Daikin RXYQ16P7YLK — основы настройки групповых адресов в DIII-NET [33/405]

Daikin REYQ168PATJ [33/405] You cannot set a same group address on a same diii net you do not need to set a group address to a child unit in a remote control group in case power proportional distribution is used you need to set a group address to a child unit in a remote control group as well
5.1 Group Address 29
ED721208 Fundamental of DIII-NET
2
5. Group and Zone
5.1 Group Address
• Set a group address to a device to be connected to DIII-NET.
• The range of addresses to be set is 64 types as shown below.
• You cannot set a same group address on a same DIII-NET.
• You do not need to set a group address to a child unit in a remote control group.
- In case power proportional distribution is used, you need to set a group address to a child unit in a remote control
group as well.
1-00~1-15 ······16 types
Total 64 types
2-00~2-15 ······16 types
3-00~3-15 ······16 types
4-00~4-15 ······16 types
Normal centralized address setting Group address setting in case power
proportional distribution is used
1-00 1-01
1-031-02
1-00 1-03
1-071-05
1-01 1-02
1-04 1-06