7 English
Outdoor unit multi connection piping kit and
Refrigerant branch kit selection
Pipe size selection
•
Refrigerant branch kits can only be used with R410A.
•
When multi outdoor system are installed, be sure to use the
special separately sold Outdoor unit multi connection piping
kit. (BHFP26P90 · 136).
(For how to select the proper kit, follow the table at right.)
•
Never use BHFP26M90 · 135, BHFP22M90 · 135P for M
type of this series or T joint (field supplyed).
How to select the REFNET joint
Piping between outdoor unit (*2) and refrigerant branch kit (part A)
How to select the REFNET header
When using REFNET joint at the first branch counted from the outdoor unit side,
choose from the following table in accordance with the outdoor unit capacity type.
(Example : REFNET joint A)
Choose from the following table in accordance with the outdoor unit system capacity type.
Piping between outdoor unit multi connection piping kit and outdoor unit (part C)
Temper grade and wall thickness for pipes
(Temper grade, O type and 1/2H type indicate the material type specified in JIS H 3300.)
Choose from the following table in accordance with the capacity type of
the outdoor unit connected.
Piping between outdoor unit multi connection piping kits (part B)
Choose from the following table in accordance with the total capacity of all
the outdoor units connected upstream.
Choose from the following table in accordance with the total capacity index of all
the indoor units connected below the REFNET header.
250 type indoor unit can not be connected below the REFNET header.
How to select the outdoor unit multi connection piping kit
(This is required when the system is multi outdoor unit system.)
Choose from the following table in accordance with the number of outdoor units.
Choose the REFNET joints other than the first branch from the following table in accordance
with the total capacity index of all the indoor units connected below the REFNET joint.
Outdoor unit capacity type
8,10HP type
12~22HP type
24HP type ~
Indoor unit total capacity index
x < 200
200 ≤ x < 290
290 ≤ x < 640
640 ≤ x
Refrigerant branch kit name
KHRP25A33T
KHRP25A72T+KHRP25M72TP
KHRP25A73T+KHRP25M73TP
3 pipes
KHRP25A22T
KHRP25A33T
KHRP25A72T+KHRP25M72TP
KHRP25A73T+KHRP25M73TP
2 pipes
KHRP26A22T
KHRP26A33T
KHRP26A72T
Refrigerant branch kit name
Indoor unit total capacity index
x < 200
200 ≤ x < 290
290 ≤ x < 640
640 ≤ x
Number of outdoor unit
2 units
3 units
Connecting piping kit name
BHFP26P90
BHFP26P136
3 pipes
KHRP25M33H
KHRP25M72H+KHRP25M72HP
KHRP25M73H+KHRP25M73HP
2 pipes
KHRP26M22H or KHRP26M33H
KHRP26M33H
KHRP26M72H
KHRP26M73H+KHRP26M73HP
Refrigerant branch kit name
Example for indoor units
connected downstream
Example REFNET joint C : Indoor units 5 + 6 + 7 + 8
Example REFNET joint B : Indoor units 7 + 8
Example REFNET header : Indoor units 1 + 2 + 3 + 4 + 5 + 6
Example REFNET header :
Indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
The thickness of the pipes in the table shows
the requirements of Japanease High Pressure
Gas Controll low. (As of Jan. 2003)
The thickness and material shall be selected in
accordance with local code.
<In case of single outdoor unit system>
<In case of multi outdoor unit system>
Equalizer pipe
(part D)
Piping between outdoor unit
multi connection piping kit
and outdoor unit (part C)
Piping between outdoor unit multi
connection piping kits (part B)
Piping between outdoor unit and
refrigerant branch kit (part A)
Piping between outdoor unit and
refrigerant branch kit (part A)
Outdoor unit
Independent
unit 1
Independent
unit 2
Independent
unit 3
Outdoor unit
capacity type
8HP type
10HP type
12HP type
14,16HP type
18HP type
20,22HP type
24HP type
26~34HP type
36HP type
38~48HP type
Piping size (O. D.)
Piping size (O. D.)
