Si34-803_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 264
The resistors among
U, V, and W are unbalanced or
short-circuited.
YES
NO
Replace the fan motor.
Replace the fan motor.
*1. Measurement of power wire connector.
Remove the X1A connector from the fan PCB (A2P) and measure
the resistance between the U and V, V and W, and W and U
phases of the motor connector (with five conductors) and check
that each phase are balanced (within a permissible dispersion
range of ±20%).
*2. Measurement of signal wire connector.
Remove the X2A connector and measure the resistance between
GND and V
CC, HW, HV, or HU terminals of the motor connector
(with five conductors).
Turn on the power.
Remove the signal connector
from the fan motor and check
the resistance (*2).
Between V
CC
and GND
terminals, and between GND
and H
W
, H
V
, or H
U
terminals
are short-circuited.
YES
NO
The HAP
lamp of the indoor PCB
(A1P) blinks and the HAP
lamp of the fan PCB
(A2P) is off.
YES
NO
Replace the fan motor.
Replace the fan PCB
(A2P).
5 Gray
4 Pink
3 Orange
2 Blue
1 Yellow
GND
Vcc
Hw
H
V
HU
5 Red
4
3 White
2
1 Black
U
V
W
Connector power wire use (X1A) Connector signal wire use (X2A)