похожие устройства
-
Daikin FXSQ125A2VEBРуководство по запуску и установке -
Daikin FXSQ100A2VEBРуководство по инсталляции -
Daikin FXSQ80A2VEBИнструкция по монтажу -
Daikin FXSQ63A2VEBРуководство по монтажу -
Daikin FXSQ50A2VEBИнструкция по монтажу -
Daikin FXSQ40A2VEBИнструкция по монтажу -
Daikin FXSQ32A2VEBИнструкция по установке -
Daikin FXSQ25A2VEBИнструкция по установке -
Daikin FXSQ20A2VEBРуководство по инсталляции -
Daikin FXSQ15A2VEBИнструкция по монтажу -
Daikin RXYQ54PYLСервис мануал -
Daikin RXYQ52PYLСервис мануал