Suction gas pipe
φ19.1
φ22.2
φ28.6
φ34.9
φ41.3
HP/LP gas pipe
φ15.9
φ19.1
φ22.2
φ28.6
φ34.9
Liquid pipe
φ9.5
φ12.7
φ15.9
φ19.1
Outdoor unit
capacity type
8,10HP type
12HP type
14,16HP type
Copper tube O. D.
Temper grade
Wall thickness
(Min. requirement)
Suction gas pipe
φ22.2
φ28.6
HP/LP gas pipe
φ19.1
φ22.2
Liquid pipe
φ9.5
×
0.8
φ12.7
φ
6.4
0.80
φ
9.5
0.80
φ
12.7
0.80
φ
15.9
0.99
φ
19.1
0.80
φ
22.2
0.80
φ
25.4
0.88
φ
28.6
0.99
φ
31.8
1.10
φ
34.9
1.21
φ
38.1
1.32
φ
41.3
1.43
Piping between refrigerant branch kits
Piping between refrigerant branch kit and BS unit
Piping between BS unit and refrigerant branch kit
Choose from the following table in accordance with the total capacity type of all the
indoor units connected downstream.
Piping between refrigerant branch kit, BS unit and indoor unit
Equalizer pipe (part D) (multi outdoor unit system only)
Match to the size of the connection piping on the indoor unit.
*1 Connection piping must not exceed the refrigerant Piping size between outdoor
unit and refrigerant branch kit (part A).
*2 When selecting 2 pipes line (gas pipe and liquid pipe), use Suction gas pipe
column for gas pipe and Liquid pipe column for liquid pipe.
Indoor capacity index
x < 150
150 ≤ x < 200
200 ≤ x < 290
290 ≤ x < 420
420 ≤ x < 640
640 ≤ x < 920
920 ≤ x
Suction gas pipe
φ15.9
φ19.1
φ22.2
φ28.6
φ34.9
φ41.3
HP/LP gas pipe
φ12.7
φ15.9
φ19.1
φ28.6
Liquid pipe
φ9.5
φ12.7
φ15.9
φ19.1
Indoor unit capacity type
20 · 25 · 32 · 40 · 50 type
63 · 80 · 100 · 125 type
200 type
250 type
gas pipe
φ12.7
φ15.9
φ19.1
φ22.2
Liquid pipe
φ6.4
φ9.5
Piping size (O. D.) φ19.1
(unit : mm)
(unit : mm)
Piping size (O. D.)
(unit : mm)
Piping size (O. D.)
(unit : mm)
(unit : mm)
1/2H type
O type
01_EN_3P201178-3B.fm Page 7 Friday, May 18, 2007 5:21 PM
Содержание
- Installation manual 1
- System air conditioner 1
- Daikin industries ltd 2
- En60335 2 40 2
- Low voltage 2006 95 ec machinery safety 98 37 ec electromagnetic compatibility 89 336 eec 2
- Noboru murata manager quality control department 1st of april 2007 2
- P177868 1c 2
- Umeda center bldg 4 12 nakazaki nishi 2 chome kita ku osaka 530 8323 japan 2
- Figure 1 3
- Figure 10 3
- Figure 11 figure 12 3
- Figure 13 3
- Figure 2 3
- Figure 3 3
- Figure 4 3
- Figure 5 3
- Figure 6 3
- Figure 7 3
- Figure 8 3
- Figure 9 3
- Figure 14 4
- Figure 15 4
- Figure 17 figure 18 4
- Figure 19 4
- Figure 20 4
- Figure 21 figure 23 4
- Figure 22 4
- Figure 24 5
- Figure 25 5
- Figure 26 figure 27 5
- Figure 28 5
- Figure 29 figure 30 5
- Figure 31 5
- Figure 32 5
- 1 safety considerations 6
- Contents 6
- English 6
- First of all 6
- Installation manual 6
- 1 combination 7
- 2 special notice of product 7
- 3 disposal requirements 7
- English 2 7
- Introduction 7
- 2 standard supplied accessories 8
- 3 option accessory 8
- 4 technical and electrical specifications 8
- 5 main components 8
- English 8
- Selection of location 8
- 1 selection of piping material and refrigerant branching kit 9
- 2 protection against contamination when installing pipes 9
- English 4 9
- Inspecting and handling the unit 9
- Placing the unit 9
- Refrigerant piping 9
- 3 pipe connection 10
- 4 connecting the refrigerant piping 1 10
- English 10
- 5 example of connection 11
- Allowable height difference 11
