Daikin RXQ24PHY1 [270/394] Troubleshooting

Daikin RXQ24PHY1 [270/394] Troubleshooting
Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 259
Troubleshooting
Power ON
YES
NO
NO
NO
NO
YES
YES
YES
Is the micro controller
normal monitor (green) of
the A1P blinking?
The A4P or A8P
does not blink.
The LC malfunction recurs.
The A3P, A4P, and
A8P do not blink.
This is not LC.
Recheck for the
malfunction code.
A3P: Replace the
inverter PCB.
If the PCB replaced is
badly damaged, the
compressor is likely to
get faulty. To make
sure, recheck the
compressor.
A4P/A8P: Replace the
fan driver
PC board.
Replace the control
PC board.
End of measures:
The malfunction may
temporarily result from
on-site causes.
Causes:
Instantaneous power
failure (open phase),
noises, or else.
A
Check 10 or more seconds after
the power supply is turned ON.