Troubleshooting by Indication on the Remote Controller SiUS34-801A_b
346 Troubleshooting
3.6 A9 Indoor Unit: Electronic Expansion Valve
Malfunction / Dust Clogging
Remote
Controller
Display
A9
Applicable
Models
FXFQ
Method of
Malfunction
Detection
Check coil condition of electronic expansion valve by using microcomputer.
Check dust clogging condition of electronic expansion valve main body by using microcomputer.
Malfunction
Decision
Conditions
Pin input for electronic expansion valve coil is abnormal when initializing microcomputer.
Either of the following conditions is seen/caused/ occurs while the unit stops operation.
Temperature of suction air (R1T) – temperature of liquid pipe of heat exchanger (R2T)>46.4°F.
Temperature of liquid pipe of heat exchanger (R2T) shows fixed degrees or below.
Supposed
Causes
Defective drive of electronic expansion valve
Defective PC board of indoor unit
Defective relay cables