Daikin RXQ14PAY1 [375/398] How to calculate the additional refrigerant to be charged

Daikin RXQ14PAY1 [375/398] How to calculate the additional refrigerant to be charged
Example of Connection (R-410A Type) Si34-804
364 Appendix
a
How to calculate the additional
refrigerant to be charged
Additional refrigerant to be charged : R (kg)
(R should be rounded off in units of 0.1 kg.)
Example for refrigerant branch using REFNET joint and REFNET header for the systems and each pipe length as shown below.
Outdoor system : RXQ34P~
Total capacity of indoor unit : 116%
a : φ19.1 × 30m
b : φ15.9 × 10m
c : φ9.5 × 10m
d : φ9.5 × 10m
e : φ9.5 × 10m
f : φ9.5 × 10m
g : φ6.4 × 10m
h : φ6.4 × 20m
i : φ12.7 × 10m
j : φ6.4 × 10m
k : φ6.4 × 9m
MODEL NAME
THE AMOUNT OF
REFRIGERANT
RXQ5P
RXQ8 ~ 12P
RXQ14 ~ 22P
RXQ24 ~ 30P
RXQ32 ~ 38P
RXQ40 ~ 48P
RXQ50 ~ 54P
0kg
0.5kg
1.0kg
1.5kg
2.0kg
2.5kg
3.0kg
TABLE B
INDOOR CONNECTION
CAPACITY [X]
X 100%
100% < X 120%
120% < X 130%
130% < X 140%
140% < X 150%
150% < X 160%
160% < X 170%
170% < X 180%
180% < X 190%
190% < X 200%
5P~8P 12P~14P
18P~22P 24P~28P 30P~32P 42P~44P 46P~48P 52P~54P10P 16P 34P 36P 38P 40P 50P
0.5kg
0.5kg
0.5kg
0.5kg
1.0kg
1.0kg
1.0kg
1.5kg 2.0kg
2.5kg
2.5kg
3.0kg
3.5kg
0.5kg 1.0kg 1.5kg 2.0kg 2.5kg
0.5kg
0.5kg
1.0kg 1.5kg
1.0kg 2.0kg 4.0kg1.5kg 2.5kg 3.0kg 3.5kg
1.5kg 2.0kg 2.5kg 3.0kg
1.5kg 2.0kg
0.5kg 1.0kg
1.0kg 1.5kg 2.0kg
0kg
0.5kg
TABLE A
R =
( 30 × 0.26 + 10 × 0.18 + 10 × 0.12 + 40 × 0.059 + 49 × 0.022 )+ 2.0 + 0.5
abi
RXQ34P~ 116%
= 16.738 16.7kg
Round off units of 0.1 kg.
c+d+e+f g+h+i+j+k
Note 1
When the equivalent pipe length between outdoor and indoor
units is 90m or more, the size of main pipes (both gas-side and
liquid-side) must be increased.
Depending on the length of the piping, the capacity may drop, but
even in such case it is able to increase the size of main pipes.
Note 2
Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to 90 m if all the following conditions are satisfied. (In case of “ Branch with REFNET joint ” )
Note 3
If the pipe size above the REFNET header is φ34.9 or more, KHRP26M73HP is required.
Diameter of above case
Model
Gas Liquid
RXQ5 Type φ19.1
Not Increased
RXQ8 Type φ22.2 φ12.7
RXQ10 Type φ25.4* φ12.7
RXQ12 Type
Not Increased
φ15.9
RXQ14 Type
Not Increased
φ15.9
RXQ16 Type φ31.8* φ15.9
*If available on the site, use this size.
Otherwise, it can not be increased.
*If available on the site, use
this size.
Otherwise it can not be
increased.
Required Conditions Example Drawings
1.It is necessary to increase the pipe size between the first branch kit and the final
branch kit. (Reducers must be procured on site)
However, the pipes that are same pipe size with main pipe must not be increased.
4.The difference between
[Outdoor unit to the farthest indoor unit] and [Outdoor unit to the nearest indoor unit]
40 m
2.For calculation of Total extension length, the actual length of above pipes must be
doubled. (except main pipe and the pipes that are not increased)
3.Indoor unit to the nearest branch kit 40 m
8 b+c+d+e+f+g+p 90 m
increase the pipe size of b, c, d, e, f, g
a+b×2+c×2+d×2+e×2+f×2+g×2
+h+i+j+k+l+m+n+p 1000 m
h, i, j....... p 40 m
The farthest indoor unit 8
The nearest indoor unit 1
(a+b+c+d+e+f+g+p)-(a+h) 40 m
Increase the pipe size as follows
φ 9.5 → φ12.7
φ12.7 → φ15.9
φ15.9 → φ19.1
φ19.1 → φ22.2
φ22.2 → φ25.4*
φ28.6 → φ31.8*
φ34.9 → φ38.1*
RXQ18 Type φ31.8* φ19.1
Model
Gas Liquid
RXQ20 Type φ31.8* φ19.1
RXQ22 Type φ31.8* φ19.1
RXQ24 Type
Not Increased
φ19.1
RXQ26 Type φ38.1* φ22.2
RXQ28 Type φ38.1* φ22.2
RXQ30 Type φ38.1* φ22.2
RXQ32 Type φ38.1* φ22.2
Model
Gas Liquid
RXQ34 Type φ38.1* φ22.2
RXQ36 Type
Not Increased
φ22.2
RXQ38 Type
Not Increased
φ22.2
RXQ40 Type
Not Increased
φ22.2
RXQ42 Type
Not Increased
φ22.2
RXQ44 Type
Not Increased
φ22.2
RXQ46 Type
Not Increased
φ22.2
Model
Gas Liquid
RXQ48 Type
Not Increased
φ22.2
RXQ50 Type
Not Increased
φ22.2
RXQ52 Type
Not Increased
φ22.2
RXQ54 Type
Not Increased
φ22.2
a
ABCDEFG
bcdef
g
hi j kl mn
1234567
8
H1
p
Outdoor unit
REFNET joint (A-G)
Indoor units ( 1 - 8 )
R =
REFRIGERANT
AMOUNT FOR
HEAT PUMP SYSTEM
TABLE A
REFRIGERANT AMOUNT
FOR EXCEEDING CONNECTION
CAPACITY OF INDOOR UNIT
TABLE B
Total length(m) of liquid
piping size at φ22.2
0.37
Total length(m) of liquid
piping size at φ19.1
0.26
Total length(m) of liquid
piping size at φ15.9
0.18
Total length(m) of liquid
piping size at φ12.7
0.12
Total length(m) of liquid
piping size at φ9.5
0.059
Total length(m) of liquid
piping size at φ6.4
0.022
MODEL NAME [RXQ ~ P]
Outdoor unit
Main pipes
Increase
The first refrigerant branch kit
Indoor unit