- Between first outdoor unit multi connection piping kit and outdoor unit in case of multi system 11
- Between outdoor and indoor units between indoor and indoor units between outdoor and outdoor units 11
- English 6 11
- Example of connection connection of 8 indoor units 11
- Maximum allowable length 11
- English 12
- Outdoor unit multi connection piping kit and refrigerant branch kit selection 12
- Pipe size selection 12
- 27 48 27 kg 13
- 50 0 6 1 0 8 3 0 2 156 0 59 20 0 22 1 2 3 0 13
- A b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m 13
- A b u r c n s t o p 13
- English 8 13
- How to calculate the additional refrigerant to be charged 13
- If available on the site use this size otherwise it can not be increased 13
- Increase the pipe size as follows 13
- Indoor units 1 8 13
- Outdoor unit refnet joint a g 13
- Required conditions example drawings 13
- Round off in units of 0 kg 13
- The farthest indoor unit 8 the nearest indoor unit 1 13
- Φ 9 φ 12 φ 12 φ 15 φ 15 φ 19 φ 19 φ 22 φ 22 φ 25 φ 28 φ 31 φ 34 φ 38 13
- 1 power circuit safety device and cable requirements 14
- 2 wiring connection example for whole system 14
- 3 leading wire procedure 14
- English 14
- Field wiring 14
- 4 transmission wiring connection procedure 15
- 5 power wiring connection procedure 15
- 6 procedure for wiring inside units 15
- Crimp style terminal 15
- Cup washer 15
- Cut out section 15
- English 10 15
- Power wire crimp style terminal 15
- Resin hook 15
- Terminal block crip style terminal wire narrow wire thick 15
- Air tight test and vacuum drying 16
- English 16
- Pipe insulation 16
- R410a label 16
- 1 before working 17
- Additional refrigerant charge and check operation 17
- Checking of device and instal lation conditions 17
- Checking of device and installation conditions 17
- English 12 17
- Stand the tank upright and charge the siphon pipe goes all the way inside so the tank does not need be put upside down charge in liquid form 17
- Stand the tank upside down and charge 17
- 2 1 procedure of adding refrigerant charging 1 18
- 2 procedure of adding refrigerant charging and check operation 18
- English 18
- H h i h h h h 18
- J h h h h h h 18
- J h h h i h i 18
- J h h i h h h 18
- J h j h j j h 18
- 2 2 procedure of check operation 19
- English 14 19
- J h h i h h h h h 19
- 1 before test run 20
- 2 test run 20
- 3 checks after test run 20
- Caution for refrigerant leaks 20
- English 20
- Onsite settings 20
- Test run 20
- English 16 21
Похожие устройства
- Daikin REYQ12PY1 Руководство по вводу в эксплуатацию
- Daikin REYQ14PY1 Спецификация
- Daikin REYQ12PY1 Сервис мануал
- Daikin REYQ14PY1 Руководство по вводу в эксплуатацию
- Daikin REYQ16PY1 Руководство по эксплуатации
- Daikin REYQ14PY1 Сервис мануал
- Daikin REYQ16PY1 Инструкция по монтажу
- Daikin REYQ18PY1 Руководство по эксплуатации
- Daikin REYQ16PY1 Спецификация
- Daikin REYQ18PY1 Инструкция по монтажу
- Daikin REYQ16PY1 Руководство по вводу в эксплуатацию
- Daikin REYQ18PY1 Спецификация
- Daikin REYQ16PY1 Сервис мануал
- Daikin REYQ18PY1 Руководство по вводу в эксплуатацию
- Daikin REYQ18PY1 Сервис мануал
- Daikin REYQ20PY1 Руководство по эксплуатации
- Daikin REYQ22PY1 Руководство по эксплуатации
- Daikin REYQ20PY1 Инструкция по монтажу
- Daikin REYQ22PY1 Инструкция по монтажу
- Daikin REYQ20PY1 Спецификация